Loading...
1st Fire Marshal ReviewCase No. ZA21-0026 Review No. 1 Dated: 04-07-2021 Number of Pages: 1 Project Name: XO Marriage Center Contact: Kelly Clements, Fire Marshal Phone: 817-748-8233 Fax: 817-748-8181 =========================================================================== The following comments are based on the review of plans received on 04/06/2021. Comments may be incorporated into the formal review to be considered by either the Planning and Zoning Commission or City Council. It is the applicant’s responsibility to contact the department representative shown above and make modifications as required by the comment. =========================================================================== GENERAL COMMENTS: The required backflow protection (double check valve) for the sprinkler systems can be located on the riser if the riser is within 100 feet of the water main, measured linearly along the length of the pipe. If the riser is further than 100 feet from the main, the double check valve shall be in a vault. Riser rooms shall be a minimum of 5’X5’ if the double check is located in a vault, or a minimum of 6’X6’ if it is located on the riser. (Label riser room location to determine termination point of riser piping, and indicate size of the riser room) The HDPE 2.5” water line is not allowed to be tapped into the fire protection line that enters the building for the fire sprinkler suppression system. FIRE LANE COMMENTS: Fire apparatus access needs to be an all-weather surface, asphalt or concrete, 24 feet wide and able to support the imposed loads of fire apparatus. (Minimum of 85,000 pounds GVW). The fire lanes appear to be less than the required 24-foot width in some areas. Fire lanes require a minimum 30 foot inside turn radius and a minimum 54 foot outside turn radius. (Per 2018 I.F.C. Sec. 503.2.4)