SS-letterW
CONSULTING
Scott E. Wyssling, PE, PP, CME
February 24, 2021
Ken Trappen
Advanced Solar Solutions
39650 Mallard
Bass Lake, CA 93604
Wyssling Consulting
76 North Meadowbrook Drive
Alpine, UT 84004
office (201) 874-3483
swyssling@wyssfingconsulting.com
Re: Engineering Services
Tew Residence
1603 Regal Oaks Drive, Southlake TX
18.975 kW System
Dear Mr. Trappen:
Pursuant to your request, we have reviewed the following information regarding solar panel installation on
the roof of the above referenced home:
1. Site Visit/Verification Form prepared by Advanced Solar Solutions representative identifying
specific site information including size and spacing of rafters for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information was prepared by Advanced Solar Solutions
and will be utilized for approval and construction of the proposed system.
3. Photographs of the interior and exterior of the roof system identifying existing structural
members and their conditions.
Based on the above information we have evaluated the structural capacity of the existing roof system to
support the additional loads imposed by the solar panels and have the following comments related to our
review and evaluation:
Description of Residence:
The existing residence is typical wood framing construction with the roof system consisting of 2 x 6
dimensional lumber at 24" on center. The attic space is unfinished and photos indicate that there was free
access to visually inspect the size and condition of the roof rafters. All wood material utilized for the roof
system is assumed to be Doug -Fir #2 or better with standard construction components. The existing roofing
material consists of composite asphalt shingles. Photos of the dwelling also indicate that there is a
permanent foundation.
A. Loading Criteria Used
• 105 MPH wind loading based on ASCE 7-16 Exposure Category "C" at a slope of 42 degrees
• 7 PSF = Dead Load roofing/framing Live Load = 20 PSF Snow Load = 5 PSF
• 3 PSF = Dead Load solar panels/mounting hardware
Total Dead Load =10 PSF
The above values are within acceptable limits of recognized industry standards for similar
structures in accordance with the Texas Uniform Construction Code (2018 IRC). Analysis
performed of the existing roof structure utilizing the above loading criteria indicates that the
existing rafters will support the additional panel loading without damage, if installed correctly.
Page 2 of 2
B. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent "IronRidge Solar Installation
Manual", which can be found on the IronRidge Solar website (http.-Iironridgesolar.coml). If during
solar panel installation, the roof framing members appear unstable or deflect non -uniformly, our
office should be notified before proceeding with the installation.
2. Maximum allowable pullout per lag screw is 235 Ibs/inch of penetration as identified in the National
Design Standards (NDS) of timber construction specifications for Doug -Fir (North Lumber)
assumed. Based on our evaluation, the pullout value, utilizing a penetration depth of 2 '/2", is less
than what is allowable per connection and therefore is adequate. Based on the variable factors for
the existing roof framing and installation tolerances, using a thread depth of 2 '/2" with a minimum
size of 5/16" lag screw per attachment point for panel anchor mounts should be adequate with a
sufficient factor of safety.
3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed
no greater than 72" o/c.
4. Panel supports connections shall be staggered to distribute load to adjacent rafters.
Based on the above evaluation, it is the opinion of this office that with appropriate panel anchors being utilized
the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is in
conformance with the Texas Uniform Construction Code, current industry and standards, and based on
information supplied to us at the time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
V truly yours,
_QL%
Scott E. Wyssli , PE
Texas License No. 1
Firm No. 20109
W CONSULTING
•-,•