Loading...
0987 OFFICIAL RECORD 2009 International Building Code and 2008 National Electrical Code ORDINANCE NO. 987 AN ORDINANCE ADOPTING THE 2009 EDITION OF THE INTERNATIONAL BUILDING CODE, REGULATING THE ERECTION, CONSTRUCTION, ENLARGEMENT, ALTERATION, REPAIR, MOVING, REMOVAL, DEMOLITION, CONVERSION, OCCUPANCY, EQUIPMENT, USE, HEIGHT, AREA AND MAINTENANCE OF ALL BUILDINGS OR STRUCTURES, EXCEPT ONE- AND TWO- FAMILY DWELLINGS AND MULTIPLE SINGLE - FAMILY DWELLINGS (TOWNHOUSES), AND INCLUDING THE NATIONAL ELECTRICAL CODE AS REFERENCED HEREIN, IN THE CITY OF SOUTHLAKE; PROVIDING FOR THE ADOPTION OF LOCAL AMENDMENTS THERETO; PROVIDING FOR RECORDING OF SUCH CODE AS A PUBLIC RECORD;_ PROVIDING THAT THIS ORDINANCE SHALL BE CUMULATIVE OF ALL ORDINANCES; PROVIDING A SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY FOR VIOLATIONS HEREOF; PROVIDING A SAVINGS CLAUSE; PROVIDING FOR PUBLICATION IN PAMPHLET FORM; PROVIDING FOR PUBLICATION IN THE OFFICIAL NEWSPAPER; AND PROVIDING AN EFFECTIVE DATE. WHEREAS, the City of Southlake is a home rule city acting under its charter adopted by the electorate pursuant to Article XI, Section 5 of the Texas Constitution and Chapter 9 of the Local Government Code; and WHEREAS, the City Council of the City of Southlake deems it necessary to adopt this ordinance providing minimum standards to safeguard the health, property, and welfare of the citizens of Southlake by regulating and controlling the use, occupancy, maintenance, repair, design, construction and quality of materials for buildings and structures within the City. WHEREAS, The /CC ELECTRICAL CODE is no longer published as a separate document but the electrical provisions are included in Appendix K, the Electrical Code is being adopted as a part of this ordinance. WHEREAS, beginning in the spring of 2010, NCTCOG's Regional Codes Coordinating Committee (RCCC) and its four advisory boards conducted 20 open review meetings over an 8 -month period to review the 2009 editions of the International Codes and to develop regional amendments. Their review and recommendations were completed and endorsed by NCTCOG's Executive Board in October 2010. Now NCTCOG encourages jurisdictions in North Central Texas to adopt the 2009 International Building Code along with its respective regional amendments.: NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF SOUTHLAKE, TEXAS: SECTION 1 That the International Building Code, 2009 Edition, published by the International Code Council, including the standards referenced therein, including Appendix Chapters A, C, F, G, H, I , J and K are hereby adopted as the Building Code of the City of Southlake regulating the erection, construction, enlargement, alteration, repair, moving, removal, demolition, conversion, occupancy, equipment, use, height, area and maintenance of all buildings or structures, except one- and two- family dwellings and multiple single family dwellings (townhouses), in the City of Southlake. True and correct copies of these documents are attached as Exhibit "A." SECTION 2 That the 2009 International Building Code, as adopted herein, is hereby amended as provided in Exhibit "B" incorporated herein and attached hereto for all purposes of this ordinance. The City of Southlake, Texas may from time to time determine that additional local modifications to the Building Code are necessary and appropriate to meet the unique needs of the City of Southlake, Texas. To effectuate these local modifications, the City Council shall enact individual ordinances amending this Ordinance, fully setting forth the change to be made in the Building or Electrical Code. These amendments shall be consolidated as Exhibit "B" to this Ordinance. SECTION 3 The material contained in Exhibits "A" and "B" to this ordinance shall not be included in the formal municipal codification of ordinances, but shall be maintained as a public record in the office of the City Secretary and will be available for public inspection and copying during regular business hours. SECTION 4 This ordinance shall be cumulative of all provisions of ordinances of the City of Southlake, Texas, except where the provisions of this ordinance are in direct conflict with the provisions of such ordinances, in which event the conflicting provisions of such ordinances are hereby repealed. This ordinance is intended to replace the following: 1. Ordinance 930, as amended, the 2006 International Building Code. 2. Ordinance 933, as amended, the 2006 ICC Electrical Code. This ordinance is not intended to amend or replace the following: 1. Ordinance 480, as amended, the Zoning Ordinance. 2. Ordinance 483, as amended, the Subdivision Ordinance. 3. Ordinance 557, as amended, Exterior Masonry Construction Requirements 4. Ordinance 568, as amended, Contractor's Licensing Ordinance 6. Ordinance 506 -A, as amended, the Sign Ordinance SECTION 5 It is hereby declared to be the intention of the City Council that the phrases, clauses, sentences, paragraphs, and sections of this ordinance are severable, and if any phrase, clause sentence, paragraph or section of this ordinance shall be declared unconstitutional by the valid judgment or decree of any court of competent jurisdiction, such unconstitutionality shall not affect any of the remaining phrases, clauses, sentences, paragraphs and sections of this ordinance, since the same would have been enacted by the City Council without the incorporation in this ordinance of any such unconstitutional phrase, clause, sentence, paragraph or section. SECTION 6 Any person, firm or corporation who violates, disobeys, omits. neglects or refuses to comply with or who resists the enforcement of any of the provisions of this ordinance shall be fined not more than Two Thousand Dollars ($ 2,000.00) for any violation involving zoning, fire safety or public health and sanitation, including dumping or refuse, and shall be fined not more than five hundred dollars ($500) for any other violation of this ordinance. Each day that a violation is permitted to exist shall constitute a separate offense. SECTION 7 All rights and remedies of the City of Southlake are expressly saved as to any and all violations of the provisions of any ordinances affecting the regulation and control of the use, occupancy, maintenance, repair, design, construction and quality of materials for buildings and structures within the City which have accrued at the time of the effective date of this ordinance; and, as to such accrued violations and all pending litigation, both civil and criminal, whether pending in court or not, under such ordinances, same shall not be affected by this ordinance but may be prosecuted until final disposition by the courts. SECTION 8 The City Secretary of the City of Southlake is hereby authorized to publish this ordinance in book or pamphlet form or on the internet for general distribution among the public, and the operative provisions of this ordinance as so published shall be admissible in evidence in all courts without further proof than the production thereof. SECTION 9 The City Secretary of the City of Southlake is hereby directed to publish in the official newspaper of the City of Southlake or as authorized by law, the caption, penalty clause, publication clause and effective date of this ordinance one time within ten days after passage of this ordinance, as required by Section 3.13 of the Charter of the City of Southlake. SECTION 10 This ordinance shall be in full force and effect from and after its passage and publication as required by law. APPROVED ON FIRST READING THIS 25 DAY OF JANUARY, 2011. MAYOR ATTEST: o ri1 • CITY SECRETARY ''•, •• " "' * *,•`' APPROVED ON SECOND READING THIS 15 DAY OF FEBRUARY, 2011. MAYOR ATTEST: , ,,,,,,,,,,,,,,,,, vp w_ \Li • • CITY SECRETARY s ,o APPR i • I TO FO M D LEGALITY: CITY ATTORNEY PUBLISHED: 18 ORRUARY 2011 EFFECTIVE: 1 APRIL, 2011 EXHIBIT A 2009 International Residential Code Complete Edition Located in the Office of the City Secretary, City of Southlake, Texas. EXHIBIT "B" LOCAL AMENDMENTS TO THE 2006 INTERNATIONAL BUILDING CODE The following sections, paragraphs, and sentences of the 2009 International Building Code are hereby amended as follows: Standard type is text from the IBC. Underlined type is text inserted. Lined through type is deleted text from IBC. A double asterisk ( * *) at the beginning of a section identifies an amendment carried over from the 2006 edition of the code and a triple asterisk ( * * *) identifies a new or revised amendment with the 2009 code. * *Section 101.1; Insert city name as follows: 101.1 Title. These regulations shall be known as the Building Code of The City of Southlake, Texas hereinafter referred to as this code." * *Section 101.4; change to read as follows: 101.4 Referenced codes. The other codes listed in Sections 101.4.1 through 101.4.7 and referenced elsewhere in this code, when specifically adopted, shall be considered part of the requirements of this code to the prescribed extent of each such reference. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. (Reason: Legal wording to recognize locally adopted codes and amendments adopted with referenced codes.) ** *Section 101.4.7; add the following: 101.4.7 Electrical. The provisions of the Electrical Code shall apply to the installation of electrical systems, including alterations, repairs, replacement, equipment, appliances, fixtures, fittings and appurtenances thereto. (Reason: This was dropped when ICC quit publishing the ICC Electrical Code, but the Electrical Code still should be referenced regardless of how it is adopted.) * ** Section 103 and 103.1 amend to insert the department name: SECTION 103 Department of Planning & Development Services, Building Inspection Division 103.1 Creation of a code enforcement agency. The Planning & Development Services Department , Building Inspection division is hereby created and the official in charge thereof shall be known as the building official. (Reason: To correlate the department name with what it is actually called in this city.) * *Section 105.1; change to read as follows: 105.1 Required. Any owner or authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure, to excavate or change the grade of any property, or to erect, install, enlarge, alter, repair, remove, convert or replace any electrical, gas, mechanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done, shall first make application to the building official and obtain the required permit. For excavation or grading permits see appendix chapter J as adopted. (Reason: Consistent with previous edition amendment, to provide means to regulate grading affecting other properties.) ** Section105.2: amend item 2 under Building and Electrical as follows; Building: 1. (No change) 2. Fences not over 6 feet(1829 mm) high) except masonry fences or pool barriers. 3. — 9. (No change) (Reason: Consistent with current policy and to match IRC Ordinance.) Electrical: See also section K 103.2 Repairs and maintenance: Minor repair work, including the replacement of lamps or the connection of approved portable electrical equipment to approved permanently installed receptacles. Repair or replacement of fixed motors, transformers or fixed approved appliances of the same type and rating in the same location; Repair or replacement of current - carryinq parts of any switch, contactor or control device; Reinstallation of attachment plug receptacles, but not the outlets therefor; Repair or replacement of any overcurrent device of the required capacity in the same location; Taping joints. Radio and television transmitting stations: The provisions of this code shall not apply to electrical equipment used for radio and television transmissions, but do apply to equipment and wiring for a power supply and the installations of towers and antennas. Temporary testing systems: A permit shall not be required for the installation of any temporary system required for the testing or servicing of electrical equipment or apparatus Other exemptions: Temporary decorative lighting; Removal of electrical wiring; Electrical wiring, devices, appliances, apparatus or equipment operating at less than 25 volts and not capable of supplying more than 50 watts of energy; Low - energy power, control and signal circuits of Class II and Class III as defined in the Electrical Code. (Reason: Added language from former UAC is more specific.) * *Section 105.3.1 and 105.3.2; change to read as follows: 105.3.1 Action on application. The building official shall examine or cause to be examined applications for permits and amendments thereto within a reasonable time after filing, but not less than required by state law. If the application or the construction documents do not conform to the requirements of pertinent laws, the building official shall reject such application in writing, stating the reasons therefor. If the building official is satisfied that the proposed work conforms to the requirements of this code and laws and ordinances applicable thereto, the building official shall issue a permit therefor as soon as practicable. 105.3.2 Time limitation of application. An application for a permit for any proposed work shall be deemed to have been abandoned -1-69 45 days after the date of filing, unless such application has been pursued in good faith or a permit has been issued; except that the building official is authorized to grant one or more extensions of time for additional periods not exceeding 98 45 days each. A good faith effort shall be deemed to be demonstrated by response to city comments, requests for additional information or purchasing of permit within 45 days of notice by the city. The extension shall be requested in writing and justifiable cause demonstrated. (Reason: to call attention to state limitations on the city and place similar limitations on applicants in order to reduce buildup of backlog of plans and applications.) * *Section 107.2.5; change to read as follows; 107.2.5 Site plan. The construction documents submitted with the application for permit shall be accompanied by a site plan showing to scale the size and location of new construction and existing structures on the site, distances from lot lines, the established street grades and the proposed finished grades and, as applicable, flood hazard areas, floodways, and design flood elevations; and it shall be drawn in accordance with an accurate boundary line survey. Plans shall also show proposed erosion control and tree protection measures in accordance with recognized standards and any additional information as required by other ordinances. In the case of demolition, the site plan shall show construction to be demolished and the location and size of existing structures and construction that are to remain on the site or plot. The building official is authorized to waive or modify the requirement for a site plan when the application for permit is for alteration or repair or when otherwise warranted. (Reason: Erosion control and tree preservation are required by other ordinances; this reference calls those requirements to the attention of the designer.) * *Section 109.7; add. 109.7 Re- inspection Fee. A fee as established by city council resolution may be charged when: 1.Work called for inspection is incomplete; 2. Building address and /or permit card is not clearly posted; 3.City approved plans are not on the iob site available to the inspector; 4.The building is locked or work otherwise not available for inspection when called; 5.Items noted for correction on initial inspection and not corrected upon re- inspection. 6.The original red taq has been removed from the iob site and /or, 7.Violations exist on the property including failure to maintain erosion control, trash control or tree protection. Any re- inspection fees assessed shall be paid before any more inspections are made on that job site. (Reason: This fee is not a fine or penalty but is designed to compensate for time and trips when inspections are called for when not ready.) * *Section 109.8 and 109.9; add: 109.8 Investigation Fee. Work without a permit. 109.8.1 Investigation. Whenever work for which a permit is required by this code has been commenced without first obtaining a permit, a special investigation shall be made before a permit may be issued for such work. 109.8.2 Fee. An investigation fee, in addition to the permit fee, shall be collected whether or not a permit is subsequently issued. The investigation fee shall be equal to the amount of the permit fee required by this code or the city fee schedule as applicable. The payment of such investigation fee shall not exempt the applicant from compliance with all other provisions of either this code or the technical codes nor from penalty prescribed by law. 109.9 Unauthorized cover up fee. 109.9.1 Any work concealed without first obtaining the required inspection in violation of section 109 shall be assessed a fee as established by the city fee schedule. (Reason: This fee is not a fine or penalty but is designed to compensate for time and to remove incentive to attempt to evade permits and code compliance. Language taken from former Uniform Administrative Code.) ** *Section 111.1; add 111.1.1 to read as follows: 111.1.1 Ordinance Inspection. An Ordinance Inspection shall be required upon chanqe of occupant or owner when a billing or meter change occurs for gas water or electrical services and a Certificate of Occupancy or building permit is not otherwise required. A change of occupant for a use with a different parking requirement as determined by the Southlake Zoning Ordinance shall also require an Ordinance Inspection. Exceptions Individually metered dwellings and dwelling units. Ordinance inspections shall be requested on a form provided by the Building Official. The building official shall classify the building occupancy group and construction type according to this code and the zoning classification according to the Zoning Ordinance. Ordinance Inspections may be used for any miscellaneous inspection upon request of the owner whether required by other codes and ordinances or desired by individuals. After the Building Official inspects the building or portion thereof and finds no violations of this code or other laws enforced by the department, the building official shall issue a Certificate of Inspection that contains the following: 1 The inspection permit number. 2 The address of the structure. 3 The name and address of the owner. 4 A description of that portion of the structure for which the certificate is issued. 5 A statement that the described portion of the structure has been inspected for compliance with the requirements of this code for the occupancy and division of occupancy and the use for which the proposed occupancy is classified. 6 The name of the building official. 7 The edition of the code under which the permit was issued. 8 The use and occupancy in accordance with the provisions of Chapter 3. 9 The type of construction as defined in Chapter 6. 10 If an automatic sprinkler system is provided whether the sprinkler system is required. 11 Any special stipulations and conditions of the inspection permit. 12 The zoning district. (Reason: The IBC as written only requires a Certificate of Occupancy for new buildings remodeled buildings or buildings where the occupancy classification changes. Previously by amendment Southlake has also required a Certificate of Occupancy be issued for a change in the business occupying the property even if the change was still within the same occupancy group. This amendment would exempt simple tenant changes other than medical occupancies where there is no occupancy change only in cases where there is no change in billing of metered utilities for electricity gas or water. Typical bills paid spaces rented for executive suites or mini warehouses would not require an Ordinance Inspection. This also provides an instrument to allow miscellaneous inspections not required by ordinance upon request.) * *Section 113.1; Amend as follows: SECTION 113 BOARD OF APPEALS R113.1 General. In order to hear and decide appeals of orders, decisions or determinations made by the building official relative to the application and interpretation of this code, there shall be and is hereby created a board of appeals. The board of appeals shall be appointed by the governing body and shall hold office at its pleasure. The board shall adopt rules of procedure for conducting its business, and shall render all decisions and findings in writing to the appellant with a duplicate copy to the building official. The Building Board of Appeals as established by ordinance 622, as amended, shall constitute the Board of Appeals referenced in this code. (Reason: recognize appeal board previously established by ordinance.) ** *Section 202; change the following definitions to read as follows: [B] Ambulatory Health Care Facility - Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing or similar care on a less than 24 -hour basis to individuals who are rendered incapable of self - preservation. This group shall include but not be limited to the following: - Dialysis centers - Sedation dentistry - Surgery centers - Colonic centers - Psychiatric centers (Reason: to clarify the range of uses included in the definition. [Explanatory note related to Ambulatory health care facilities: This group of uses as defined in chapter 2 includes a medical or dental office where persons are put under for dental surgery or other services. Section 903.2.2 will now require such uses to be sprinkled if on other than the floor of exit discharge or if four or more persons are put under on the level of exit discharge. Recommend (1.) jurisdictions document any pre existing non conforming conditions prior to issuing a new C of 0 for a change of tenant and, (2.) On any medical or dental office specify on C of 0 specify the maximum number of persons permitted to be put under general anesthesia.] It is recommended that before a Certificate of Occupancy is issued, a letter of intended use shall be included and a C of 0 documenting the maximum number of care recipients incapable of self preservation allowed.) HIGH -RISE BUILDING is a building having floors used for human occupancy located more than 7-5 55 feet (16 764 mm) above the lowest level of fire department vehicle access. (Reason: To define high -rise, as it influences sprinkler requirement thresholds based on the fire fighting capabilities of the jurisdiction.) * *Section 304.1; add the following to the list of occupancies: Fire stations Police stations with detention facilities for 5 or less (Reason: Clarify classification of these uses.) ** *Section 307.1; add the following to Exception 4: 4. Cleaning establishments... {language unchanged }. See also IFC chapter 12, Dry Cleaning Plant provisions. (Reason: To call attention to detailed requirements in the Fire Code.) * *Section 403.1, exception #3; change to read as follows: 3. Open air portions of Bbuildings with an occupancy in Group A -5 in accordance with Section 303.1 (Reason: To clarify enclosed portions are not exempt.) * *Section 403.3, exception #2; delete. (Reason: To provide adequate fire protection to enclosed areas.) * *Section 404.1.1; amend definition of Atrium as follows: ATRIUM. An opening connecting twe three or more stories ... {Balance remains unchanged} (Reason: Code is not consistent. Section 1022 permits unenclosed two story stairways under certain circumstances.) * *Section 404.5; delete exception. (Reason: Consistent with amended atrium definition.) * *Section 406.1.2; add item # 3 to read as follows: 3. A separation is not required between a Group R -2 and U carport provided that the carport is entirely open on all sides and that the distance between the two is at least 10 feet (3048 mm) (Reason: Simplifies the fire separation distance and eliminates the need to obtain opening information on existing buildings when adding carports in existing apartment complexes. Consistent with legacy codes in effect in region for years and no record of problems with car fires spreading to apartments as a result.) ** *Section 406.2.7 Change reference section as follows: 406.2.7 Mixed Separation. Parking garages shall be separated from other occupancies in accordance with Section 5084 508. (Reason: Section 508 provides a more complete range of options for separation. Parking garages are sometimes an incidental use and sometimes a separate occupancy.) * *Section 406.6.1; add a second paragraph to read as follows: This occupancy shall include garages involved in servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement and other such non -major repair. (Reason: Correction to distinguish that service work is a repair garage as well to correspond with definition in the IFC.) * *Section 501.2; Amend to read as follows: 501.2 Address numbers. Buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. • - - . _ - _ -e' _ ' - - - • nm ) See Ordinance # 441 for specific addressing requirements. (Reason: Call attention to addressing ordinance. Also matches amendment to IFC 505.1.) ** *Section 506.2.2; add a sentence to read as follows: In order to be considered as accessible, if not in direct contact with a street or fire lane, a minimum 10 -foot wide pathway from the street or approved fire lane must be provided. (See International Fire Code Section 503.1.1 for hose lay measurement pathway requirements.) (Reason: To define what is considered accessible. Consistent with regional amendment to IFC 503.1.1.) ** *Section 508.2.5, add a sentence at the end of paragraph: 508.2.5 Separation of Incidental accessory occupancies. (Sentence remains unchanged.) An incidental accessory occupancy shall be classified in accordance with the occupancy of that portion of the building in which it is located. (Reason: To clarify incidental accessory occupancies classified as a portion of the building they are located.) * *Section 708.2; Exception 7; amend item 7.2, delete items 7.4 and 7.5 and renumber as follows: 7. In other than Groups 1 -2 and 1 -3, a shaft enclosure is not required for a floor opening or an air transfer opening that complies with the following: 7.1. Does not connect more than two stories. 7.2. Is not part of the required means of egress system, except as permitted in Section 1022.1. 7.3. Is not concealed within the building construction of a wall or floor /ceiling assembly. r • • • 7.5. Is not open to a corridor on noncprinklered floors in any occupancy. 7.6. 7.4 Is separated from floor openings and air transfer openings serving other floors by construction conforming to required shaft enclosures. 7.5 Is limited to the same smoke compartment. (Reason: To be consistent with regionally accepted practices and legacy codes.) * *Section 903.1.1; amend to read as follows: [F] 903.1.1 Alternative protection. Alternative automatic fire - extinguishing systems complying with Section 904 shall be permitted in lieu of addition to automatic sprinkler protection where recognized by the applicable standard and approved by the fire code official. (Reason: Such alternative systems do not provide the reliability of automatic sprinkler protection in general. An applicant could pursue an Alternate Method request to help mitigate the reliability issues with these alternative systems with the fire code official if so desired. This also meets with local practices in the region.) ** *Section 903.2; add the following: 903.2 Where required. {Language unchanged)... Automatic Sprinklers shall not be installed in elevator machine rooms, elevator machine spaces, and elevator hoistways. Storage shall not be allowed within the elevator machine room. Signage shall be provided at the entry doors to the elevator machine room indicating "ELEVATOR MACHINERY— NO STORAGE ALLOWED." Exception: {Delete Exception). (Reason: Firefighter safety. This amendment eliminates the shunt trip requirement of the International Building Code Section 3006.5 for the purpose of elevator passenger and firefighter safety. This amendment is contingent on the Building Code amendment eliminating the Exceptions to Section 3006.4, such that passive fire barriers for these areas are maintained. This also meets with local practices in the region.) * *Section 903.2.9.3; Add section to read as follows: [F] 903.2.9.3. Self- service storage facility. An automatic sprinkler system shall be installed throughout all self - service storage facilities. Exception: One -story self - service storage facilities that have no interior corridors, with a one -hour fire barrier wall installed between every storage compartment. (Reason: Fire departments are unable to inspect these commercial occupancies and are unaware of the contents being stored.) * *Section 903.2.11; amend 903.2.11.3 and add 903.2.11.7, 903.2.11.8, and 903.2.11.9 as follows: [F] 903.2.11.3 Buildings 66 35 feet or more in height. An automatic sprinkler system shall be installed throughout buildings with a floor level, other than penthouses in compliance with Section 1509, • - • • - - • • • • - - e _ . ! e "e - that is located 5.5 35 feet (16 764 10 668mm) or more above the lowest level of fire department vehicle access. Exceptions: 1. Airport control towers. 2. Open parking structures in compliance with Section 406.3 of the IBC. 3. Occupancics in Group F 2. (Reason: Lower height threshold for sprinklers reduces demands on fire fighters.) [F] 903.2.11.7 High -Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4572 mm), see Chapter 23 of the International Fire Code to determine if those provisions apply. (Reason: Reference to Fire Code for special conditions.) [F] 903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire - extinguishing system. (Reason: Reflects local practices. Consistent with regional amendments to IFC 903.2.10 and 903.2.10.5) [F] 903.2.11.9 Buildings Over 6,000 sq. ft. An automatic sprinkler system shall be installed throughout all buildings over 6,000 sq. ft. For the purpose of this provision, fire walls shall not define separate buildings. For this section only area measurement shall be based on outside dimensions of exterior walls, exclusive of vent shafts and courts, without deduction for corridors, stairways, closets, the thickness of interior walls, columns or other features. The floor area of a building, or portion thereof, not provided with surrounding exterior walls shall be the usable area under the horizontal projection of the roof or floor above. The gross floor area shall not include shafts with no openings or interior courts. For upper level attic type rooms, areas where the ceiling height is less than five feet (5' 0 ") shall not be considered. Unfinished space framed to permit future expansion of floor area shall be considered as part of the area. Joists designed to support floor loads shall be assumed to be for future area. Exception: Open parking garages in compliance with Section 406.3. (Reason: Lower area threshold for sprinklers reduces demand on fire fighters. Based on NFPA and US Fire Administration study that analyzed fire response time and manpower needs Detail added to explain more precisely how areas are to be figured.) * *Section 903.3.1.1.1; amend as follows: [F] 903.3.1.1.1 Exempt locations. When approved by the fire code official, automatic Automatic sprinklers shall not be required in the following rooms or areas where such .. {bulk of section unchanged) ... because it is damp, of fire - resistance -rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the building official. 3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor /ceiling or roof /ceiling assemblies having a fire - resistance rating of not less than 2 hours. • 4. - -- ' - - -- - - - - • - -- -- - - -- • -- • - ' - - - -- -- - - 5. Fire service access c Elevator machine rooms and machinery spaces. (Reason: Gives more direction to code official. Exception 4 deleted to provide protection where fire risks are poorly addressed. Amendment 903.2 addresses Exception 5 above.) ** *Section 903.3.1.3; add the following: [F] 903.3.1.3 NFPA 13D sprinkler systems. Where allowed, automatic sprinkler systems installed in one- and two- family dwellings and townhouses shall be installed throughout in accordance with NFPA 13D or in accordance with state law. (Reason: To allow the use of the Plumbing section (P2904) of the IRC.) * *Section 903.3.5; add a second paragraph to read as follows: Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every fire protection system shall be designed with a 10 psi safety factor. (Reason: To define a uniform safety factor and to allow for seasonal changes to water pressure.) ** *Section 903.3.7; add the following: fF1903.3.7 Fire Department Connection Lock. All fire department connections shall be secured with a Knox Locking Fire Department Cap. (Reason: Assure sprinkler lines will be available for their intended purposes) * *Section 903.4; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. (Reason: To avoid significant water losses. Consistent with amendment to section 905.9) * *Section 903.4.2 — Add second paragraph to read as follows: The alarm device required on the exterior of the building shall be a weatherproof horn /strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection. (Reason: Fire department connections are not always located at the riser, this allows the fire department faster access.) * *Add Section 903.6 to read as follows: JF1 903.6 Spray booths and rooms. New and existing spray booths and spray rooms shall be protected by an approved automatic fire - extinguishinq system in accordance with IFC Section 1504. (Reason: Call attention to amendment to IFC 1504.) * *Section 905.2; change to read as follows: [F] 905.2 Installation standards. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high /low alarm. (Reason: To define manual dry standpipe supervision requirements.) ** *Add Section 905.3.8: Building Area. [F] 905.3.8: Building Area. In buildings exceeding 10,000 square feet in area per story, Class I automatic wet or manual wet standpipes shall be provided where any portion of the building's interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department vehicle access. Exception: Automatic dry and semi - automatic dry standpipes are allowed as provided for in NFPA 14. (Reason: Allows for the rapid deployment of hoselines to the body of the fire.) * *Section 905.4, item #5; change to read as follows: 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3 - percent slope), each standpipe shall be provided with an approved hose connection located either ... {remainder of paragraph unchanged) .. . (Reason: Hose connection type to be consistent with Fire Department policy. Consistent with regional amendment to IFC 905.4.) ** *Section 905.4; add the following item #7: 7. When required by this Chapter, standpipe connections shall be placed adjacent to all required exits to the structure and at two hundred feet (200') intervals along major corridors thereafter. (Reason: Allows for the rapid deployment of hoselines to the body of the fire.) * *Section 905.9; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. (Reason: To avoid significant water losses. Consistent with regional amendment to IFC 905.9.) ** *Section 906.1 (Where required); change Exception to Line Number 1 as follows: specified in Items 2 through 6. (Reason: Matches section 906.1 IFC.) ** *Add Section 907.1.4 to read as follows: [F] 907.1.4 Design Standards. All alarm systems new or replacement serving 20 or more alarm actuating devices shall be addressable fire detection systems. Alarm systems serving more than 20 smoke detectors or more than 100 total alarm activating devices shall be analog intelligent addressable fire detection systems. Exception: Existing systems need not comply unless the total building remodel or expansion initiated after the effective date of this code, as adopted, exceeds 30% of the building. When cumulative building remodel or expansion exceeds 50% of the building must comply within 18 months of permit application. (Reason: Consistent with local practice. Consistent with regional amendment to IFC 907.1.3.) * *Section 907.2.1; change to read as follows: E.907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A occupancies having an occupant Toad of 300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy. Activation of fire alarm notification appliances shall: 1. Cause illumination of the means of egress with Tight of not Tess than 1 foot - candle (11 lux) at the walking surface level; 2. Stop any conflicting or confusing sounds and visual distractions. (Reason: Increases the requirement is changed to be consistent with Group B requirement. Also addresses issue found in Group A occupancies of reduced lighting levels and otherAN equipment that distracts from fire alarm notification devices. Also reflects regional practice.) * *Section 907.2.3; change to read as follows: fF1907.2.3 Group E. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant Toad consideration and interconnection of alarm systems. Exceptions: 1. A manual fire alarm system is not required in Group E educational and day care occupancies with an occupant Toad of Tess than 50 when provided with an approved automatic sprinkler system. 1.1. Residential In -Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2 1/2 or less years of age, see Section 907.2.6.) {Remainder of exceptions unchanged) (Reason: To distinguish educational from day care occupancy minimum protection requirements. Further, to define threshold at which portable buildings are considered a separate building for the purposes of alarm systems. Consistent with Texas State laws concerning day care facility requirements.) * *Section 907.2.13; change to read as follows: . 0_907.2.13 High -rise buildings. Buildings having any floors used for human occupancy located more than 7-5 55 feet (22 860 16 764 mm) above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voice /alarm communications system in accordance with Section 907.2.12.2. (Reason: Consistent with definition of high - rise andt with regional amendment to IFC 907.2.12.) * *Section 907.2.13, exception #3; change to read as follows: 3. Buildings with an occupancy in Group A -5 in accordance with Section 303.1 when used for open air seating; however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants and similarly enclosed areas. (Reason: To indicate that enclosed areas within open air seating type occupancies are not excepted from automatic fire alarm system requirements. Consistent with regional amendment to IFC 907.2.12.) * *Section 907.4.2.6; add Section 907.4.2.6 to read as follows: fF] 907.4.2.6 Type. Manual alarm initiating devices shall be an approved double action type. (Reason: Helps to reduce false alarms. Code section relocated from previous edition. Consistent with regional requirements. {IFC Section 907.4.2.6 - Regional Amendment. }) * *Add Section 907.6.5.2 to read as follows: fn 907.6.5.2 Installation.. All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All initiating circuit conductors shall be Class "A" wired with a minimum of six feet separation between supply and return circuit conductors. IDC — Class "A" Style D; SLC - Class "A" Style 6; NAC - Class "B" Style Y. The IDC from an addressable device used to monitor the status of a suppression system may be wired Class B, Style B provided the distance from the addressable device is within 10 -feet of the suppression system device. (Reason: To provide uniformity in system specifications and guidance to design engineers. Consistent with regional amendment to IFC 907.7) ** *Section 910.1; Amend exception 2 to read as follows: [F] 910.1 General. Where required by this code or otherwise installed, smoke and heat vents, or mechanical smoke exhaust systems, and draft curtains shall conform to the requirements of this section. Exceptions: 1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system. 2: Where areas of buildings are equipped with early suppression fast - response (ESFR) sprinklers -only manual smoke and heat vents shall not be required within these areas. Automatic smoke and heat vents are prohibited. (Reason: Allows the fire department to control the smoke and heat during and after a fire event.) ** *Section 910.2; add Section 910.2.3 with exceptions and 910.2.4 to read as follows: [Fl 910.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as follows: 1. In occupancies classified as Group H -2 or H -3, any of which are more than 15,000 square feet (1394 m in single floor area. Exceptions: 1. Buildings of noncombustible construction containing only noncombustible materials. 2. In areas of buildings in Group H used for storing Class 2, 3 and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water - reactive materials as required for a high- hazard commodity classification. FF1910.2.4 Exit access travel distance increase. Buildings and portions thereof used as a Group F -1 or S -1 occupancy where the maximum exit access travel distance is increased in accordance with Section 1016.3. (Reason: Maintain the current level of protection as outlined in the 2003 IFC.) ** *Table 910.3; Change the title of the first row of the table to read as follows: [F] TABLE 910.3 REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa OCCUPANCY DESIGNATED MINIMUM MAXIMUM VENT- MAXIMUM MAXIMUM GROUP AND STORAGE DRAFT AREA AREATO- SPACING OF DISTANCE TO COMMODITY HEIGHT CURTAIN FORMED BY FLOOR -AREA VENT VENTS FROM CLASSIFICATION (feet) DEPTH DRAFT RATIOS CENTERS WALL OR (feet) CURTAINS (feet) DRAFT (square feet) CURTAINS& (feet) Group F -1 H and — 0.2 X Hd 50,000 1:100 120 60 S -1 but >_ 4 (Balance of table remains unchanged) {footnotes remain unchanged) (Reason: Consistency with the amendment 910.2.4 to include Group H) ** *Section 910.3.2.2; Add second paragraph to read as follows: The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at least 100 degrees (F) (approximately 38 degrees Celsius) greater than the temperature rating of the sprinklers installed. (Reason: Specifies a temperature range at which smoke and heat vents should activate in sprinklered buildings to ensure that the sprinkler system has an opportunity to activate and control the fire prior to vent operation. The intent is to allow the sprinkler system to operate prior to allowing the smoke and heat vents to operate so as not to pose a detriment to the operation of the sprinkler system. This follows recommendations indicated in NFPA 204, Section F.3 with regards to Design Considerations of smoke and heat vents in sprinklered buildings. Full scale fire testing results have shown that smoke and heat venting is potentially detrimental to the proper operation of the sprinkler system when vents are open prior to sprinkler activation. This was a primary reason for removing smoke and heat venting requirements with regards to ESFR sprinkler systems in Article 23 of the IFC for high -piled storage.) ** *Section 912.2; add Section 912.2.3 to read as follows: IF] 912.2.3 Hydrant distance. An approved fire hydrant shall be located within 100 feet of the fire department connection as the fire hose lays. (Reason: Consistent with regional practices.) * *Section 913.1; add second paragraph and exception to read as follows: When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior fire department access door that is not less than 3 ft. in width and 6 ft. — 8 in. in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by Section 506.1. Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that required for the pump room, or as approved by the fire code official. Access keys shall be provided in the key box as required by Section 506.1. (Reason: This requirement allows fire fighters safer access to the fire pump room. The requirement allows access without being required to enter the building and locate the fire pump room interior access door during a fire event. The exception recognizes that this will not always be a feasible design scenario for some buildings, and as such, provides an acceptable alternative to protect the pathway to the fire pump room.) * *Section 1004.1.1; Delete exception as follows: 1004.1.1 Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas without fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. (Reason: Consistent with local practice.) * *Section 1007.1; add the following exception #4: Exceptions: {1 through 3 unchanged} 4. Buildings regulated under State Law and built in accordance with State registered plans, including any variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of Section 1007. (Reason: To accommodate buildings regulated under Texas State Law and to be consistent with amendments to Chapter 11.) ** *Section 1008.1.9.3; Locks and Latches; add section 3.1 as follows: 1008.1.9.3, Locks and latches. (3.1) Where egress doors are used in pairs and positive latching is required, approved automatic flush bolts shall be permitted to be used, provided that both leaves achieve positive latching regardless of the closing sequence and the door leaf having the automatic flush bolts has no doorknobs or surface mounted hardware. (Reason: To ensure positive latching.) ** *Section 1008.1.9.4; amend exceptions #3 and #4 as follows: 1008.1.9.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Exceptions: 1. On doors not required for egress in individual dwelling units or sleeping units. 2. Where a pair of doors serves a storage or equipment room, manually operated edge- or surface- mounted bolts are permitted on the inactive leaf. 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F M or S occupancy, manually operated edge- or surface - mounted bolts are permitted on the inactive leaf. The inactive leaf shall contain no doorknobs, panic bars or similar operating hardware. 4. Where a pair of doors serves a Group B, F, M or S occupancy, manually operated edge- or surface - mounted bolts are permitted on the inactive leaf provided such inactive leaf is not needed to meet egress width requirements and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The inactive leaf shall contain no doorknobs, panic bars or similar operating hardware. 5. Where a pair of doors serves patient care rooms in Group 1 -2 occupancies, self - latching edge- or surface- mounted bolts are permitted on the inactive leaf provided that the inactive leaf is not needed to meet egress width requirements and the inactive leaf contains no doorknobs, panic bars or similar operating hardware. (Reason: reflects regional practice.) ** *Section 1008.1.9.8; change to read as follows: 1008.1.9.8. Electromagnetically locked egress doors. Doors in the means of egress that are not otherwise required to have panic hardware in buildings with an occupancy in Group A, B, E, 1 -1, 1 -2, M, R -1 or R -2 and doors to tenant spaces in Group A, B, E, 1 -1, 1 -2, M, R -1 or R -2 shall be permitted to be electromagnetically locked if equipped with listed hardware that incorporates a built -in switch and meet the requirements below: [remaining text unchanged] (Reason: Common regional practice to permit such locks due to the presence of trained staff.) ** *Section 1015.7; add new section 1015.7 to read as follows: 1015.7 Electrical Rooms. For electrical rooms, special exiting requirements may apply. Reference the electrical code as adopted. (Reason: Reference necessary for coordination.) ** *Section 1016.3; add new section to read as follows: 1016.3. Roof Vent Increase. In buildings that are one story in height, equipped with automatic heat and smoke roof vents complying with Section 910 and equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the maximum exit access travel distance shall be 400 feet for occupancies in Group F -1 or S -1. (Reason: Disagree with reason for deletion of Section 1016.2 in 2006 IBC as indicated in ICC E114/07/08 Commentary.) * *Section 1018.1; add exception # 5 to read as follows: 5. In Group B office buildings, corridor walls and ceilings need not be of fire - resistive construction within office spaces of a single tenant when the space is equipped with an approved automatic fire alarm system within the corridor. The actuation of any detector shall activate alarms audible in all areas served by the corridor. (Reason: To reduce redundant requirements in a single tenant situation. Intended to be consistent with regional amendment to IFC. Carried over from 2006 IBC, numbering change.) ** *Section 1018.6; amend to read as follows: 1018.6 Corridor Continuity. Fire Resistance Rated All corridors shall be continuous from the point of entry to an exit, and shall not be interrupted by intervening rooms. {Exception unchanged} (Reason: Once in a corridor, the degree of protection should not be reduced priorto egress from the building.) ** *Section 1022.1; add exceptions #8 & #9 to read as follows: 8. In other than occupancy Groups H and I, a maximum of 50 percent of egress stairways serving one adjacent floor are not required to be enclosed, provided at least two means of egress are provided from both floors served by the unenclosed stairways. Any two such interconnected floors shall not be open to other floors. 9. In other than occupancy Groups H and I, interior egress stairways serving only the first and second stories of a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 are not required to be enclosed, provided at least two means of egress are provided from both floors served by the unenclosed stairways. Such interconnected stories shall not be open to other stories. (Reason: To be consistent with regionally accepted practices and legacy codes.) * *Section 1022.9; change to read as follows: 1022.9 Smokeproof enclosures and pressurized stairways. In buildings required to comply with Section 403 or 405, each of the exit enclosures serving a story with a floor surface located more than 7-5 55 feet (22 860 16 764 mm) above the lowest level of fire department vehicle access or more than 30 feet (9144 mm) below the finished floor of a level of exit discharge serving such stories shall be a smokeproof enclosure or pressurized stairway in accordance with Section 909.20. (Reason: Consistent with high rise definition as amended and clarify only one floor need be above the threshold.) ** *Section 1024.1; change to read as follows: 1024.1 General. Approved luminous egress path markings delineating the exit path shall be provided in buildings of Groups A, B, E, I, M and R -1 having occupied floors located more than 7-5 55 -feet (22860 16 764 mm) above the lowest level of fire department vehicle access in accordance with ... {Remaining language unchanged.) (Reason: Consistent with high rise definition as amended and clarify only one floor need be above the threshold.) ** *Section 1026.6; amend exception #4 to read as follows: 4. Separation from the intpr+er open -ended corridors of the building is not required for exterior ramps or stairways connected to open -ended corridors, provided that Items 4.1 through 4.4 are met. (Reason: to clarify section 1022.6 , i.e., the 180 degree rule is applicable.) Section 1101.2; add an exception to read as follows: Exception: Buildings regulated under State Law and built in accordance with State registered plans, including any variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of this Chapter. (Reason: To accommodate buildings regulated under Texas State law.) * *Section 1210.2, exception #2; change to read as follows: 2. Toilet rooms that are not accessible to the public and which have not more than one water closet; provided that walls around urinals comply with the minimum surrounding material specified by Section 419.3 of the International Plumbing Code. (Reason: Recognize the minimum wall material requirements of the IPC. Consistent with regional amendment to IPC 419.3.) * *Table 1505.1; replace footnotes b and c with the following: •b. - - - - - - - - - .- •. • -e - • e - - - — - -- ' - _-e _ - -- - the leading e o f the r square feet of projected roof area and where there is a minimum 10 foot fire separation shakes n - classified roof coverings shall be permitted on buildings of U occupancies having not more than 120 sq.ft. of projected roof area. . When exceeding 120 sq.ft of projected roof area, buildings of U occupancies may use non -rated non- combustible roof coverings. When exceeding 120 sq.ft of projected roof area, buildings of U occupancies may use non -rated non - combustible roof coverings. (Reason: Conforms to local practice affording increased fire protection.) * *Section 1507.8.1 and 1507.8.1.1; change deck requirement as follows: 1507.8.1 Deck requirements. Wood shingles shall be installed on solid or spaced sheathing. Where spaced sh athing is used, sheathing boards shall not be lest, than equal to the w ather exposure to coincide with the placement of fasteners. (Reason: Solid sheathing makes roof replacement easier. In event of a roof fire less air is available to the fire.) * *Section 1507.9.1 and 1507.9.1.1; change deck requirement as follows: 1507.9.1 Deck requirements. Wood shakes shall only be used on solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall not be le= than 1 inch by 4 inch (25mmby 102 mm) nominal- d-imcr cions and shall be spaced on centers equal to the weatinicf-cxpecure to coincide with the placement of fat Where 1 inch by 4 inch (25 mm by 102 mm) spaced sheathing is installed at 10 inches (254 mm) o.c., additional 1 inch by 4 inch (25 mm by 102 mm) boards shall be installed between the sheathing boards. (Reason: Solid sheathing makes roof replacement easier. In event of a roof fire less air is available to the fire.) * *Section 1510.1; add a sentence to read as follows: All individual replacement shingles or shakes shall be in compliance with the rating required by Table 1505.1. (Reason: Relocated the language to more appropriate place. Previously was footnote "b" to Table 1505.1) * *Section 1612.3; Insert name as follows: 1612.3 Establishment of flood hazard areas. To establish flood hazard areas, the governing body shall adopt a flood hazard map and supporting data. The flood hazard map shall include, at a minimum, areas of special flood hazard as identified by the Federal Emergency Management Agency in an engineering report entitled "The Flood Insurance Study for The City of Southlake, Texas," dated 2009 as amended or revised with the accompanying Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map (FBFM) and related supporting data along with any revisions thereto. The adopted flood hazard map and supporting data are hereby adopted by reference and declared to be part of this section. * *Add Section 2308.4.3 to read as follows: 2308.4.3 Application to engineered design. When accepted by the Building Official, any portion of this section is permitted to apply to buildings that are otherwise outside the limitations of this section provided that: 1. The resulting design will comply with the requirements specified in Chapter 16; 2. The Toad limitations of various elements of this section are not exceeded; and 3. The portions of this section which will apply are identified by an engineer in the construction documents. (Reason: Allows engineer to reference Section 2308 for designs for wood structures; eliminates excessive engineering. Added text relocated to a more appropriate section.) * *Section 2901.1; add a sentence to read as follows: The provisions of this Chapter are meant to work in coordination with the provisions of Chapter 4 of the International Plumbing Code. Should any conflicts arise between the two chapters, the Building Official shall determine which provision applies. (Reason: Gives building official discretion.) ** Section 2902.1; change to read as follows: 2902.1 Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number as follows: 1. Assembly Occupancies: At least one drinking fountain shall be provided at each floor level in an approved location. Exception: A drinking fountain need not be provided in a drinking or dining establishment. 2. Groups A, B, F, H, I, M and S Occupancies: Buildings or portions thereof where persons are employed shall be provided with at least one water closet for each sex except as provided for in Section 2902.2. 3. Group E Occupancies: Shall be provided with fixtures as shown in Table 2902.1. 4. Group R Occupancies: Shall be provided with fixtures as shown in Table 2902.1. It is recommended, but not required, that the minimum number of fixtures provided also comply with the number shown in Table 2902.1. Types of occupancies not shown in Table 2902.1 shall be considered individually by the building official. The number of occupants shall be determined by this code. Occupancy classification shall be determined in accordance with Chapter 3. (Reason: To allow flexibility for designer to consider specific occupancy needs.) ** *Section (P] 2902.2; change exception # 3 as follows: 3.Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 5-0 100 or less. (Reason: Reflects regional practice.) ** *Section 3006.1; add 3006.1 and renumber the remaining 3006 sections: 3006.1, General. Elevator machine rooms shall be provided." {Renumber remaining sections.} (Reason: An elevator machine room is necessary to provide a protected space for elevator equipment that is used by the fire service, the disabled, and in the future, building occupant evacuations.) ***Section IF] 3006.4 {1F] 3006.5 when renumbered according to previous amendment), add a sentence as follows and delete exceptions #1 & #2: LE 3006.5. Machine Rooms: {language unchanged)... Storage shall not be allowed within the elevator machine room. Provide approved signage at each entry door to the elevator machine room stating "Elevator Machinery — No Storage Allowed." (Reason: To specify what is permitted in such areas.) * *Section 3109.1 ; add a section to read as follows: 3109.1 General. Swimming pools shall comply with the requirements of this section and other applicable sections of this code as well as also complying with applicable state laws. (Reason: to recognize "state requirements ") * *Section 3403.1.1 and 3404.1.1; add the following subsections: fF] 3403.1.1. For additions where chapter 9 of this code or the Fire Code require structures to have fire protection system(s) such systems installed throughout the building, both existing and new portions. Fl 3404.1.1. Alterations shall not require fire protection systems be added due to area limits specified in chapter 9 of this code or the Fire Code. (For change of occupancy see section 3406.) (Reason: to clarify application of fire protection requirements for additions or remodeling conditions.) * *Section 3412.2; Fill in the blank as follows: 3412.2 Applicability. Structures existing prior to annexation into the city limits or constructed within the city prior to June 20, 1978 , in which there is work involving additions, alterations or changes of occupancy shall be made to conform to the requirements of this section or the provisions of Sections 3403 through 3407. The provisions in Sections 3410.2.1 through 3410.2.5 shall apply to existing occupancies that will continue to be, or are proposed to be, in Groups A, B, E, F, M, R, S and U. These provisions shall not apply to buildings with occupancies in Group H or I. (Reason: To properly address buildings constructed without any regulating codes or inspections.) **Section H101.1: add the following paragraph: The sign ordinance of the City of Southlake is not changed by this chapter. This chapter is intended to only provide the structural standards for signs. In any conflict, the sign ordinance shall take precedence. * *SectionJ103.2: amend the exemptions as follows: J103.2 Exemptions. A grading permit shall not be required for the following: 1. Grading in an isolated, self- contained area, provided there is no danger to the public, and that such grading will not adversely affect adjoining properties when approved by the Building Official. 2. Excavation for construction of a structure permitted under this code. 3. Cemetery graves. c disposal sites controlled by othcr regulations. 5. Excavations for wells, or trenches for utilities. p roperties 7. Exploratory excavations performed under the direction of a registered design professional. (This phrase was added to assure that the "exploratory excavation" is not to begin construction of a building prior to receiving a permit, but is for the sole purpose of preparing a soils report.) Exemption from the permit requirements of this appendix shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or ordinances of this jurisdiction. END OF AMENDMENTS. INVOICE Star - Telegram Customer ID: CIT57 400 W. 7TH STREET Invoice Number: 313978911 FORT WORTH, TX 76102 ti lc ,:,,,%, (817) 390 -7761 Invoice Date: 1/15/2011 Federal Tax ID 26- 2674582 Terms: Net due in 21 days Due Date: 1/31/2011 Bill To: PO Number: NO PO CITY OF SOUTHLAKE C -, C F CiTY r 1400 MAIN ST . -, ,,, Order Number: 31397891 STE 440 Sales Rep: 073 SOUTHLAKE, TX 76092 -7604 Description: CITY OF SOUTHLA Attn: Attn: ACCOUNTS PAYABLE Publication Date: 1/15/2011 I D , �: ' L� Col. D Li nage ` mu " >& Rate 1 4=z° A l ountt CITY OF SOUTHLAKE CITY OF SOU7� Notice is hereby given by the city I3580 1 67 67 LINE $17.29 $1,158.74 Council of the City of Southlake, Texas, that a public hearing will be held on February 1, 2011, at 5:30 Sales Discount j p.m. or immediately following the ($1,054.17) Work Session, during the Regular City Council meeting to be held in Misc Fee the City Council Chambers of Town $10.00 Hall, 1400 Main Street, Southlake, Texas. Purpose of the public hearing is to consider the second reading of the following ordinance: ORDINANCE 987 AN 2009 EDITION OF OF THE Net Amount: $114.57 TIONAL BUILDING CODE REGU- LATING THE ERECTION CON- STRUCTION, ENLARGEMENT, AL- tttttlil HIg 1 TERATION, REPAIR, MOVING, ��````,d L H o '� / fie REMOVAL, DEMOLITION, CON S. • ° ... e/ 4 VERSION, OCCUPANCY, EQUIP - f � � MENT, USE, HEIGHT, AREA AND Q O P q 10 MAINTENANCE OF ALL BUILDINGS O � • Q OR STRUCTURES, EXCEPT ONE- ®G ° 2 j AND TWO- FAMILY DWELLINGS •1 AND MULTIPLE SINGLE-FAMILY c ° DWELLINGS (TOWNHOUSES), AND INCLUDING THE NATIONAL ELECTRICAL CODE AS REFER- OF w ENCED HEREIN, IN THE CITY OF i ° �lPIRES. �� THE STATE OF ADOPTION AE ND- :AMNDS ''Bf /1 ' . ° - 31 °' ON County of Tarrai MENTSTHERETO; PROVIDING FOR �P /g / / /Btil111tttt RECORDING OF SUCH CODE AS -A PUBLIC RECORD; PROVIDING THAT Before me, a Nc MuLATIVE FNA SHALL ANCE ; 'and State, this day personally appeared Deborah Baylor Norwood, Bid and Legal Coordinator for the Star - Telegra PROVIDING A SEVERABILITY m, Inc. at Fort Worth, in Tarrant County, Texas; and who, after being duly sworn, did depose and say that the attache( CLAUSE; PROVIDING FOR A PEN s published in the above named paper on the listed dates: BIDS & LEGAL DEPT. STAR TELEGRAM ALTY FOR VIOLATIONS HEREOF; (817) 215 - 2323 PROVIDING A SAVINGS CLAUSE; PROVIDING AM LET FOR PUBLI TION IN ZA ^ _ _ ` ^ AD `� 11� FOR PUBICA fi` ' ' 4 Signed 3Q �� `\ CIAL NEWSPAPER; A:PROV SUBSCRIBED / HIS Wednesday, . y, 19, 2011. Any person, firm o corporation who I Notary Public .d' 4 �/ , /� 1 1 _4 — �� violates, disobeys, omits: neglects ! rY or refuses to comply with or who resists the enforcement of any of the provisions of this ordinance shall be fined not more than Two Thousand Dollars ($ 2,000.00) for any violation involvin zoning, fire Thank You l to e o i y , incluudin dum g o refuse, and shall be fined not more than five hundred dollars ($500) for any — other violation of this ordinance. Each day that a violation is permitted to exist shalt .'constitute a separate offense. ( City of Southlake Customer ID: CIT57 Remit To: In t er im City Secretary 1 .U. OVA 9010 Customer Name: CITY OF SOUTHLAKE FORT WORTH, TX 76101 -2051 Invoice Number: 313978911 Invoice Amount: $114.57 PO Number: NO PO Amount Enclosed: INVOICE Star - Telegram Customer ID: CIT57 400 W. 7TH STREET Invoice Number: 314438951 RECEIVED FORT WORTH, TX 76102 (817) 390 -7761 Invoice Date: 2/17/2011 Federal Tax ID 26- 2674582 . Terms: Net due in 21 days Due Date: 2/28/2011 Bill To: PO Number: NO PO CITY OF SOUTHLAKE 1400 MAIN ST OFFICE SECRETARY Order Number: 31443895 STE 440 Sales Rep: 073 SOUTHLAKE, TX 76092 -7604 Description: CITY OF SOUTHLA Attn: Attn: ACCOUNTS PAYABLE Publication Date: 2/17/2011 . E CITY OF Sourauk 1 Descr;.al AN o a N a r THE " ation Col Depth. Linage MU Rate Amount 1 2009 10101. DI BUi t4+ COD - CITY OF !. L ERECTIOI�CON- NO I3580 1 58 58 LINE $17.31 $1,003.76 STRUCTION, ENLARGEMENT, AL- TERATION, REPAIR, MOVING, Sales D REMOVAL, " DEMOLITION, CON- ($914.58) VERSION, OCCUPANCY, EQUIP- MENT, USE, HEIGHT, AREA AND Mlsc Fee MAINTENANCE OF ALL LD OR STRUCTURES, EXCEPT ONE - INGS $10.00 AND TWO - FAMILY DWELLINGS AND MULTIPLE SINGLE- FAMILY DWELLINGS (TOWNHOUSES), AND INCLUDING THE NATIONAL ELECTRICAL CODE AS REFER- $99.18 ENCED HEREIN IN THE CITY OF Net Amount: SOUTHLAKE; PROVIDING FOR THE ADOPTION OF LOCAL AMEND- MENTS THERETO; PROVIDING FOR ` \ \ \ \Uilillllf / / /// PUB PROVIDING AS ` L. .H 0 �� /i�� THIS ORDINANCE SHALL BE CU- "y MULATIVE OF ALL ORDINANCES; Q `• ' P PY P(je ' � e PROVIDING A SEVERABILITY Z '� <', ;O CLAUSE; PROVIDING • FOR A PEN - U . ' i 1411:-.1 - ALTY FOR VIOLATIONS HEREOF; PROVIDING A SAVINGS CLAUSE; * : /\ PROVIDING FOR PUBLICATION IN • Q PAMPHLET FORM; PROVIDING FOR PUBLICATION IN THE OFFI- � - OF CIAL NEWSPAPER; AND PROVID- • `•• FXPIRE . •• � ING AN EFFECTIVE DATE. 's 4 .\2 THE STA A violates n di sob eys omits. negl is � / // / lil y tt� \ \ \ \ \‘ ` County of or refuses to comply with or who resists the enforcement of any of the provisions of this ordinance . Before me shall be fined not more than Two .ounty and State, this day personally appeared Deborah Baylor Norwood, Bid and Legal Coordinator for the Star -T Thousand Dollars ($ 9g 2,000.00) for ;legram, Inc. at Fort Worth, in Tarrant County, Texas; and who, after being duly sworn, did depose and say that the at safety f or �publ c andg'J nt was published in the above named paper on the listed dates: BIDS & LEGAL DEPT. STAR TELEGRAM (817) 215- tation including dumping or refuse, and shall be fined not more than ` , five hundred dollars ($500) for any - „,,,,,,,,,K other violation of this ordinance. Signed IS C;IS)...Q.N.5•-- \C\ - Each day that a violation is SUBSCRI Pe eu constitute ME, THIS Friday, Febru- �11. a se E rmitt D t A N to offense. xist sha Y. I PA AND APPROVED THIS THE 15th DAY OF FEBRUARY 2011, ' DURING ILC MEETING. REGULAR CITY Notary Public d 1. ./. i _1(,,,iii.) MAYOR: Jotin Terrell ATTEST: A icia Richardson, City Secretary Thank You For Your Payment Remit To: Star - Telegram Customer ID: CIT57 P.O. BOX 901051 Customer Name: CITY OF SOUTHLAKE FORT WORTH, TX 76101 -2051 Invoice Number: 314438951 Invoice Amount: $99.18 PO Number: NO PO Amount Enclosed: