Loading...
0868 2003 International Building Code ORDINANCE NO. 868 OFFICIAL RECORD AN ORDINANCE ADOPTING THE 2003 EDITION OF THE INTERNATIONAL BUILDING CODE, RI<~GrLATING THE ERECTION, CONSTRUCTION, ENLARGEMENT, ALTERATION, REPAIR, MOVING, REMOV AL, DEMOLITION, CONVERSION, OCCUPANCY, EQUIPMENT, USE, HEIGHT, AREA AND MAINTENANCE OF ALL BUILDINGS OR STRUCTURES, EXCEPT ONE- AND TWO-FAMIL Y DWELLINGS AND MULTIPLE SINGLE-FAMILY DWELLINGS (TOWNHOUSES), IN THE CITY OF SOUTHLAKE AND PROVIDING FOR THE ADOPTION OF LOCAL AMENDMENTS THERETO; PROVIDING FOR RECORDING OF SUCH CODE AS A PUBLIC RECORD;_PROVIDING THAT THIS ORDINANCE SHALL BE CUMULATIVE OF ALL ORDINANCES; PROVIDING A SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY FOR VIOLATIONS HEREOF; PROVIDING A SAVINGS CLAUSE; PROVIDING FOR PUBLICATION IN PAMPHLET FORM; PROVIDING FOR PUBLICATION IN THE OFFICIAL NEWSPAPER; AND PROVIDING AN EFFECTIVE DATE. WHEREAS, the City of Southlake is a home rule city acting under its charter adopted by the electorate pursuant to Article Xl, SectIOn 5 of the Texas Constitution and Chapter 9 of the Local Government Code; and WHEREAS, the City Council of the City of Southlake deems it necessary to adopt this ordinance providing minimum standards to safeguard the health, property, and welfare of the citizens of Southlake by regulating and controlling the use, occupancy, maintenance, repair, design, construction and quality of materials for buildings and structures within the City. WHEREAS, beginning in the summer of2003, NCTCOG's Regional Codes Coordinating Committee (RCCC) and its four advisory boards conducted 26 open review meetings over a 10-month period to review the 2003 editions of the International Codes and to develop regional amendments. Their review and recommendations were completed and endorsed by NCTCOG's Executive Board in March 2004. Now NCTCOG encourages jurisdictions in North Central Texas to adopt the 2003 International Building Code along with its respective regional amendments with an effective date of July 1,2004: NOW. THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF SOUTHLAKE, TEXAS: SECTION 1 That the International Building Code, 2003 Edition, published by the International Code Council, including the standards referenced therein, including Appendix Chapters A, C, F, G, H, I and J are hereby adopted as the Building Code of the City of Southlake regulating the erection, construction, enlargement, alteration, repair, moving, remma], demolition, conversion, occupancy, equipment, use, height, area and maintenance of all buildings or structures, except one- and two-family dwellings and multiple single family dwellings (townhouses), in the City of South lake. True and correct copies of these documents are attached as Exhibit "A." SECTION 2 That the 2003 International Building Code, as adopted herein, is hereby amended as provided in Exhibit "B" incorporated herein and attached hereto for all purposes of this ordinance. The City of Southlake, Texas may from time to time determine that additional local modifications to the Building Code are necessary and appropriate to meet the unique needs of the City of South lake, Texas. To effectuate these local modifications, the City Council shall cnact individual ordinances amending this Ordinance, fully setting forth the change to be made in the Building Code Upon adoption, copies of these amendments shall be attached to ExhibIt "B" to this Ordinance. SECTION 3 The materIal contained in Exhibits "A" and "R" to this ordinance shall not be included in the formal municipal codification of ordinances, but shall be maintained as a pubJic record in the office of the City Building Official and will he available for public lIlspection and copying during regular business hours. SECTION 4 This ordinance shall be cumulative of all provisions of ordinances of the City of Southlake, Texas, except where the provisions of this ordinance are in direct conflict with the provisions of such ordinances, in which event the conflicting provisions of such ordinances are hereby repealed. ThIS ordinance is intended to replace the following: I. Ordinance 815, as amended, the 2000 International Building Code. Th]s ordinance is not intended to amend or replace the following: 1. Ordinance 480, the Zoning Ordinance. 2. Ordinance 483, the Subdivision Ordinance. ~. Ordinance 557, Exterior Masonry Construction Requirements 4. Ordinance 568, as amended, Contractor's Licensing Ordinance 6. Ordinance 506-A, as amended, the Sign Ordinance SECTION 5 It is hereby declared to be the intention of the City Council that the phrases, clauses, sentences, paragraphs, and sections of this ordinance are severable, and if any phrase, clause sentence, paragraph or section of this ordinance shall be dec lared unconstitutional by the valid judgment or decree of any court of competent jurisdiction, such unconstitutionality shall not affect any of the remaining phrases, clauses, sentences, paragraphs and sections of this ordlllance, since the same would have been enacted by the City Council without the incorporation in this ordinance of any such unconstitutional phrase, clause, sentence, paragraph or section. SECTION 6 Any person, firm or corporation who violates, disobeys, omits. neglects or refuses to comply with or who resists the enforcement of any of the provisions of this ordinance shall be fined not more than Two Thousand Dollars ($ 2,000.00) for all violations involving zoning, fire safety or public health and sanitation, including dumping or refuse, and shall be tined not more than five hundred dollars ($500) for all other violations ofthis ordinance. Each day that a violation is permitted to exist shall constitute a separate offense. SECTION 7 All rights and remedies of the City of Southlake are expressly saved as to any and all violations of the provisions of any ordinances affecting the regulation and control of the use, occupancy, maintenance, repair, design, construction and quality of materials for buildings and structures within the City which have accrued at the time of the effective date of this ordinance: and, as to such accrued violations and all pending litigation, both civil and cllminal, whether pending in court or not, under such ordinances, same shall not be affected by this ordinance but may be prosecuted until final disposition by the courts. SECTION 8 The City Secretary of the City of Southlake is hereby authorized to publish this ordinance in book or pamphlet form for general distribution among the public, and the operative provisions of this ordinance as so published shall be admissible in evidence in all courts without further proof than the production thereof. SECTION 9 The Clty Secretary of the City of South lake is hereby directed to publish in the official newspaper of the City of South lake, the caption, penalty clause, publication clause and effective date of this ordinance one time within ten days after passage of this ordinance, as required by Section 3.13 of the Charter of the City of Southlake. 2 • SECTION 10 This ordinance shall be in full force and effect from and after its passage and publication as required by • law,but not sooner than September 30,2004 and it is so ordained. PASSED AND APPROVED ON FIRST READING THIS jli h DAY OF id'll.� ,2004. ,,,,��,nq►q,,, J — .sis50tTH(�,,,,,. • •I. AYOR =~s• i� •'141:. ATTEST: ' CITY SECRETARY PASSED AND APPROVED ON SECOND READING THIS DAY OF ,2004. OVTHLq,.''• AYOR ' •T(: =VS " •D: I. ATTEST• ' •: t CITY SE. TARY •'• ••• s,��'► *** ,,,,,, APP' 1.1 VED AS TO F' AND LEGALITY: City Attorney / ,I Date: 8.3-U`i EFFECTIVE: Date: 7 d31y1 3 EXHIBIT "B" LOCAL AMENDMENTS TO THE 2003 INTERNATIONAL BUILDING CODE The following sections, paragraphs, and sentences of the 2003 International Building Code are hereby amended as follows (Standard type is text from the IBC. Underlined type is text inserted. Lined through type is doleted text from IBC.) After each code amendment a reason is given in parentheses. The reason is not a part of the code, but is given to aid in understanding the code. Section 101.1; Insert city name as follows: 101.1 Title. These regulations shall be known as the Building Code of The City of South lake. Texas hereinafter referred to as "this code." Section 101.2, exception No.2; delete .amend as follows: 2. Existing buildings undergoing repair, alterations or additions, and change of occupancy sÞa# may be permitted to comply with the International Existing Building Code when approved by the Buildinq Official. Otherwise see chapter 34. (Reason: To allow flexibility to work with existing conditions.) Section 101.4; change to read as follows: 101.4 Referenced codes. The other codes listed in Sections 101.4.1 through 101.4.7 and referenced elsewhere in this code, when specifically adopted, shall be considered part of the requirements of this code to the prescribed extent of each such reference. Whenever amendments have been adopted to the referenced codes and standards. each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. (Reason: Legal wording to recognize locally adopted codes and amendments adopted with referenced codes. ) Section 105.1; change to read as follows: 105.1 Required. Any owner or authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure, to excavate or chanqe the qrade of any property, or to erect, install, enlarge, alter, repair, remove, convert or replace any electrical, gas, mechanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done, shall first make application to the building official and obtain the required permit. (Reason: Consistent with previous edition amendment, to provide means to regulate grading affecting other properties. ) Section 106.2; change to read as follows: 106.2 Site plan. The construction documents submitted with the application for permit shall be accompanied by a site plan showing to scale the size and location of new construction and existing structures on the site, distances from lot lines, the established street grades and the proposed finished grades and, as applicable, flood hazard areas, floodways, and design flood elevations; and it shall be drawn in accordance with an accurate boundary line survey. Plans shall also show proposed erosion control and tree protection measures in accordance with recoqnize? stand a rd.s and any additional information as required by other ordinan~es. In th~ case o~ d.emolltlon, the site plan shall show construction to be demolished and the 10~a~lon a~d. sl~e of exl~tlng struct~res and construction that are to remain on the site or plot. The building official IS authorized to waive or 4 modify the requirement for a site plan when the application for permit is for alteration or repair or when otherwise warranted. (Reason: Erosion control and tree preservation are required by other ordinances; this reference calls those req uirements to the attention of the designer.) Section 108.7; add. 108.7 Re-inspection Fee. A fee as established by city council resolution may be charged when: . The inspection called for is not ready when the inspector arrives; . The temporary electrical pole does not have a building permit clearly posted; . No building address or permit card is clearly posted; . City approved plans are not on the job site available to the inspector; . The building is locked or work otherwise not available for inspection when called; . The job site is red-tagged twice for the same item; . The original red tag has been removed from the job site. . Violations exist on the property including failure to maintain erosion control, trash control or tree protection. Any re-inspection fees assessed shall be paid before any more inspections are made on that job site. (Reason: This fee is not a fine or penalty but is designed to compensate for wasted time and trips when inspections are called for when not ready.) Section 108.8; add. 108.7 Investigation Fee. Work without a permit. 108.7.1 Investigation. Whenever work for which a permit is required by this code has been commenced without first obtaining a permit, a special investigation shall be made before a permit may be issued for such work. 108.7.2 Fee. An investigation fee, in addition to the permit fee, shall be collected whether or not a permit is subsequently issued. The investigation fee shall be equal to the amount of the permit fee required by this code or the city fee schedule as applicable. The payment of such investigation fee shall not exempt the applicant from compliance with all other provisions of either this code or the technical codes nor from penalty prescribed by law. (Reason: This fee is not a fine or penalty but is designed to compensate for wasted time and to remove incentive to attempt to evade permits and code compliance. Language taken from former Uniform Administrative Code.) Section 109.3.5; delete. (Reason: Lath or gypsum board inspections are not normally performed in this area and that has not caused problems. ) Section 110.1; change to read as follows: 110.1 Use and occupancy. No building or structure shall be used or occupied, and no change in the existing occupancy classification or occupant, either owner or tenant, of a building or ~tructure or portion thereof shall. be made until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. . . (Reason: Reflects regional policy and assists code officials track changes that affect building safety.) 5 Section 112; delete entirely and substitute the following: SECTION 112 BOARD OF APPEALS 112.1 General. In order to hear and decide appeals of orders, decisions or determinations made bv the buildinq official relative to the application and interpretation of this code, there shall be and is hereby created a board of appeals. The Buildinq Board of Appeals as established bv Ordinance 622, as amended. shall constitutte the Board of Appeals referenced in this code. 112.2 Limitations on authority. An application for appeal shall be based on a claim that the true intent of this code or the rules leqallv adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully apply, or an equally qood or better form of construction is proposed. The board shall have no authority to waive requirements of this code. (Reason: References local ordinance.) Section 202; add a new definition to read as follows: HIGH-RISE BUILDING is a buildinq havinq floors used for human occupancy located more than 55 feet (16 764 mm) or three stories above the lowest level of fire department vehicle access. (Reason: To define high-rise, as it influences sprinkler requirement thresholds based on the fire fighting capabilities of the jurisdiction.) Section 302.2.1; amend to read as follows: 302.2.1 Assembly areas. Accessory assembly areas are not considered separate occupancies if the floor area is equal to or less than 750 square feet (69.7 m2). Assembly areas that are accessory to Group E occupancies are Ret considered sep3rate occupancies exempt from the separation requirements of Table 302.3.2 and are considered Group E occupancies only for the purposes of Table 503. Accessory religious educational rooms and religious auditoriums with occupant loads of less than 100 are not considered separate occupancies. (Reason: The NCTCOG committee determined that the exiting requirements for Group A occupancies should apply to assembly occupancies in schools.) Table 302.3.2, change the footnote reference in column U row R-3, R-4 from ud" to "f' and add footnote "f' to read as follows: f. See Section 406.1.4. (Reason: Editorial; corresponds with regional amendment to 406.1.4.) Section 303.1; amend to read as follows: 303.1 Assembly Group A. Assembly Group A occupancy includes, among others, the use of a building or structure, or a portion thereof, for the gathering together of persons for purposes such as civic, social or religious functions, recreation, food or drink consumption or awaiting transportation. A room or space used for assembly purposes by less than 50 persons and accessory to another occupancy shall be included as a part of that occupancy. Assembly areas with less than 750 square feet (69.7 m2) and which are accessory to another occupancy according to Section 302.2.1 are not assembly occupancies. Assembly occupancies areas wAiGA that are accessory to Group E in accordance with section 302.2 are not considered 3ssembly occupancies are exempt from the separation requirements of Table 302.3.2 and are considered Group E occupancies only for the purposes of Table 503. Religious educational rooms and religious auditoriums which are accessory to churches in accordance with Section 302.2 and which have occupant loads of less than 100 shall be classified as A-3. (Balance of section remain unchanged) (Reason: Clarify that intent to exception is limited. Corresponds with regional amendment to section 302.2 1) Table 302.3.2; change the footnote reference in column U row R-3, R-4 from ud" to "f' and add footnote uf' to read as follows: f. See section 406.1.4 (Reason: Reference corrected to appropriate section.) Section 304.1; add the following to the list of occupancies: 6 Fire stations Police stations with detention facilities for 5 or less (Reason Clarify classification of these uses.) Section 403.1; change to read as follows: 403.1 Applicability. The provisions of this section shall apply to buildings having .ê!lY..occupied floors located more than +B 55 feet (n-8w 16 764 mm) above the lowest level of fire department vehicle access. (Reason: Consistent with amended definition of High Rise.) Section 403.2, exception #2; delete. (Reason: To provide adequate fire protection to enclosed areas.) Section 404.1.1; amend definition of Atrium as follows: ATRIUM. An opening connecting twe three or more stories. . . {Balance remains unchanged} (Reason: Code is not consistent. Section 1019 permits unenclosed two story stairways under certain circumstances. ) Section 406.6.1; add a second paragraph to read as follows: This occupancy shall include qaraqes involved in servicinq of motor vehicles for items such as lube chanqes, inspections, windshield repair or replacement, shocks. minor part replacement and other such non-maior repair. When the repair qaraqe is only involved in such minor repair, it need not comply with Section 406.6.2. (Reason: Correction to distinguish that service work is a repair garage as well to correspond with definition in the IFC.) Section 506.2.2; add a sentence to read as follows: In order to be considered as accessible, if not in direct contact with a street or fire lane, a minimum 1 a-foot wide pathway from the street or approved fire lane must be provided. (See International Fire Code Section 503.1.1 for hose lay measurement pathway requirements.) (Reason: To define what is considered accessible. Consistent with regional amendment to IFC 503.1.1.) Section 705.11; change the exception to read as follows: Exception: For other than hazardous exhaust ducts, penetrations by ducts and air transfer openings of . . . {remainder of exception unchanged}. (Reason: To distinguish that hazardous exhaust ducts are a special case to be treated differently.) Section 707.2; change exception number 7 to delete items 7.4 and 7.5 as follows: {7, 7.1, 7.2 and 7.3 unchanged} 7.~. Is not open to 3 corridor in Group I ~nd R occup3ncies. 7.5. Is not open to 3 corridor on nonsprinkled floors in 3ny occup~ncy. 1---:B-. 7.4 Is separated from floor openings. ..{remainder of exceptions unchanged} (Reason: To be consistent with regionally accepted practices.) Section 716.5.2; add exception #4 to read as follows: 716.5.2 Fire barriers. Duct and air transfer openings of fire barriers shall be protected with approved fire dampers 7 installed in accordance with their listing. Exception: Fire dampers are not required at penetrations of fire barriers where any of the following apply: 1. Penetrations are tested in accordance with ASTM E119 as part of the fire-resistance-rated assembly. 2. Ducts are used as part of an approved smoke control system in accordance with Section 909. 3. Such walls are penetrated by ducted HVAC systems, have a required fire-resistance rating of 1 hour or less, are in areas of other than Group H and are in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. For the purposes of this exception, a ducted HVAC system shall be a duct system for conveying supply, return or exhaust air as part of the structure's HVAC system. Such a duct system shall be constructed of sheet steel not less than 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals. 4. In the duct penetration of the separation between the private qaraqe and its residence when constructed in accordance with Section 406.1.4, exception #2. (Reason: To exclude specific penetration from fire damper requirements.) Section 902.1; under "Standpipe, Types of" definition amend "Manual dry" by adding a sentence to read as follows: The system must be supervised as specified in Section 905.9. (Reason: To conform to consistent standards of safety. Corresponds to IBC 905.2 amendment. Consistent with regional amendment to IFC 902.1.) Section 903.2.8.3; Add section to read as follows: 903.2.8.3. Self-service storaae facility. An automatic sprinkler system shall be installed throuqhout all self-service storaqe facilities. Exception: One-story self-service storaqe facilities that have no interior corridors, a one-hour fire barrier wall installed between every storaqe compartment. (Reason: Consistent with regional practice, reduces hazard of occupancies that often have unknown contents. ) with Section 903.2.10; amend title and 903.2.10.3 and add 903.2.10.4 thru 903.2.10.6 as follows: [F] 903.2.10 All occupancies except Groups R 3 and U. An automatic sprinkler system shall be installed in the locations set forth in Sections 903.2.10.1 through 903.2.10.1.3. Exception: Group R-3 as applicable in Section 101.2 and Group U. (Reason: exception jn title creates confusion.) 903.2.10.3 Buildings over 55 35 feet in height. An automatic sprinkler system shall be installed throughout buildings with a floor level, other than penthouses in compliance with Section 1509, having an occup::mt lo:::ld of 30 or more that IS located 5-á 35 feet (.w..+M 10 668mm) or more above the lowest level of fire department vehicle access. Exceptions: 1. Airport control towers. 2. Open parking structures in compliance with Section 406.3. 3. Occup:::lncios in Group F 2. (Reason: Lower height threshold for sprinklers reduces demands on fire fighters.) 903.2.10.4 Hiah-Piled Combustible Storaae. For any buildinq with a clear heiqht from floor to lowest projection of roof/ceilinq exceedinq 12 feet (4572 mm). see Chapter 23 of the International Fire Code to determine if those provisions apply. (Reason: Reference to Fire Code for special conditions.) 8 903.2.10.5 Spray Booths and Rooms. New and existinq spray booths and sprayinq rooms shall be protected by an approved automatic fire-extinquishinq system. (Reason: Reflects local practices. Consistent with regional amendments to IFC 903.2.10 and 903.2.10.5) 903.2.10.6 Buildinas Over 6,000 SQ. 11. An automatic sprinkler system shall be installed throuqhout all buildinqs over 6,000 sq. ft. For the purpose of this provision, fire walls shall not define separate buildinqs. For this section only area measurement shall be based on outside dimensions of exterior walls, exclusive of vent shafts and courts, without deduction for corridors, stairways, closets, the thickness of interior walls, columns or other features. The floor area of a buildinq, or portion thereof, not provided with surroundinq exterior walls shall be the usable area under the horizontal projection of the roof or floor above. The qross floor area shall not include shafts with no openinqs or interior courts. For upper level attic type rooms, areas where the ceilinq heiqht is less than five feet (5' 0") shall not be considered. Unfinished space framed to permit future expansion of qross floor area shall be considered as part of the area. Joists desiqned to support floor loads shall be assumed to be for future area. Exception: Open parkinq qaraqes in compliance with Section 406.3. (Reason: Lower area threshold for sprinklers reduces demand on fire fighters. Detail added to explain more precisely how areas are to be figured.) Section 903.3.1.1.1; amend as follows: 903.3.1.1.1 Exempt locations. When approved by the fire code official. automatic ,^,utomatic sprinklers shall not be required in the following rooms or areas where such. . . {bulk of section unchanged} . . . because it is damp, of fire- resistance-rated construction or contains electrical equipment. 1 Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2 Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the building official. 3-. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours. ,.,. In rooms or areas that are of noncombustiblo construction with wholly noncombustiblo contonts. (Reason: Individual approval of exceptions allows code official to consider individual circumstances.) Section 903.3.5; add a second paragraph to read as follows: Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every fire protection system shall be desiqned with a 10 psi safety factor. (Reason: To allow for seasonal changes to water pressure.) Section 903.3.7; change to read as follows: 903.3.7 Fire department connections. The location of fire department connections shall be approved by the building fire code official. (Reason: To match fire code language.) Section 903.4; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory siqnal at the central station upon tamperinq. (Reason:To avoid significant water losses. Consistent with amendment to section 905.9) Section 905.2; change to read as follows: 9 905.2 Installation standards. Standpipe system shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psiq and a maximum of 40 psiq air pressure with a hiqh/low alarm. (Reason: To define manual dry standpipe supervision requirements. Consistent with amendment to IFC 905.2) Section 905.3.2; delete exceptions #1 and 2. (Reason: Reflects local practice. Consistent with regional amendment to IFC 905.3.2.) Section 905.4, item #5; change to read as follows: 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with an approved hose connection located either. . . {remainder of paragraph unchanged} . . . (Reason: Clarity. Consistent with regional amendment to IFC 905.4.) Section 905.9; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm to reqister upon detection of water flow for more than 45 seconds, All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory siqnal at the central station upon tamperinq. (Reason: To avoid significant water losses. Consistent with regional amendment to IFC 905.9.) Add Section 907.1.3 to read as follows: 907.1.3 DesiQn Standards. All alarm systems new or replacement servinq 50 or more alarm actuatinq devices shall be addressable fire detection systems. Alarm systems servinq more than 75 smoke detectors or more than 100 total alarm activatinq devices shall be analoq intelliqent addressable fire detection systems. Exception: Existinq systems need not comply unless the total buildinq remodel or expansion initiated after the effective date of this code, as adopted, exceeds 30% of the buildinq. When cumulative buildinq remodel or expansion exceeds 50% of the buildinq must comply within 18 months of permit application. (Reason: Consistent with local practice Consistent with regional amendment to IFC 907.1.3.) Section 907.2.3; change to read as follows: 907.2.3 Group E. A manual fire alarm system shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildinqs, whether portable buildinqs or the main buildinq, will be considered one buildinq for alarm occupant load consideration and interconnection of alarm systems. (Reason: To distinguish educational from day care occupancy minimum protection requirements. Further, to define threshold at which portable buildings are considered a separate building for the purposes of alarm systems. Consistent with regional amendment to IFC 907.2.3.) Section 907.2.3; change exception #1 and add exception #1.1 added to read as follows: Group E educational and day care occupancies with an occupant load of less than 50 when provided with an approved automatic sprinkler system. 1.1 Residential In-Home day care with not more than 12 children may use interconnected sinqle station detectors in all habitable rooms. (For care of more than five children 2 1/2 or less years of aqe, see Section 907.2.6.) 10 (Reason: Consistent with Texas State laws concerning day care facility requirements. Consistent with regional amendment to IFC 907.2.3.) Section 907.2.12; change to read as follows: 907.2.12 High-rise buildings. Buildings having any floors used for human occupancy located more than 7á 55 feet (~ 16 764 mm) or three stories above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voice/alarm communications system in accordance with Section 907.2.12.2. (Reason: To correct per definition of high-rise. Consistent with regional amendment to IFC 907.2.12.) Section 907.2.12, exception #3; change to read as follows: 3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1, when used for open air seatinq; however, this exception does not apply to accessory uses includinq but not limited to sky boxes, restaurants and similarly enclosed areas. (Reason: To indicate that enclosed areas within open air seating type occupancies are not excepted from automatic fire alarm system requirements. Consistent with regional amendment to IFC 907.2.12.) Section 907.3; add a second paragraph to read as follows: Manual alarm actuatinq devices shall be an approved double action type. (Reason: Consistent with local requirements. Consistent with regional amendment to IFC 907.4.) Add Section 907.5.1 to read as follows: 907.5.1 Installation. All fire alarm systems shall be installed in such a manner that the failure of any sinqle alarm- actuatinq or alarm-indicatinq device will not interfere with the normal operation of any other such devices. All systems shall be Class "AU wired with a minimum of six feet separation between supply and return loops. IOC - Class "Au style - 0 - SLC Class "A" Style 6 - notification Class "Bu Style Y. (Reason: To provide uniformity in system specifications and guidance to design engineers. Consistent with regional amendment to IFC 907.6.1.) **Section 907.8.2; change to read as follows: 907.8.2 High-rise buildings. In buildings that have floors located more than :f.é 55 feet (22 860 16 764 mm) or three stories above the. . . {remainder of section unchanged}. (Reason: Consistent with high rise definition as amended.) Section 911; add subsection 911.2 as follows: 911.2 Emergency Radio Communications. In all buildings in which the type of construction or distance from an operational emergency services antenna or dispatch site does not provide adequate frequency or signal strength as determined by as determined by the fire code official, the building owner shall be responsible for providing the equipment, installation and maintenance of said equipment in a manner to strengthen the radio signal. The radio signal shall meet the minimum input / output strengths according to the emergency radio system's provider and system manager. (Reason: Assures that emergency communications are available, functional and provided in all areas where may be needed.) Section 1008.1.3.4; add item # 7. as follows: 1008.1.3.4 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 or R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria: 11 A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2 Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm t01219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads "PUSH TO EXIT". When operated. the manual unlocking device shall result in direct interruption of power to the lock - independent of the access control system electronics - and the doors shall remain unlocked for a minimum of 30 seconds. 4 Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. 7. If a full buildinG smoke detection system is not provided, approved smoke detectors shall be provided on both the access and eGress sides of doors and in a location approved by the authority havinq iurisdiction of NFPA 72. Actuation of a smoke detector shall automatically unlock the door. (Reason: To provide for emergency egress in event of a fire without having to find "push to exit" button in smoke condition.) Section 1019.1.8; change to read as follows: 1019.1.8 Smokeproof enclosures. In buildings required to comply with Section 403 or 405, each of the exits of a building that serves stories where Ute any floor surface is located more than 7-á 55 feet (22 860 16 764 mm) above the lowest level of fire. . . {remainder of section unchanged}. (Reason: Consistent with high rise definition as amended.) Section 1101.2; add an exception to read as follows: Exception: BuildinGs reGulated under State Law and built in accordance with State certified plans, includinq any variances or waivers Granted by the State, shall be deemed to be in compliance with the requirements of this Chapter. (Reason: To accommodate buildings regulated under Texas State law.) Section 1109.2.1; change to read as follows: 1109.2.1 Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an accessible unisex toilet room shall be provided where an aggregate of six or more male and female water closets are required provided. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the unisex toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessible unisex bathing room shall be provided. Fixtures located within unisex toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy. Exception: Where each separate-sex bathing room has only one shower or bathing room is not required. (Reason: Amendment is necessary to coincide with amendments in IBC Chapter 29.) bathtub fixture, a unisex Section 1210.2, exception #2; change to read as follows: 2 Toilet rooms that are not accessible to the public and which have not more than one water closet; provided that walls around urinals are constructed with the minimum surroundinG material specified by Section 419.3 of the International PlumbinG Code. (Reason: Recognize the minimum wall material requirements of the IPC. Consistent with regional amendment to IPC 419.3.) 12 Section 1403.3; change to read as follows: 1403.3 Vapor retarder. (See also definition) An approved '/3por retarder Sh311 be provided. In all framed walls. floors and roof/ceilinqs comprisinq elements of the buildinq thermal envelope. a vapor retarder. when installed. shall be installed in a manner so as to not trap moisture. Vapor retarders shall be tested in accordance with ASTM E 96. (delete all exceptions) (Reason: Vapor retarders installed in this region perform best if the vapor retarder is installed in a position opposite that of position required in northern climates in the nation. However, no vapor retarder at all is preferable in this region.) Table 1505.1; replace footnotes band c with the following: b All individual replacement shinqles or shakes shall be in compliance with the ratinq required by this table. c. Non-classified roof coverinqs shall be permitted on buildinqs of U occupancies havinq not more than 120 Sq.ft. of proiected roof area. When exceedinq 120 Sq.ft of proiected roof area, buildinqs of U occupancies may use non-rated non-combustible roof coverinqs. (Reason: Conforms to local practice affording increased fire protection.) Table 1507.8; change deck requirement as follows: 2. Deck requirement. Eliminate climate distinction and require solid sheathing under either wood shakes or wood shingles Also amend 1507.8.11507.9.1 to permit only solid sheathing. (Reason: Solid sheathing makes roof replacement easier. In event of a roof fire less ait is available to the fire.) Section 1612.1; Insert name and date as follows: 1612.3 Establishment of flood hazard areas. To establish flood hazard areas, the governing body shall adopt a flood hazard map and supporting data. The flood hazard map shall include, at a minimum, areas of special flood hazard as identified by the Federal Emergency Management Agency in an engineering report entitled "The Flood Insurance Study for The City of Southlake, Texas," as amended or revised with the accompanying Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map (FBFM) and related supporting data along with any revisions thereto. The adopted flood hazard map and supporting data are hereby adopted by reference and declared to be part of this section. Add Section 2308.2.3 to read as follows: 2308.2.3 Application to enQineered desiQn. When accepted by the Buildinq Official, any portion of this section is permitted to apply to buildinqs that are otherwise outside the limitations of this section provided that: 1. The resultinq desiqn will comply with the requirements specified in Chapter 16; 2. The load limitations of various elements of this section are not exceeded; and 3. The portions of this section which will apply are identified by an enqineer in the construction documents. (Reason: Allows engineer to reference Section 2308 for designs for wood structures; eliminates excessive engineering.) Section 2901.1; add a sentence to read as follows: The provisions of this Chapter are intended to coordinate with the provisions of Chapter 4 of the International Plumbinq Code. Should a conflict arise between this chapter and Chapter 4, the Buildinq Official shall determine which provision applies. (Reason: Gives building official discretion.) 13 Section 2902.1, 2902.1.1 and 2902.1.2; change to read as follows and add sub- sections: 2902.1 Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number as follows: 1 Assembly Occupancies: At least one drinkinç¡ fountain shall be provided at each floor level in an approved location. Exception: A drinkinç¡ fountain need not be provided in a drinkinç¡ or dininç¡ establishment. 2. Groups A, B, F, H, I, M and S Occupancies: Buildinç¡s or portions thereof where persons are employed shall be provided with at least one water closet for each sex except as provided for in Section 2902.2. 3. Group E Occupancies: Shall be provided with fixtures as shown in Table 2902.1. 4. Group R Occupancies: Shall be provided with fixtures as shown in Table 2902.1. It is recommended, but not required, that the minimum number of fixtures provided also comply with the number shown in Table 2902.1. Types of occupancies not shown in Table 2902.1 shall be considered individually by the building official The number of occupants shall be determined by this code. Occupancy classification shall be determined in accordance with Chapter 3. (Reason: To allow flexibility to designer to consider specific occupancy and keep Building Official from becoming toilet police.) 2902.1.1 Unisex toilet and bath fixtures. Fixtures located within unisex toilet and bathinq rooms complyinç¡ with Chapter 11 are permitted to be included in determininç¡ the minimum required number of fixtures for assembly and mercantile occupancies. (Reason: Clarify intent.) 2902.1.2 Finish material. Finish materials shall comply with Section 1210. Section 3403.1; add exceptions 2 and 3 as follows: §3403.1 Existing buildings or structures. Additions or alterations to any building or structure shall conform with the requirements of the code for new construction. Additions or alterations shall not be made to an existing building or structure which will cause the existing building or structure to be in violation of any provisions of this code. An existing building plus additions shall comply with the height and area provisions of Chapter 5. Portions of the structure not altered and not affected by the alteration are not required to comply with the code requirements for a new structure. EXGEPTION§: .L For buildings and structures in flood hazard areas established in §1612.3, any additions, alterations or repairs that constitute substantial improvement of the existing structure, as defined in §1612.2, shall comply with the flood design requirements for new construction and all aspects of the existing structure shall be brought into compliance with the requirements for new construction for flood design. 2. For additions where chapter 9 of this code or the Fire Code require structures to have fire protection system(s) such systems installed throuqhout the buildinç¡, both existinq and new portions. 3. Alterations shall not require fire protection systems be added due to area limits specified in chapter 9 of this code or the Fire Code. (For chanç¡e of occupancy see section 3406.) 3410.2 Applicability. Structures existing prior to annexation into the city limits or constructed within the city prior to June 20, 1978 , in which there is work involving additions, alterations or changes of occupancy shall be made to conform to the requirements of this section or the provisions of Sections 3403 through 3407. The provisions in Sections 3410.2.1 through 3410.2.5 shall apply to existing occupancies that will continue to be, or are proposed to be, in Groups A, B. E, F, M, R, Sand U. These provisions shall not apply to buildings with occupancies in Group H or I. (Reason: To properly address buildings constructed without any regulating codes or inspections.) Section H101.1: add the following paragraph: The siqn ordinance of the City of Southlake is not chanqed by this chapter. This chapter is intended to only provide the structural standards for siqns. In any conflict. the siqn ordinance shall take precedence. SectionJ103.2: amend the exemptions as follows: J103.2 Exemptions. 14 A grading permit shall not be required for the following: 1. Grading in an isolated, self-contained area, provided there is no danger to the public, and that such grading will not adversely affect adjoining properties when approved by the Buildinq Official. 2. Excavation for construction of a structure permitted under this code. 3. Cemetery graves. 1. Refuse diE:posal sites controlled by other regulations. 6. Excav:JtionE: for wells, or trencheE: for utilities. 6. Mining, qu:mying, excavating, proceE:E:ing or stockpiling rock, E::md, gr:JVel, 3ggreg3te or cl3y controlled by other regulations, provided such operations do not 3ffect the lateral support of, or E:ignific3ntly incro3E:e streE:ses in, soil on 3djoining properties. 7. Exploratory excav3tions performed under the direction of a registered design profeE:E:ion31. (This phrase was 3dded to 3ssure th3t the "explor3tory excav3tion" is not to begin construction of 3 building prior to receiving a permit, but is for the sole purpose of preparing a soils report.) Exemption from the permit requirements of this appendix shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or ordinances of this jurisdiction. END OF AMENDMENTS. 15 INVOICE Star-Telegram Customer ID: CIT57 400 W.7th Street Invoice Number: 243462931 FORT WORTH,TX 76102 (817)390-7761 Invoice Date: 7/6/04 Federal Tax ID 22-3148254 Terms: Net due in 21 days Due Date: 7/31/04 Bill To: PO Number: CITY OF SOUTHLAKE 1400 MAIN ST Order Number: 24346293 STE 440 Sales Rep: 073 SOUTHLAKE, TX 76092-7604 Description: CITY OF SOUTHLA SO TTSOUTHLAKEPublication Date: 7/6/04 Attn FINANCE . DEPT Novo. hearina will be .�. on Ju y 20, 2004, at CITY OF SOUTHLAKE Notice is he a p'ol immthteltlowi e I 112 112 LINE $0.81 $90.72 Work Session, during the Regular City Council meeting to be held in the City Council Chambers of Town Hall,1400 Main Street, Southlake, Net Amount: $90.72 Texas.Purpose of the public ere he second reading of the fol- lowing ordinance: 2003 International Building Code ORDINANCE NO. AN ORDINANCE ADOPTING THE 2003 EDITION OF THE INTERNATION- AL BUILDING CODE REGULATING THE TU CENSRCTIIONT - LARGEMENR AL- TERATION REPAIR,DELONMOItI ON- "i. CHRISTY L.HOLLAND VERSION, OCCU- '4• PANCY, EQUIP- /'r MENT USE • ' MY COMMISSION EXPIRES HEIGHT AREA AND • MAINTENANCE. OF �� drtF' UI..Y 31,2004 ALL BUILDINGS OR .,,„,y STRUCTURES, EX- - - CEPT ONE- AND THE STATE OF TEXAS TWO- FAMILY DWELLINGS AND County of Tarrant FAMILY DWELLINGS (TOWNHOUSES), IN THE CITY OF Before me,a Notary Public in and for said County p°ROVIDING FOR)rally appeared Lisa Wesselman, Bid and Legal Coordinator for the Star-Telegram, published by the Star-Teleg LOCAL OPTION OF in Tarrant County,Texas;and who,after being duly sworn, did depose and say AMEND- that the attached clipping of an advertisement was MENTS THERETO•name pap n the listed da es: BIDS LEGAL DEPT. STAR TLEGRAM PROVIDING FON (817) 390-7320 PUBLIC �E As A ✓�� /,� PROVIDING ECORATHAfi `� THIS ORDINANCE SHALL BE CUMU- LATIVE OF ALL SUBSCRIBED AND SWORN TO BEFORE ME, T PROVIDING A SEV-• 2004• ERABILITY CLAUSE; PROVIDING FOR A PENALTY FOR VIO- LATIONS HEREOF; PROVIDING A SAV- INGS CLAUSE; PROVIDING FOR PUBLICATION IN PAMPHLETI FORK 9 Thank PUBLICATION IN You For Your Payment THE OFFICIAL PROVIDINGRANANDEF- FECTIVE DATE. SECTION 6 Any person, firm or corporation who vio- lates,disobeys,omits. neglects or refuses to comply with or who Customer ID: CIT57 Remit To: Star-Telegram resists the yenforce- provisionsaof th s ore-1 P.O. Box 901051 dinance shall be fined i Customer Name: CITY OF SOUTHLAKE not more than Two I FORT WORTH, TX 7H Thousand Dollars c$ Invoice Number: 243462931 2,000.00) for all vio- lations involving zon- ing, fire safety or public• health and Invoice Amount: $90.72 sanitation, including dumpingor refuse and more fanefive fined PO Number: droll rs($500)for ;fiiaa etIon°; Amount Enclosed: $ to exist shall ��s"erote C City Secretary INVOICE Star-Telegram Customer ID: CIT57 400 W.7th Street Invoice Number: 244155731 FORT WORTH,TX 76102 (817)390 7761 Invoice Date: 7/23/04 Federal Tax ID 22-3148254 Terms: Net due in 21 days Due Date: 7/31/04 Bill To: PO Number: CITY OF SOUTHLAKE 1400 MAIN ST Order Number: 24415573 STE 440 Sales Rep: 073 SOUTHLAKE, TX 76092-7604 Description: CITY OF SOUTHLA Publication Date: 7/23/04 CITY OF SOUTHLAKE U�22y0003 Interna I3580 1 99 99 LINE $0.81 $80.19 OF 200KE 3�International O NIDOI BCEs Net Amount: $80.19 AN ORDINANCE ADOPTING THE 2003 EDITION OF THE INTERNATION- AL ERECTION CON- STRUCTION EN- LARGEMENT, AL- t� --.-, MOVINTERATION, REPAIR, [ill Iy I� R Q W . )` DEMOLIIITION OCON- LLSS IUr U VERSION, OCCU- PANCY, EQUSE, I 1 MAIHEINTEIJANCE EA AOF AUG ZQU4ill ALL BUILDINGS OR • I STRUCTURES, EX- CEPT ONE- AND • 11k TWO- FAMILY _ CHRIST(L HOLLAND '� _ MY COMMISSION EXPIRES DWELLINGS AND *: K: OFFICE OF CITY SECRETARY MULTIPLE SINGLE- FAMILY DWELLINGS July 31,20()8 (TOWNHOUSES), IN , 1 ` TSOUTHLAKE AND ~ THEVADOPTIONFOF THE STATE OF LOCAL AMEND- County of AMEND- ,. PROVIDING THERETO; RECORDING OF SUCH CODE AS A Before me,a NC PROVIDING E°CHAT •id County and State, this day personally appeared Lisa Wesselman, Bid and Legal Coordinator for the Star-TeIE SHALL ORDINANCE CUMU- Star-Telegram, Inc.at Fort Worth, in arrant County,Texas; and who, her being duly sworn, did depose and say that the attaches O RIDE N A N C ALL 'ment was published in the above nami�paper on the listed dates. BI el LEGAL DEPT. STAR TLEGRAM (817) 390-73 ERABIOTY CLAUSE; t//� PROVIDING FOR A /� PENALTY FOR VIO- LATIONS HEREOF; Signed mir PROVIDING A SAV- INGS CLAUSE PROVIDING FOR July 2 2 SUBSCRIBED? PUBLICATION UB ICATIO TORN tE ME, THIS Thursday, • OVIDING // PUBLICATION IN // THE OFFICIAL Notary Public rlih 'Y"[// PROVIDINGRANAND EF- FECTIVE DATE. SECTION 6 Any person, firm or corporation who vio- Thank You naeglecs orrerefus sitfo lent comply with or who. resists the enforce- ment of any of the provisions of this or- dinance shall be fined not more than Two Thousand Dollars ($ 2,000.00) for all vio- lations involving zon- Remit Customer ID: CIT57 To: in ire sa publicf healthfety andor sanitation, including dumping or refuse, Customer Name: CITY OF SOUTHLAKE and shall be fined not more thanr five5 )for TX 76101-2051 Invoice Number: 244155731 all o other atio for all violations of this ordinance. Each day that a violation is Invoice Amount: $80.19 permitted to exist shall constitute a separate PASSED AND AP- PO Number: PROVED THIS THE _w.1 20th DAY OF JULY 20E04(1�D,gURRING TK Amount Enclosed: � 8QBNCI LMEETING . MAYOR: Andy Wambgpanss ATTE Lori Farwell, City Secretary