08152000 International Building Code
ORDINANCE NO. 815
AN ORDINANCE ~M)OPT1NG THE 2000 EDITION OF THE INTERNATIONAL
BUILDING CODE, REGULATING THE ERECTION, CONSTRUCTION,
ENLARGEMENT, ALTERATION, REPAIR, MOVING, REMOVAL,
DEMOLITION, CONVERSION, OCCUPANCY, EQUIPMENT, USE, HEIGHT,
AREA AND MAINTENANCE OF ALL BUILDINGS OR STRUCTURES, EXCEPT
()NE- AND TWO-FAMILY DWELLINGS AND MULTIPLE SINGLE-FAMILY
D'~VELLINGS (TO~VNHOUSES), IN THE CITY OF SOUTHLAKE; PROVIDING
FOR THE .M)OPTION OF LOCAL AMENDMENTS THERETO; PRO'~q[DING FOR
RECORDING OF SUCH CODE AS A PUBLIC RECORD;.PROVIDING THAT THIS
ORDINANCE SHALI. BE CUMULATIVE OF ALI. ORDINANCES; PROVIDING
A SEVERABILITY CLAUSE: PROVIDING FOR A PENALTY FOR VIOLATIONS
ItEREOF; PROVIDING A SAVINGS CLAUSE; PROVIDING FOR PUBLICATION
IN PAMPHLET FORM; PROVIDING FOR PUBLICATION IN THE OFFICIAL
NEWSPAPER; AND PROVIDING AN EFFECTIVE DATE.
WHEREAS, the City of Southlake is a home rule city acting under its charter adopted by
the electorate pursuant to Article XI, Section 5 of the Texas Constitution and Chapter 9 of the Local
Government Code; and
WHEREAS, the City Council of the City of Southlake deems it necessa~ to adopt this
ordinance providing minimum standards to safeguard the health, property, and welfare of the citizens
of South]ake bv regulating and controlling the use, occupancy, maintenance, repair, design,
construction aod quality of materials for buildings and structures within the City.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY
OF SOUTHLAKE, TEXAS:
SECTION 1
That the International Building Code, 2000 Edition, published by the International Code
Council. including the standards referenced therein, including Appendix Chapters A, C, F, G, H,
I and J are hcreby adopted as the Building Code of the City of Southlake regulating the erection,
construction, enlargement, alteration, repair, moving, removal, demolition, conversion,
occupancy, equipment, use. height, area and maintenance of all buildings or structures, except
one and lwo-i'amily dwellings and multiple single family dwellings (townhouses), in the City of
Southlake. 7rue and correct copies of these documents are attached as Exhibit "A."
SECTION 2
That the 2000 international Building code, as adopted herein, is hereby amended as provided in
Exhibil "B" incorporated herein and attached hereto for all purposes of this ordinance. The City
of Southlake. Texas may from time to time determine that additional local modifications to the
Building Code are necessary and appropriate to meet the unique needs of the City of Southlake,
Texas. To effectuate these local modifications, the City Council shall enact individual
ordinances amending this Ordinance, fully setting forth the change to be made in the Building
Code. These amendments shall be consolidaled as Exhibit "B" to this Ordinance.
SECTION 3
['he material contained m Exhibits "A" and "B" to this ordinance shall not be included in the
lbrmal nmnicipal codification of ordinances, but shall be maintained as a public record in the
office oflhe City Sccreta~ and will be available for public inspection and copying during
regular business hours.
SECTION 4
This ordinance shall be cumulative of all provisions of ordinances of the City of
Southlake, Texas, except where the provisions of this ordinance are in direct conflict with the
provisions of such ordinances, in which event the conflicting provisions of such ordinances are
hereby repealed.
'['his ordinance is intended to replace the following: 1. Ordinance 693, as amended, the 1997 Uniform Building Code.
2. Ordinance 621, the 1994 Uniform Administrative Code.
This ordinance is not intended to amend or replace the following:
Ordinance 480, the Zoning Ordinance.
2. Ordinance 483, the Subdivision Ordinance.
3. Ordinance 557, Exterior Masonry Construction Requirements
4. Ordinance 568, Contractor's Licensing Ordinance
Ordinance 506-A, as amended, the Sign Ordinance
SECTION 5
I~ is hereby declared to be the intention of the City council that the phrases, clauses,
sentences, paragraphs, and sections of this ordinance are severable, and if any phrase, clause
scmence, paragraph or section of this ordinance shall be declared unconstitutional by the valid
2
.I udgment or decree of any courl of competent jurisdiction, sucln unconstitutionality shall not
afl'cci any of the remaining phrases, clauses, sentences, paragraphs and sections of this ordinance,
since thc same would lnave been enacted by tine City Council without the incorporation in this
ordinance of any such unconstitutional phrase, clause, sentence, paragraph or section.
SECTION 6
Any person, firm or corporation who violates, disobeys, omits, neglects or refuses to
comply with or who resists fine enforcement of any of the provisions of this ordinance shall be
fined no~ more than Two Thousand Dollars ($ 2,000.00) for all violations involving zoning, fire
safety or public healtln and sanitation, including dumping or refuse, and shall be fined not more
tlmn five hundred dollars ($500) for all other violations of this ordinance. Each day that a
violation is pennitled to exisl shall constitute a separate offense.
SECTION 7
All rights and remedies of the City of Southlake are expressly saved as to any and all
x iolations of the provisions of any ordinances affecting the regulation and control of the use,
occupancy, maintenance, repair, design, construction and quality of materials for buildings and
structures x~ itlmn the City whicln have accrued at the time of the effective date of this ordinance;
and. as to sucln accrued violations and all pending litigation, both civil and criminal, whether
pending in court or not, under such ordinances, same shall not be affected by this ordinance bul
may be prosecuted until final disposition by the courts.
SECTION 8
The City Secretau of the City of Southlake is hereby authorized to publish this ordinance
in book or pamphlet form for general distribution among the public, and the operative provisions
of this ordinance as so published shall be admissible in evidence in all courts without further
prooftNm tine produclion thereof.
SECTION 9
Thc Cit5 Secretary of the City of Southlake is hereby directed to publish in the official newspaper
of linc City of Soutlnlake, tine caption, penalty clause, publication clause and effective date of this
ordinm~ce one time within ten days after passage of this ordinance, as required by Section 3.13 of
tine Charter of the City of Southlake.
SECTION 10
This ordinance shall be in full force and effect from and after its passage and publication
as required by law, and it is so ordained.
PASSED .AND APPROVED ON FIRST READING THIS ~ DAY OF
~ · ~ ~ITY SECRETARY
~oI·
CITY SECRETARY
APPRO!VED AS TO FORM AND I.EGALITY:
City Attorney /
Date:
EFFECTIVE:
4
EXHIBIT "B"
LOCAL AMENDMENTS TO THE 2000 INTERNATIONAL BUILDING CODE
Die £ollowing sections, paragraphs, and sentences of the 2000 International Building Code are
ac-cb> amended as follows:
(Standard t_vpe is text from the IBC Underlined type is text inserted ~
**Section 101.4; change to read as follows:
101.4 Rel~renced codes. The other codes listed in Sections 101.4.1 through 101.4.7 and referenced
elsewhere in this code, when specifically adopte& shall be considered part of the requirements of
this code to lhe prescribed extend of each such reference. Whenever amendments have been
adopted to the referenced codes and standards, each reference to said code and standard shall be
considered to reference the amendnrents as well. Any reference to NFPA 70 or the ICC Electrical
('ode shall mean thc Electrical Code as adopted.
**Section 105.1; eha,ge to read as.follows:
105.1 Required. Any owner or authorized agent who intends to construct, enlarge, alter, repair,
move, demolish, or change the occupancy ora building or structure, to excavate or change the grade
of any property, or to erect, install, enlarge, alter, repair, remove, convert or replace any electrical,
gas, mechanical or plumbing system, the installation of which is regulated by this code, or to cause
an,~ such work to be done, shall first make application to the building official and obtain the
required permit.
**Sectio, 106.2; challg~ to read as follows:
106.2 Site plan. Thc construction documents submitted with the application for pennit shall be
accompanied by a sile plan shoxxing to scale the size and location of new construction and existing
slructures on thc site, distances from lot lines, the established street grades and the proposed
finished grades; and it shall be drawn in accordance with an accurate boundary line survey. Plans
shall also show proposed erosion control and tree protection measures in accordance with
recognized standards and any additional infomlation as required bv other ordinances. In the case of
demolition, the site plan shall show construction to be demolished and the location and size of
exisling straclures and construction that are to remain on the site or plot. The building official is
authorized to waive or modify the requirement for a site plan when the application for permit is for
aheralion or repair Ol- when otherwise warranted.
**Seetio, 109.3.5: delete.
5
'~*Section 112; delete entirel)' and substitute the./bllowing:
SECTION 112 BOARD OF APPEALS
112.1 General. In order to hear and decide appeals of orders, decisions or determinations made bv
thc buildin~ official relative to the application and interpretation of this code. there shall be and is
hcrebx created a board of appeals. The Building Board of Appeals as established bv ordinance 622
as amended shall be the Board of Appeals referenced in this code.
112.2 Limitations on authority. An application for appeal shall be based on a claim that the true
intent of this code or the rules legally adopted thereunder have been incorrectly interpreted, the
provisions of this code do not fully apply, or an equally good or better form of construction is
proposed. The board shall have no authority to waive requirements of this code.
**Section 110.1; change to read as./ollows:
110.1 Use and occupancy. No building or structure shall be used or occupied, and no change in the
existing occupancy classification or occupant, either owner or tenant, of a building or structure or
portion thereof sbatl be made until the building official has issued a certificate of occupancy therefor
as prox idcd herein. Issuance ora certificate of occupancy shall not be construed as an approval of a
viola0on of the provisions of this code or of other ordinances of the jurisdiction.
**Section 202; add a new definition to read as follows:
HIGH-RISE BUILDING is a buildina havin.~ floors used for human occupancy located more than
55 feet (16 764 mm) or three stories above the lowest level of fire department vehicle access.
**Table 302.3.3, faotnote e; change to read as follows:
c. Assembly uses accesso~?' to Group E Occupancy must comply with the provisions for Group A
Occupancv bm for the purpose of Section 302.3 are not considered separate occupancies.
*:"Section 403.1; change to read as fallows:
403.1 Applicability. The provisions of this section shall apply to buildings having occupied floors
located more than 74 55 feet (22 86(? 16 764 mm) above thc lowest level of fire department vehicle
access.
**Section 403.1, exception #3: change to read as follows:
3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1 when used
for open air seatino,; however, this exception does not appl5, to accessory uses including
but not limited to sky boxes restaurants and similarly enclosed areas.
6
**Section 403.2, exception #2; delete.
**Section 406.6.1; add a second paragraph to read as follows:
This occupancx shall include garages involved in servicina of motor vehicles for items such
as lube chan~es, it!hpections, windshield repair or replacement, shocks, minor part replacement and
other sach non-major repair. When the repair aara~e is only involved in such minor repair, it need
nol compt¥ with Section 406.6.2.
**Section 506.2.2; add a sentence to read as follows:
order to be considered as accessible, if not in direct contact with a street or fire lane, a minimum
1 O-fool wide pathway from the street or approved fire lane must be provided. (See International
]:'irc ('ode Section 503.1.1 for hose lay measurement pathway requirements.)
**Section 705.11; change the exception to read as follows:
Exception: For other than hazardous exhaust ducts, penetrations by ducts and air transfer openings
of . . /remainder qf exce£tion unchangedj.
**Section 715.5.2: add exception # 4 to read as.follows:
4. In the duct penetration of the separation between the private garage and its residence when
constructed in accordance with Section 302.3.3, exceptions #2 and 3.
**Section 902.1; under "Standpipe, Types off' dqfinition amend "Manual dry" bi; adding a
sentence to read as follows:
The system must be supervised as specified in Section 905.2.
**Section 903.1.2; change to read as follows:
903.1.2 Residential systems. Unless specifically allowed by this code, residential spnnkler systems
installed in accordance with NFPA 13D or NFPA 13R shall not be recognized for the purposes of
exceptions or reductions, commonly referred to as "trade-offs", permitted by other requirements of
this code.
In addition, residential sprinkler systems installed in accordance with NFPA 13R must
include attic sprinkler protection to be recognized for the purposes of such trade-offs permitted by
other requirements of this code.
**Sections 903.2.1.1, 903.2.1.2, 903.2.1.3 and 903.2.1.4; change to read as follows:
903.2.1.1 Group A-1. An aulomatic sprinkler system shall be provided throughout a fire area
con,Z,2,,~, ~.,,,-,,-,, a for Group A-I occ~:~anc"~,, : Occupancies where one of the followin~ conditions exists:
1. The fire area exceeds q2,000 6.000 square feet (11 ]5 m-~¥
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than the level of exit discharge.
4. Thc fire area contains a multi theater complex.
903.2.1.2 Group A-2. An automatic sprinkler system shall be provided ~
cenlaininz-a for Group A-2 occupg, ucy Occupancies where one of the following conditions exists:
1. The fire area exceeds 5,000 square feet (464.5 m2).
2. Thc fire area has an occupant load of 300 or more.
The fire area is located on a floor other than the level of exit discharge.
903.2.1.3 Group A-3. An automatic sprimkler system shall be provided ~
centainina a for Group A-3 e, ccupancy Occupancies where one of the following conditions exists:
1. Thc fire area exceeds 12,000 6,000 square feet (! ! !5 mak
2. Thc fire area has an occupant load of 300 or more.
3. Thc fire area is located on a floor other than the level of exit discharge.
Exception: Areas used exclusively as participant spor~s areas where the main floor area is
located at the stone level as the level of exit discharge of the main entrance and exit.
903.2.1.4 Group A-4. An automatic sprinkler system shall be provided
centaining a for Group A-4 occupancy Occupancies where one of the following conditions exists:
1. Tile fire area exceeds !2,000 6.000 square feet (1115
The fire area has an occupan! load of 300 or more.
3. Tile fire area is located on a floor other than the level of exit discharge.
Exception: Areas used exclusively as participant sports areas where tile main floor area is
located at lhe same level as tile level of exit discharge of the main entrance and exit.
**Section 903.2. 7: change to read as follows:
903.2.7 Group R-1. An automatic sprinkler system shall be provided throughout buildings with a
Group Rd fire area.
Exceptions:
~1. A residential sprinkler system installed in accordance with Section 903.3.1.2 shall be
allowed in buildings, or portions thereof, of Group R-1.
**Section 903.2.8: change to read as follows:
903.2.8 Group R-2. An automatic sprinkler system shall be provided throughout all buildings with
a Group R-2 fire area where more than Pea3~4owes one stop/in height, including basements,
or where having more than 16 dwelling units.
[m'c~7~fion unchanged].
**Add Section 903.2.10.3 to read as follows:
903.2.10.3. Self-service storage facility. ,An automatic sprinkler system shall be installed
throuo_hou~ all self-service storage facilities.
8
Exception: One-stor~ self-service storage facilities that have no interior corridors,
wilb a one-hour fire barrier wall installed between every storage compartment.
**Section 903.2.12.3; amend as follows:
903.2.12.3 Buildings over ~ 35 feet in height. ,An automatic sprinkler system shall be installed
throughout buildings with a floor level, other than penthouses in compliance with Section 1509.
having an ..... v .... lead ef 30 ar ...... that ~s located ~ o~ feet (16 764 10 668mm) or more above
thc Iowesl level of fire depa~ment vehicle access.
Exceptions:
2. Open parking structures ~n compliance wkb Section 406.
3. ~ .......... ;~' ;" ~ ..... F2
** Section 903.2.12; Add 903.2.12.4, 903.2.12.5 and 903.2.12.6 as follows:
903.2.12.4 High-Piled Combustible Storage. For any building with a clear height exceeding 12
feet (4572 mm). see Chapter 23 of the International Fire Code to determine if those provisions
apply.
903.2.12.5 Sprat' Booths and Rooms. Next' and existing sprav booths and spraying rooms shall be
protecled by an approved aulomatic fire-extintmishino_ st,siena.
903.2.12.6 Buildings Over 6,000 sq.ft. An automalic sprinkler system shall be installed
throughout all buildin<s over 6,000 sq.fl. For the purpose of this provision, fire walls shall not
define separate buildings.
Exception: Open parking garages in complim~ce with Section 406.3.
**Section 903.3.1.1.1; change to read as follows:
903.3.1.1.1 Exempt locations. When approved by the code official (defined in the fire code),
automatic ............ spnnklers shall not be required in the following rooms or areas where such
[hull; r!fsection u,changed/.., because it is damp, of fire-resistance-rated construction or contains
electrical equipment.
1. Any room where the application of water, or flame and water, constitutes a serious life or fire
hazard.
2. Any room or space where sprinklers are considered undcsirable because of the nature of the
contents, when approved by the ~ui,~i,,~ code official.
3. Generator and lransfo er rooms, under the direct control of a public utility, separated from the
remainder of the building by walls and floor, ceiling or rooffceiling assemblies having a fire-
resistance rating of not less than 2 hours.
~:~ roon]s 0r ~ .... tbat ..... nol ............... r ........ ........... 2 ...... on] .................
**Section 903.3.5: add a second paragraph to read as follows:
Water supptv as required lbr such systems shall be provided in conformance with the supply
requirements of the respective standards; howcver, eve;¥' fire prolection system shall be designed with
a I (I psi safety factor.
**Section 903.3. 7; change to read as follows:
903.3.7 Fire department connections. The location of fire departmenl connections shall be approved
b? the hui!ding code official (as defined in the fire code).
**Section 903.4; add a second paragraph after the exceptions to read as follows:
Sprinkler and standpipe system waler-flow detectors shall be provided for each floor tap to the sprinkler
svslem and shall cause an alarm upon detection of water flow for more than 45 seconds. All control
valx es in the sprinkler and standpipe systems except for fire department hose connection valves shall
be electricallv supervised to initiale a supervisory signal al the central station upon tampering.
**Section 905.2; change to read as follows:
905.2 Installation standards. Standpipe system shall be installed in accordance with this section mad
?-,~FPA 14. Manual d~' standpipe systems shall be supervised with a minimum of 10 psig and
a maximum of 40 psig air pressurc with a high'low alarm.
**Section 905.3.2: delete exceptions #I and 2.
**Section 905.4, item #5;change to read as follows:
Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope),
each standpipe shall be provided with an approved hose connection located either... O'emainder
c~f paragraph unchanged/...
**Section 905.9; add a second paragraph after the exceptions to read as follows:
Sprinkler a~d stm~dpipe system water-flow detectors shall be provided for each floor tap to the sprinkler
system and shall cause an alm~n upon detection of water flow for more than 45 seconds. Ail control
valx es in the sprinkler and stm~dpipe systems except for fire deparlment hose connection valves shall
be electrically supervised to initiate a supervisow signal at the central station upon tampering.
**.4dd Section 907.1.3 to read as follows:
907.1.3 Design Standards. All alarm systems new or replacement servim, 50 or more alarm
ac~uatin~ devices shall be addressable fire detection systems. Alarm systems serving more than 75
smoke de~ectors or more than 200 total alarm actix ating devices shall be analog, intelligent
addressahle fire detection systems.
l0
Exception: Existin2, systems need not comply unless the total building remodel or expansion
initiated arier thc effective date of this code, as adopted, exceeds 30% of the building. When
cumulative building remodel or expansion exceeds 50% of the buildine must comply within 18 months
permit application.
Section 90~2.3: change to read as follows:
907.2.3 Grnup E. A manual fire alam~ system shall be installed in Group E educational occupancies.
When automatic sprinkler syslems or smoke delectors are installed, such systems or detectors shall be
connected to the building fire alarm system. An approved smoke detection system shall be installed in
Group E day care occupancies. Unless separated bva minimum of 100' open space, all buildings,
,Mqether po~lable buildings or the main building, will be considered one building for alarm occupant
load consideration and interconnection of alarm systems.
** Section 907.2.3: change exception #1 and add exception #I. 1 added to read as follows:
Group E educational and day care occupancies with an occupant load of less than 50
when provided with an approved automatic sprinkler system.
1.1 Residential In-Home day care with not more than 12 children max' use
inlerconnected sinale station detectors in all habitable rooms. (For care of more
than fixe children 2 1/2 or less years of a~zc. see Section 907.2.6.)
**Section 907.2.12; change to read as follows:
907.2.12 High-rise buildings. Buildings having floors used for human occupancy located more than
74 55 feet (22 ~60 16 764 mm) or three stories above the lowest level of fire department vehicle access
shall be proxided with an automatic fire alarm system and an emergency voice/alarm communications
sSstcm in accordance with Section 907.2.12.2.
**Section 907.2.12, exception #3; change to read as follows:
3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1, when used for open
air seating: however, this exception does not apply to accessotw' uses including but not limited to sky
boxes, restaurants and similarly enclosed areas.
**Section 907.2.12.2; change the beginaiag paragraph to read as follows:
907.2.12.2 Emergenc) voice/alarm communication system. The operation of any automatic fire
detector, sprinkler water-flow device or manual fire alarm box shall automatically sound an alert tone
follox~ ed by voice instructions giving approved information and directions on a general or selective
basis to the follo,a lng terminal areas on a mininmm of the alamrin~ floor, the floor above, and the floor
below in accordance with the I~tternational Fire Code.
**Section 907.3: add a second paragraph to read as follows:
Manual alarm acluating devices shall be an approved double action type.
**Add Section 90T5.1 to read as follows:
907.5.1 Installation. All fire alarm systems shall be installed in such a manner that the failure of
an~ sin<le alarm-actuating or alarm-indicatin< device will not interfere with the normal operation of
anx other soch dex ices. All systems shall be Class "A" wired with a minimum of six feet separation
between supplx and return loops. IDC -- Class "A" style D - SLC Class -A" Style 6 - notification
Class '~a" Stile Y.
**Section 907.8.2; change to read as follows:
907.8.2 High-rise buildings. In huildings that have floors located more than ~5 5~5 feet ( ...... 16 764
mini or three stories above the... /remainder (~fseczion unchanged).
**Section 1003.2.12.2, exception #3; change to read as follows:
3. In occupancies in Group 1~3 F, H or in non-public portions of S balusters horizontal intermediate
rails or other... /remainder ~flexception unchanged].
**Section 1004.3.2.1; add an exception #5 to read as follows:
5. In Group B office buildings, corridor walls and ceilings need not be of fire-resistive construction
within office spaccs ora single tenant when the space is equipped with an approved automatic smoke-
detection %stem within the con-idor. The actuation of any detector shall activate alarms audible in all
areas ser,'ed b) the corridor. The smoke-detection system shall be connected to the building's fire alarm
system where such a system is provided.
**Section 1005.2. l; change to read as follows:
1005.2.1 Minimum number of exits. Ever,:, floor area shall be provided with the minimum number
of approved independent exits as required by Table 1005.2.1 based on the occupant load, except as
modified in Section ! 094.2.! or 1005.2.2. For the purposes of this chapter, occupied roofs shall...
/remainder qf sec~ion unchanged].
"Section 1005.3.2.5: change to read as follows:
1005.3.2.5 Smokeproof enclosures. In buildings required to comply with Section 403 or 405, each of
the exits ora building that serves stories where the floor surface is located more than 74 55 feet (22 ~0
16 764 mm) or tba'ee stories above thc lowest level of fire., iremainder qflsection unchanged].
**Sectiou 1101.2: add att exception to read as follows:
Exception: Buildings regulated under State Law and built in accordance with State certified
p aqs, includin~ any variances or waivers ,4ranted bv the State, shall be deemed to be in
compliance with the requirements of this Chapter.
22
**Section 1108.2.1: change to read as Jbllows:
1108.2.1 Unisex toilet and bathing rooms, in assembly and mercantile occupancies, an accessible
unisex toilet room shall be provided where an aggregate of six or more male and o~r female water
closets are ,~u ...... ..... ;'-"~ provided. In buildin~s~ of mixed occupancy,, only. those water closets.. .
/rcm~.nder oflseelio~ unrhanged/(
**Section 1209.2, exception ~2; change to read as follows:
2. 7oi}et ~ooms that are not accessible to the public and which have not more than one water closet2
provided that walls aroand m-inals comply with the minimum sm~ounding material specified bv
Section 419.3 of the ]~ternational Plumbin.~ Code
.... 3ectton 1403._; change to read as.follows:
1403.3 Vapor retarder. ~ ......... n ;..,~4 ......... ~;'-~ va"cr rc*~-'~ ~h~11 k ...... ;A~A In all
framed walls, floors and rooffceilings comprising elements of the buildine the~al envelope, a
xapor retarder, when installed, shall be installed in a manner so as to not trap moisture. Vapor
retm-ders slnall be tested in accordance with ASTM E 96.
(delete all exceptions)
**Table 15~5.1; replace fi~otnotes b and e with the following:
b. All indix idual replacement shingles or shakes shall be in compliance with the rating required by
this table.
c. Non classified roof coverings shall be pemaitted on buildings of U occupancies having not more
than 120 ~.fl. of projected roof area. When exceeding 120 sq.ft of projected roof area. buildings of
U occupancies may use non-rated non-combustible roof cox erings.
**Section 1505. 7; delete
**.4dd Section 2308.2.3 to read as follows:
2308.2.3 Application to engineered design. When accepted by the code official, any portion of
this section is permitted to apply to buildings thal are othemdse outside the limitations of this
section provided that:
I. The resulting desizn will comply with the requirements specified in Chapter 16;
2. The 10ad limitations 0f vari0us elements of this section are not exceeded: and
3. The portions of this section which will apply are identified by an engineer in the
construcfion documents.
13
**Section 2901.1; add a sentence to read as.follows:
Thc provisions of this Chapter are meant to work in coordination with the provisions of Chapter 4 of
the lnlernanonal Plumbin~ Code. Should an,,, conflicts arise between the two chapters, the Code
Official (as defined in the Plumbing Code) shall determine which provision applies.
** Section 2902.1: change to read as follows:
2902.1 Minimum number of fixtures. Plumbing fixtures shall be provided for the t,vpe of
occupancy and iT] the minimum number as follows:
1. Assembly Occupancies: At leasl one drinking fountain shall be provided at each floor level in
an approved location.
Exception: A drinkina fountain need not be provided in a drinking or dining establ shment
2. Groups A, B, F H. i, M and S Occupancies: Buildings or portions thereof where persons are
employed shall be provided with at least one water closet for each sex except as provided for in
Section 2902.2.
3. Group E Occupancies: Shall be provided with fixtures as shown ii] Table 2902.1.
4. Group R Occupancies: Shall be provided with fixtures as shown in Table 2902.1.
I1 is recommended, but not required, thai the minimum number of fixtures provided also comply
with the nmnber shown in Table 2902.1. Types of occupancies not shown in Table 2902.1 shall be
considered individually by the
_ · ......... ~ code official (as defined in the Plumbing COde) The
number of occupams shall be determined by this code. Occupancy classification shall be
delemqined in accordance with Chapter 3.
2902.1.1 Finish material. Finish materials shall comply with Section 1209.
2902.2 Unisex toilet and bath fixtures. Fixtures located within unisex toilet and bathin~ rooms
complying with Chapter 11 are permitted to be included in detenninin~ the minimum required number
of fixtures for assembly and mercantile occupancies.
**SectionHl 0l. 1: add the following paragraph:
The sign ordinance of the City of Southlake is not changed bv this chapter. This chapter is intended to
on]x. provide the structural standards for signs_.
END OF AMENDMENTS.
3_4
INVOICE
Star-Telegram Custo r:-..er ID: CIT5
400 W.7th Street Invoi Number: 20904-7831
FORT WORTH,TX 76102
(817)390-7761 Invoice Date: ..2'2?/01
Federal Tax ID 22-3148254 Terms: Net due in 21 days
Due Dlte: 12/31/01
Bill To: PO 1 umber:
CITY OF SOUTHLAKE
1400 MAIN ST Orclel,N Number: 20904783
STE 440 Sl.les Rep: 073
SOUTHLAKE, TX 76092-7604 ▪oc,:r:n:tlon: rTTV OF SOUTHLA
'F► lic tion Date: 12/21/01
;�� .:.:..<::...,�:.�; :'� . ...: : ..,:.::.. t� . wit dge � l� + i�t`
CITY OF SOUTHLAKE, TEXAS 2000 I3580 1 104 10 LINE $632.32
Sales Discount CITY OF
SOUTHLAKE, TEXAS ($548.08)
2000 International
Building Code
ORDINANCE NO.
815
AN ORDINANCE
ADOPTING THE
THE INTERNATION-
AL -t Amount: $84.24
REGULAT BUILDING
ERECTION CON-
STRUCTION, EN-
LARGEMEN ", AL-
TERATION REPAIR,
MOVING REMOVAL,
DEMOLITION, CON- © N a^
L.) .
VERSION, OCCU-
PANCY, EQUIP-
MAINTT AREA AND /
MAINTENANCE OF
ALL BUILDINGS OR
STRUCTURES, EX- 0 2002
CEPT ONE- AND
TWO- FAMILY
DWELLINGS AND
MULTIPLE SINGLE-
FAMILY DWELLINGS '� "`
TfTOWNH tiT,ES),clF -
•
THE STATE OFT SOUTHLAKE PRO- '',
V�Dp INe FOR THE
County of Tarran CALL AMENDMENTS
THERETO; PROVID-
ING FOR RECORD-
Before :1e,a Not OD
AS AO PUBLICF SUCH CRECE aid County and State,this y personally appeared ( ty Holland, iid nd Legal Coordinator
for the Star-Tele( o afi THIS PROVIDING
Star-Telegram, Inc. at For W rt , in Tarrant County axes; and v 10 after being duly sworn,did
deposeORDI-
and say tl NANCE SHALL BE ng of an advertisement as fled in the above ed aper o . e list d ates:
CUMULATIVE OF _
ALL ORDINANCES;
PROVIDING A SEV •
-
ERABILITY CLAUSE; Signed
PROVIDING FOR A
PENALTY FOR VIO-
SUBSC3IBED AN', CATIONS HEREOF;: ME,THIS Wednesday, Dece ber 26, 2 01.
PROVIDING A SAV-•
INGS CLAUSE 1 -
PROVIDING FOR /
PUBLICATION IN
PROVIDING FOFOF; Notary Public
PUBLICATION IN
THE OFFICIAL
NEWSPAPER; AND 'p"..""..."'."'"""ftm.'""'''."'"'4.*ati47t'r'<;\
PROVIDING AN EF-
FECTIVE VICKI L.WASON
DATE. MY COMMISSION EXPIRES
SECTION 6 Any person, firm orcorporation who vio-
lates,disobeys,omits, AUGUST 28,2004'
Thank You Fc neglects or refuses to If It
comply with or who ,v,..........,_....... ...............__.,___
—`-• � w- . _
resists the enforce-
. •—••••----• ment of any of the . _. ».................. ...... ..........__ _.,.., ............._...
provisions of this or-
dinance . ... .... ..... .""""...".".._.........` "."'."."
shall be fined
not more than Two
Thousand Dollars
o$2 000.00) for all vi-
lations involving
Remit To: Sty
zoning, fire safety or
public health and Customer ID: CIT57
sanitation, including
P.( dunmpng or fieu so Customer : 1-:: CITY OF SOUTHLAKE
more that five hundred
FC othle,via a,a°s fofrthls( 76101-2051 Invoice Number: 209047831
ordinance. Each day
that a violation is
permitted to exist shall
constitute a separate Invoice Amount: $84.24
offense.
PASSED AND AP-
PROVED BY THE PO Number:
CITY COUNCIL OF
SOUTHLAKE,
OUTH THIS THE' Amount Enc'cce1:
18tASh DAY OF DE- 3 `'
MAYOR RICKSTACY
ATTEST: SANDRA L.
SECRETARY CITY
APPROVED AS TO
FORM: E. ALLEN
TAVI C1R .IR CITY
INVOICE
Star-Telegram Customer ID: CIT57
400 W.7th Street Invoice Number: 208146281
FORT WORTH,TX 76102
(817)390-7761 Invoice Date: 11/30/01
Federal Tax ID 22-3148254 Terms: Net due in 21 days
Due Date: 11/30/01
Bill To: PO Number:
CITY OF SOUTHLAKE Order Number: 20814628
1400 MAIN ST
STE 440 Sales Rep: 073
SOUTHLAKE, TX 76092-7604 Description: CITY OF SOUTHLA
Publication Date: 11/30/01
Description Location Col Depth Linage MU Rate Amount;
CITY OF SOUTHLAKE,TEXAS NOTIC I3580 1 81 81 LINE $6.08 $492.48
CITY OF
Sales Discount SOUTHLAKE, TEXAS( ($426.87)
NOTICE was hereby
given to all Interested
persons that the City
Council of the City of
Southlake,Texas,will
be holding a public
hearing during the
regular city council Net Amount: $65.61
Decembermeetinp to 118,e 2001,on
he
meet g will p.m.:00 held
I the City Council
allChambers00f Main
Street, Southiake,
Texas.Purpose of the
hearing will be held
r. arding the follow-
In
2000 International
Building. Code
ORDINA8NCE NO.
AN ORDINANCE
ADOPTING
TF0DIION O
THE INTERNATION-
AL BUILDING CODE
REGULATING THE
• ERECTION CON-
THE STATE OF TEX, STRUCTION EN-
CON-
THE AL-
TERATION,County of Tarrant I EMOVAL,
DEMOLITION, CON-
VERSION, OCCU-
Before me,a Notary PANCY, EQUIP- and State,this d ersonally
MENT USE ounty appeared Christy Holland, Bid nd Legal Coordinator
for the Star-Telegran HEIGHT AREA ANI� -Telegram, Inc. at For W rth in Tarrant County,Texas; and who after beingdulyswor ,did
MAINTENANCE OF g
depose and say that ALL BUILDINGS OR f an advertisement •
STRUCTURES EX- as bl e din the above name er o t e lis ed dates:
CEPT ONE-AND
TWO- FAMILY
DWELLINGS AND Signed
FAMILY DWELLINGS
SUBSCRIBED AND S' HEwNHO1TEs) OF THIS Monday, December 0 , 2001.-
SOUTHLAKE; PRO-
VIDING FOR THE �� /
ADOPTION OF LO- .e
CAL AMENDMENTS Notary Public ..0e
THERETO, PROVID-
ING THAT THIS
ORDINANCE SHALL ,,,,,,,,,,x,
BE CUMULATIVE OF
ALL ORDINANCES;
PROVIDING A SEV- "�, VICKI L.WASON
ERABILITY CLAUSE;
PROVIDING FOR A ;° MY COMMISSION EXPIRES
PLqETIONTY S HEREOF;
Thank You For PROVIDING A snv. AUGUST 28,2004
INGS CLAUSE,* __
PROVIDING FOR
PUBLICATION IR�--- --••—
PAMPHLET FORM;
PROVIDING FOR
PUBLICATION IN
THE OFFICIAL
NEWSPAPER• AND