Loading...
0762ORDINANCE NO. 762 AN ORDINANCE OF THE CITY OF SOUTHLAKE, TEXAS, AMENDING THE CODE OF ORDINANCES OF THE CITY OFSOUTHLAKE, TEXAS BY ADOPTING THE 1997 EDITION OF TH E UNIFORM FIRE CODEVOLUMES 1 AND 2; REPEALING ORDINANCE NUMBER 572; REPEALING ALL ORDINANCES IN CONFLICT HEREWITH; PRESCRIBING REGULATIONS GOVERNING CONDITIONS HAZARDOUS TO LIFE AND PROPERTY FROM FIRE AND EXPLOSION; PROVIDING FOR THE AMENDMENT OF THE 1997 UNIFORM FIRE CODE VOLUMES 1 AND 2, WITH CERTAIN DELETIONS, AMENDMENTS, AND/OR ADDITIONS; PROVIDING A PENALTY CLAUSE; A CUMULATIVE CLAUSE; A SEVERABILITY CLAUSE; PROVIDING FOR PUBLICATION; AND PROVIDING AN EFFECTIVE DATE. WHEREAS, the City of Southlake, Texas is a home rule city acting under its charter adopted by the electorate pursuant to Article XI, Section 5 of the Texas Constitution and Chapter 9 of the Local Government Code; and WHEREAS, the City wishes to adopt the 1997 Edition of the Uniform Fire Code to provide for the safety of the citizens of Southlake; and WHEREAS, the Director of Public Safety has recommended certain amendments to the Uniform Fire Code; NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF SOUTHLAKE, TEXAS: Section 1. That Article Ill of Chapter 15 of the Code of Ordinances, City of Southlake, Texas, is hereby amended to read as follows: ARTICLE III. FIRE CODE Sec. 15-126. Adoption of Uniform Fire Code. The City of Southlake hereby adopts the Uniform Fire Code, Volumes 1 and 2, including Appendix Chapters I-C, II-B, II-C, II-E, II-F, II-H, II-J, Ill-A, Ill-C, IV-B,V-A, VI-E, both publislaed by the International Fire Code Institute, and the whole thereof, save and except such portions as are deleted or amended by this ordinance, and the same are hereby adopted and incorporated as fully as if set out at length herein. Page 1 of 20 Sec. 15-127. Amendments. The following sections of the Uniform Fire Code, as adopted in Sec. 15-126, are hereby amended as follows: Section 202-A, the addition of the following definitions: ADDRESSABLE FIRE DETECTION SYSTEM is any system capable of providing identification of each individual alarm initiating device. The identification shall be in plain English and as descriptive as possible to specifically identify the location of the device in alarm. The system shall have alarm verification. ANALOG INTELLIGENT ADDRESSABLE FIRE DETECTION SYSTEM is any system capable of calculating a change in value by directly measurable quantities (voltage, resistance, etc.) at the sensing point. The physical analog may be conducted at the sensing point or at the main control panel. The system shall be capable of compensating for long-term changes in sensor response while maintaining a constant sensitivity. The compensation shall have a preset point at which a detector maintenance signal shall be transmitted to the control panel. The sensor shall remain capable of detectin9 and transmitting an alarm while in the maintenance mode. Section 204-C, page 1-11, the addition of the following definition: CITY shall mean the City of Southlake, Texas. Section 207-F, page 1-14, the addition of the following: FIRE CHIEF shall mean the City of Southlake Chief of Fire Services. FIRE LANE shall mean fire apparatus access road. Section 214-M, page 1-18, the amendment of the definition of "Mechanical Code, "to read as follows: MECHANICAL CODE is the International Mechanical CodeTM as adopted by this jurisdiction. Section 220-,S, page %24, the addition of the following definition: SELF-SERVICE STORAGE FACILITY shall mean real property designed and used for the purpose of renting or leasing individual storage and removing personal property on a self-service basis. Page 2 of 20 Section 90f.4.1, page 1-27, is amended to read as follows: 901.4.1 General. Marking of fire apparatus access roads, addresses and fire protection equipment shall be in accordance with Section 901.4 and Section 902.2.3. Section 902.2. 1, page 'I-27, is amended to read as follows: 902.2.1 Required access. Fire apparatus access roads shall be provided in accordance with Sections 901 and 902.2 for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction when any portion of the facility or any portion of an exterior wall of the first story of the building is located more than 150 feet (45 720 mm) from fire apparatus access as measured by an approved route around the exterior of the building or facility. The path of measurement shall be along a minimum of a 10 foot wide unobstructed pathway around the external walls of the structure. See also Section 902.3 for personnel access to buildings. Fire lane and access easements shall be provided to serve all buildings through parking areas, to service entrances of buildings, loading areas and trash collection areas, and other areas deemed necessary to be available to fire and emergency vehicles. The Fire Chief is authorized to designate additional requirements for fire lanes where reasonably necessary to provide access for fire and rescue vehicles. EXCEPTIONS: When buildings are completely protected with an approved automatic fire sprinkler system, the provisions of Sections 902.2.1 and 902.2.2 may be modified by the chief. When access roads cannot be installed due to location on property, topography, waterways, nonnegotiable grades or other similar conditions, the chief is authorized to required additional fire protection as specified in Section 1001.9. When there are not more than two Group R. Division 3, or Group U Occupancies, the requirements of Sections 902.2.1 and 902.2.2 may be modified by the Fire Chief. More than one fire apparatus road shall be provided when it is determined by the chief that access by a single road might be impaired by vehicle congestion, condition of terrain, climate conditions or other factors that could limit access. For high-piled combustible storage, see Section 8102.6.1. Page 3 of 20 For required access during construction, alteration or demolition of a building, see Section 8704.2. Section 902.2.2. 1, page 1-27 is amended to read as follows: 902.2.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet (7315 mm) and an unobstructed vertical clearance of not less than 14 feet (4267 mm). EXCEPTION: Vertical clearance may be reduced, provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance when approved. Vertical clearances or widths shall be increased when, in the opinion of the chief, vertical clearances or widths are not adequate to provide fire apparatus access. Section 902.2.2.2, page 1-28, is amended to add the following sentences after the first paragraph: 902.2.2.2 Surface. All-weather surface shall be asphalt or concrete. Fire lanes shall be designed to support a minimum 65,000 lb. GVW load. Subgrade shall be prepared to a density of not less than 95% as determined by Standard Proctor. Concrete fire lane shall be minimum five (5) inch thick 3000 psi concrete reinforced with #3 rebar on 18 inch centers. Asphalt fire lane shall be minimum six (6) inches thick. Drive approaches shall be minimum six (6) inches 3000 PSI concrete with #3 rebaron 18 inch centers both ways on chairs. Section 902.2.3, page 1-28, is amended to read as follows: 902.2.3 Marking. Either approved striping or signs shall be provided and maintained for fire apparatus access roads to identify such roads and prohibit the obstruction thereof or both. (4) Striping - Fire apparatus access roads shall be marked by painted lines of red traffic paint six inches in width to show the boundaries of the lane. The words "FIRE LANE NO PARKING" shall appear in four inch white letters with a one inch stroke centered on the red stripe at 25 foot intervals on the red border markings along both sides of the fire lanes. (2) Signs -If signs are used, the signs shall read "FIRE LANE NO PARKING" and shall be 12 inches wide and 18 inches high. Signs shall be painted on a white background with letters and borders in red, using not less than two Page 4 of 20 inch lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet, six inches above finished grade. Signs shall be spaced not more than 50 feet apart. Signs may be installed on permanent buildings or walls or as approved by the Fire Chief. Section 903.4.2, page 1-29 is amended to read as follows: 903.4.2 Required Installations. The location, number and type of fire hydrants connected to a water supply capable of delivering the required fire flow shall be provided on the public street or on the site of the premises, or both, to be protected as required and approved by the Chief. A fire hydrant shall be located within 100 feet of a fire department connection. Maximum spacing of Fire hydrants shall be in accordance with the following distances: Occupancy R-3 and U Occupancies 400 feet All Others 300 feet Unsprinklered Sprinklered 600 feet 600 feet Hydrants shall be provided at all intersecting streets and at intermediate locations between intersections as prescribed above, measured as the hose would be laid. Fire hydrants shall be accessible to the fire department apparatus by roads which meet the requirements of Section 902.2. Section 1003. '1.2, page 1-32, is amended to read as follows: 1003.1.2 Standards. Fire Protection systems shall comply with the appropriate Uniform Building Code Standards and National Fire Protection Association Standards. (See UBC Standard 9-1). EXCEPTIONS: 1. Automatic fire-extinguishing systems not covered by the Building Code shall be approved and installed in accordance with approved standards. 2. Automatic sprinkler systems may be connected to the domestic water-supply main when approved by the building official, provided the domestic water supply is of adequate pressure, capacity and sizing for the combined domestic and sprinkler requirements. In such case, the sprinkler system connection shall be made between the public water main or meter and the building shutoff valve, and there shall not be intervening valves or connections. The fire department connection may be omitted when approved. {balance of Exception #2 to remain unchanged} Page 5 of 20 3. Automatic sprinkler systems in Group R Occupancies four stories or less may be in accordance with the Building Code requirements for residential sprinkler systems. (See U.B.C. Standard 9-3.) 4. Automatic sprinkler systems in One- and Two-Family Dwellings and Manufactured Homes may be in accordance with U.B.C. Standard 9-7. 5. Where sprinklers are installed in electrical rooms, they shall be separated from the building's main sprinkler system by a pre-action valve. This valve shall be connected to fire detection device(s) in the electrical room. Sprinkler piping shall remain dry until the fire detection device activates and opens the pre-action valve. Detection devices shall have a minimum temperature rating of 165 degrees Fahrenheit. Sprinkler head(s) shall be of a type to remain closed until sufficient heat is present to open them. The sprinkler(s) shall have a minimum temperature rating of 212 degrees Fahrenheit. Sprinkler heads in electrical rooms shall be protected with a listed guard over the head. Sprinkler heads may be installed in electrical rooms without the pre-action valve, fire detection device and guard if approved tamper-proof sprinkler heads are installed in place of standard heads. Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every fire protection system shall be designed with a § psi margin of safety. Section 1003.1.3, page %32, is amended to read as follows: 1003.1.3 Modifications. When residential sprinkler systems as set forth in the Building Code (see UBC Standard 9-3) are provided, exceptions to, or reductions in, Building Code requirements based on the installation of an automatic fire-extinguishing system are not allowed. Allowable tradeoffs for, or increases in, Building Code provisions based on the installation of an automatic fire-extinguishing system are not allowed. EXCEPTION: Reductions are allowed for the fo[lowing provisions: Section 708.3.1.1.3 of the Building Code, draft stops in floor-ceiling assemblies. 2. Section 708.3.1.2.1 of the Building Code, draft stops in attics. 3. Section 708.3.1.2.2 of the Building Code, draft stops in attics. Section 1003.2.2, page 1-33, item 5, is amended to read as follows: 1003.2.2 All occupancies except Group U occupancies. Except for Group U Occupancies, an automatic sprinkler system shall be installed: Page 6 of 20 In every stow or basement of all buildings when the floor area exceeds 1,500 square feet (139.4 m2) and there is not provided at least 20 square feet (1.86 m2) of opening entirely above the adjoining ground level in each 50 lineal feet (15 240 mm) or fraction thereof of exterior wall in the stow or basement on at least one side of the building. Openings shall have a minimum dimension of not less than 30 inches (762 mm). Such openings shall be accessible to the fire depar[ment from the exterior and shall not be obstructed in a manner that firefighting or rescue cannot be accomplished from the exterior. When openings in a story are provided on only one side and the opposite wall of such story is more than 75 feet (22 860 mm) from such openings, the story shall be provided with an approved automatic sprinkler system, or opening as specified above shall be provided on at least two sides of an exterior wall of the stow. If any portion of a basement is located more than 75 feet (22 860 mm) from openings required in Section 1003.2.2, the basement shall be provided with an approved automatic sprinkler system. At the top of rubbish and linen chutes and in their terminal rooms. Chutes extending through three or more floors shall have additional sprinkler heads installed within such chutes at alternate floors. Sprinkler heads shall be accessible for servicing. In rooms where nitrate film is stored or handled. See also Article 33. in protected combustible fiber storage vaults as defined in Article 2. See also Article 28. Throughout all buildings with a floor level, other than a penthouse in compliance with Section 1511 of the Building Code, that is located 35 feet (10688 mm) or more above the lowest level of fire department vehicle access. EXCEPTION: Open parking structures. In any building used for high-piled combustible storage with a clear height exceeding 15', see Section 8101. In all new and existing spray booths and spraying rooms. EXCEPTION: A spray booth existing as of the effective date of this ordinance shall have 12 months from the effective date to comply with the requirements of this section. Throughout any building over 6,000 square feet. For the purpose of this subsection, area separation walls shall not be considered as forming separate buildings. Calculation of square footage shall based upon the following: Page 7 of 20 a. For dwellings, only the conditioned living space, as defined by the Uniform Building Code, shall be considered. For other buildings, the total floor area, as defined by the Uniform Building Code, shall be considered. EXCEPTIONS: 1. Any dwelling for which a building permit application has been submitted as of the effective date of this ordinance is not required to add sprinklers. Such dwellings may be expanded or remodeled without meeting the requirements of this section. Any dwelling for which a building permit application is submitted after the effective date of this ordinance and which is enlarged, so long as the increase in square footage of conditioned living space does not exceed 20 percent of the size of the existing dwelling. Section 1003.2.6.4 is added to read as follows: 1003.2.6.4 Group H, Division 5 Occupancies. Aircraft hangars shall be classified by Group and Type* and shall be provided with a fire extinguishing system as specified by UBC Standard 9-4. (*Note: Any classification of construction type under UBC Standard 9-4 shall be for use with that standard only and shall have no bearing on the construction type used in conjunction with any other provision of this code.) Section 1003.2.9, page 1-34, is amended to read as follows: 1003.2.9 Group R, Division 1 Occupancies. An automatic sprinkler system shall be installed throughout every apartment house two or more stories in height or containing three or more dwelling units, every congregate residence two or more stories in height or having an occupant load of more than 10, and every hotel two or more stories in height or containing 20 or more guest rooms. Residential or quick-response standard sprinklers shall be used in the dwelling units and guest room portions of the building. Section 1003.2.10, page 1-34, is added to read as follows: 1003.2.10 Self-service storage facilities. An automatic sprinkler system shall be installed throughout all self-service storage facilities. EXCEPTION: One-story self-service storage facilities, that have no interior corridors, and have a one-hour fire-rated occupancy separation wall installed Page 8 of 20 between every storage compartment. Section 1003.2.11, page 1-34, is added to read as foflows: 1003.2.11 Group S, Division 5 Occupancies. Aircraft hangers shall be classified by Group and Type*, and shall be provided with a fire-extinguishing system as specified by UBC Standard 9-4. *Note: Any classification of construction type under UBC Standard 9-4 shaft be for use with that standard only and shall have no bearing on the construction type used in conjunction with any other provision of this code. Section 1003.4, page 1-34, the amendment of subparagraph 4.4 as foflows: 1003.4.1 Permissible Sprinkler Omissions 4.4 Other approved fire-protection equipment is installed in such areas. Section 1004.3, page 1-35, the third paragraph is amended to read as follows: 1004.3 Location of Class I Standpipe Hose Connections. There shall be a two-way outlet above the roof line on every standpipe when the roof hasa slope of less than 4 units vertical in 12 units horizontal (33.3% slope). EXCEPTION: Where the stairway extends to the roof, the two-way outlet may be located at the topmost floor landing. Section 1004.3, page 1-35, is amended to add a new paragraph to read as foflows: 1004.3 Standpipe Requirements. Ail class I standpipes shall be: 1. Water filled at all times, or 2. Supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/iow alarm. Section 1007.2.4. l, page 1-36, is amended to read as follows: 1007.2.4 Group E Occupancies. 1007.2.4.1 General. Group E Occupancies shall be provided with fire alarm systems Page 9 of 20 in accordance with Section 1007.2.4. Group E Occupancies shall be provided with an approved manual fire alarm system. In Division 3 occupancies, system smoke detectors shall be installed in all rooms used by children .... (balance to remain unchanged} Section 1007.2.12.2.1, page 1-38, is amended to read as follows: 1007.2.12.2.1 General. Occupancies having floors used for human occupancy located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and a communication system in accordance with Section 1007.2.12.2. EXCEPTION: Open parking garages which comply Section 311.9 of the Building Code. Section 1007.2.12.2.3, page 1-38, adds a fourth paragraph to read as follows: 1007.2.12.2.3 Emergency voice alarm-signaling system. Actuation of any automatic or manual device shall initiate an alarm signal on the alarming floor, the floor above, and the floor below and identify on an annunciator the zone or address from which the alarm signal originated. Section 1007.2. 12.2.4, page 1-38, is amended to read as follows: 1007.2.12.2.4 Fire department communication system. A two-way, approved fire department communication system shall be provided for fire department use. It shall operate between the central control station and elevators, elevator lobbies, emergency standby power rooms, fire pump room and inside stairways at each floor level. Section 1007.2.12.6, page 1-38, is amended to read as follows: 1007.2.12.6 Corridors in office uses. When required by the Building Code for corridors in lieu of one-hour corridor construction, smoke detectors shall be installed within office corridors in accordance with their listing. The actuation of any detector shall activate alarms audible in all areas served by the corridor. (See UBC Section 1004.3.4.3, Exceptions 4 and 6.) Section 1007.3.1, page 1-39, add a second paragraph and exception to read as follows: Page 10 of 20 1007.3.1 Design Standards All alarm systems, new or replacement, serving 50 or more alarm actuating devices shall be addressable fire detection systems. Alarm systems serving more than 75 smoke detectors or more than 200 total alarm activating devices shall be analog intelligent addressable fire detection systems. EXCEPTION: Systems existing on the effective date of this ordinance need not comply unless the total system remodel or expansion initiated after the effective date of the ordinance, exceeds 30% of the square footage of the building. When the cumulative square footage of a building remodeling or expansion exceeds 50% of the size of the existing building, the building must comply within 18 months of permit application. Section 1007.3.3.1, page 1-39, adds an item no. 3 to read as follows: 1007.3.3 Manual Fire Alarm Boxes. 3. Manual alarm actuating devices shall be an approved double action type. Section 1007.3.3.8, page 1-39, is added to read as follows: 1007.3.3.8 Wiring. All fire alarm systems shall be installed in such a manner that the failure of any single alarm-actuating or alarm-indicating device will not interfere with the normal operation of any other such devices. All systems shall be Class "A" wired with a minimum of six feet separation between supply and return loops. Initiating Device Circuits (IDC): Class "A", Style E - Signaling Line Circuits (SLC): Class "A", Style 6 - Notification Appliance Circuits (NAC): Class "B", Style X. Section ?007.3.3.9, page 1-39. is added to read as follows: 1007.3.3.9 Flow detectors and electronic monitoring. Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 15 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a trouble signal atthe central control station upon tampering. The fire-pump system shall also be supervised for "power available", "phase reversal" and "pump running" conditions by trouble signal on distinct circuits. Table 1004-A, page 1-40 is amended to be as follows: Pagellof20 Table 1004-A. -Standpipe Required Systems OCCUPANCY NON- BUILDING~ SPRINKLERED 2B3UILDINGS SPRINKLERED . x304.8 for mm Standpipe Hose Standpipe Hose x 0.0929 for m2 Class Requirement Class Requirement 5 Groups I; H; B; S; II Yes I No M; F, Division I Occupancies less than 4 stories in height but greater than 20,000 square feet per floor6 Section 1'102.3.1, page 1-41, is amended to read as foflows: 1102.3.1 General. Open burning shall be conducted in trenches with approved equipment and in accordance with Section 1102.3 and Ordinance No. 545. Open burning shall also be conducted as required by other governmental agencies regulating emissions. EXCEPTION: Recreational fires shall comply with Section 1102.4 and Ordinance No. 545. Approved bonfires shall not be required to be trench burned. Section 1102.6, page %42, is added to read as follows: 1102.6 Grills or Hibachis at R-1 Occupancies. All fixed or podable grills or hibachis at Group R, Division 1 occupancies shall, when in use, be a minimum of ten (10)feet from any structure and not on or under any portion of the structure. Section 4502.8.1, page %91, is amended to read as follows: 4502.8.1 General. New and existing spray booths and spraying rooms shall be protected by approved automatic fire-extinguishing systems. Such systems shall be extended to protect exhaust plenums, exhaust ducts and both sides of dry filters when such filters are used. For installation of automatic sprinklers in ducts, see the Mechanical Code. Section 5204.5.2, page 1-726, is amended to add a new paragraph to read as follows: 5204.5.2 Maximum Capacity Within Established Limits. For land located within the following zoning districts, the aggregate capacity of any one installation of CNG shall not exceed 183,000 cubic feet. (5 181 974 L): all residential Page12of20 districts, including "SF-1A. SF-1B, SF-30, SF-20A, and SF-20B, Single Family Residential Districts;" "RE, Single Family Residential Estate District;" "AG," Agricultural District; "MF-1, Two Family Residential District;" "MF-2, Multiple Family Residential District;" and "MH, Manufactured Housing District;" certain office and commercial districts, including "HC, Hotel District;" "O-1 and 0-2, Office Districts;" "C-1, Neighborhood Commercial District;" "C-2, Local Retail Commercial District;" "C-3, General Commercial District;" "C-4, Arterial Mall District;" "B-2, Commercial Manufacturing District;" and any "PUD, Planned Unit Development District," "S-P-l, Detailed Site Plan District," and "S-P-2, Generalized Site Plan District" which includes any use permitted in the above-referenced districts. This requirement is for the protection of heavily regulated or congested commercial areas, This limit does not apply in "B-l, Business Service Park District;" "1-1, Light Industrial District;" '%2, Heavy Industrial District;" and "CS, Community Service District or any S-P-1 Detailed Site Plan District," S-P-2 Generalized Site Plan District which includes one of the foregoing uses. Section 7701.7.2, page 1-150, is amended to read as foflows: Section 7701.7.2, Limitations. Storage of explosive materials is prohibited unless approved by the Fire Chief. Section 7801.3.1.1, page 1-159, is amended to read as fellows: 7801.3.1.1 Manufacturing. The manufacturing of fireworks is prohibited. Section 7802.3, page 1-159, is amended to read as follows; 7802.3 Prohibition. The storage, use and handling of fireworks are prohibited unless approved by the Fire Chief. EXCEPTION: The use of fireworks for display is allowed as set forth in Section 7802.4. Section 7902.2.2, page 1-172, is amended to add a new paragraph to read as follows: 7902.2.2.1 Locations where above ground tanks are prohibited. Storage of Class I and Crass II liquids in above-ground tanks outside of buildings is prohibited in land located in the following zoning districts: all residential districts, including "SF-1A, SF-1B, SF-30, SF-20A, and SF-20B, Single Family Residential Districts;" "RE, Single Family Residential Estate District;" "AG," Agricultural District; "MF-1, Two Family Residential District;" "MF-2, Multiple Family Residential District;" and "MH, Manufactured Housing District;" "HC, Hotel District; ....O-1 and 0-2, Office Districts; .... C-1, Neighborhood Page13of20 Commercial District;" "C-2, Local Retail Commercial District;" "C-3, General Commercial District;" "C-4, Arterial Mall District; .... B-2, Commercial Manufacturing District;" and any "PUD, Planned Unit Development District," "S-P-l, Detailed Site Plan District," and "S-P-2, Generalized Site Plan District" which includes any use permitted in the above-referenced districts. Such storage is permitted in land located in the following zoning districts: "B-l, Business Service Park District;" "1-1, Light Industrial District;" "1-2, Heavy Industrial District;" and "CS, Community Service District or in S-P-1 or S-P-2 Districts with the approval of the Fire Chief." Section 7902.6.11, page 1-180, is amended to read as follows: 7902.6.11 Secondary Containment: An approved method of secondary containment shall be provided for underground tank systems, including tanks, piping and related components. See Appendix II-G. Section 7902.6.12.1, page 1-180, is added to read as follows: 7902.6.12.1 Dry sumps. Approved sampling tubes cfa minimum six inches in diameter shall be installed in the backfill material of each underground flammable or combustible liquid storage tank. The tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling sump at the corners of the excavation with a minimum of four sumps. Sampling tubes shall be placed in the product line excavation within 10 feet of the tank excavation and one every 50 feet routed along product lines towards the dispensers. A minimum of two sampling tubes are required. Section 7904.2.5.4.2, page 1-192, is amended to add a new paragraph to read as follows: 7904.2.5.4.2 Locations where above ground tanks are prohibited. The storage of Class I and II liquids in above ground tanks is prohibited on land located in the following zoning districts: all residential districts, including "S F-1 A, SF-1 B, SF-30, SF-20A, and SF-20B, Single Family Residential Districts;" "RE, Single Family Residential Estate District;" "AG," Agricultural District; "MF~I, Two Family Residential District;" "MF-2, Multiple Family Residential District;" and "MH, Manufactured Housing District;" "HC, Hotel District;" "O-1 and 0-2, Office Districts;" "C-1, Neighborhood Commercial District;" "C-2, Local Retail Commercial District;" "C-3, General Commercial District;" "C-4, Arterial Mall District; .... B-2, Commercial Manufacturing District;" and any "PUD, Planned Unit Development District," "S-P-l, Detailed Site Plan District," and "S-P-2, Generalized Site Plan District" which includes any use permitted in any of the above-referenced districts Page 14 of 20 Such storage is permitted on land zoned within the following zoning districts: "B-l, Business Service Park District;" "1-1, Light Industrial District;" "1-2, Heavy Industrial District;" and "CS, Community Service District," or on land zoned for certain S-1-1 or S-P-2 Districts with the approval of the Fire Chief. Section 7904.5.1.2, page 'I-197, a second paragraph is added to read as follows: 7904.5.1.2. Fire Protection. An approved deluge water foam extinguishing system shall be installed and maintained on all loading facilities and on all unloading facilities. Section 800'1. '1.1, page 1-201, is amended to the second paragraph, to read as follows: 8001.1.1 General. The storage of hazardous materials and maximum quantity on-site is prohibited on land located in the following zoning districts: Property located within all residential districts, including "SF-1A, SF-1 B, SF-30, SF-20A, and SF-20B, Single Family Residential Districts;" "RE, Single Family Residential Estate District;" "AG," Agricultural District; "MF-1, Two Family Residential District;" "MF-2, Multiple Family Residential District;" and "MH, Manufactured Housing District;" certain office and commercial districts, including "HC, Hotel District;" "O-1 and 0-2, Office Districts;" "C-1, Neighborhood Commercial District; "C-4, Arterial Mall District;" and any "PUD, Planned Unit Development District," "S-P-l, Detailed Site Plan District," and "S-P-2, Generalized Site Plan District" which includes any use permitted of the above-referenced districts. Such storage is permitted on land located within the following zoning districts: "C-2, Local Retail Commercial District;" "C-3, General Commercial District; .... B-l, Business Service Park District; .... B-2, Commercial Manufacturing District;" "1-1, Light Industrial District;" "1-2, Heavy Industrial District;" and "CS, Community Service District," or on land zoned for certain S-P-1 or S-P-2 Districts with the approval of the Fire Chief. Section 8'101.1, page 1-231, is amended to add a third paragraph to read as follows: 8101.1 Scope. Any building exceeding 6,000 square feet that has a clear height in excess of 15 feet, making it possible to be used for storage in excess of 12 feet, shall be considered to be high-piled storage and shall comply with the provisions of this section. When a specific product cannot be identified, a fire protection system shall be installed as for Class IV commodities. Section 8'102.8, page 1-235, is amended to read as follows: 8102.8.1 General. When curtain boards are required by Table 81-A, curtain boards Page15of20 shall be provided in accordance with Section 8102.8. Aisc see Footnote 2, Table 81-B. EXCEPTION: Fully sprinklered Group S occupancies, storing Class I-IV commodities, provided that a curtain board is installed between different system designs. Section 8203.2.1.9, page 1-239, is added to read as foflows: 8203.2.1.9 Jewelry Repair, Dental Labs and Similar Occupancies. Where natural gas service is not available, portable LP-Gas containers are allowed to be used to supply approved torch assemblies or similar appliances. Each container shall not exceed 20-pound (9.0 kg) water capacity. Aggregate capacity shall not exceed 60-pound (27.2 kg) water capacity. Each device shall be separated from other containers by a distance of not less than 20 feet. Section 8203.2.1.10, page 1-239, is added to read as foflows: 8203.2.1.10 Portable Gas Grills. LP-Gas containers are allowed to be used to supply portable gas grills at residential occupancies. Each container shall not exceed 20-pound (9.0 kg) water capacity. Aggregate capacity shall not exceed 40-pound (18 kg) water capacity. Section 8203.4, page 1-239, is added to read as follows: 8203.4 Spas and Pool Heaters. Where natural gas service is not available, LP-Gas containers are allowed to be used to supply spa and pool heaters. One such container not exceeding 250-gallon water capacity is allowed. See Table 8204-A for location of containers. Section 8204.2, page 1-239, exception added as foflows: 8204.2 Maximum Capacity. The aggregate capacity of any one installation of LP Gas shall not exceed a 2,000 gallon (7571 L) water capacity on land located within the following zoning districts: certain office and commercial districts, including "HC, Hotel District; .... O-1 and 0-2, Office Districts;" "C-1, Neighborhood Commercial District;" "C-2, Local Retail Commercial District;" "C-3, General Commercial District;" "C-4, Arterial Mall District; .... B-2, Commercial Manufacturing District;" and any "PUD, Planned Unit Development District," "S-P-l, Detailed Site Plan District," and "S-P-2, Generalized Site Plan District" which includes, any use permitted in any of the above-referenced districts. Except as noted in the following exception, LP gas shall not be stored on land located in all residential districts, including "SF-1A, SF-1B, SF-30, SF-20A, and SF-20B, Single Family Residential Page 16 of 20 Districts;" "RE, Single Family Residential Estate District;" "AG," Agricultural District; "MF-1, Two Family Residential District;" "MF-2, Multiple Family Residential District;" and "MH, Manufactured Housing District;" A single installation of LP gas may exceed 2,000 gallon (7571L) water capacity on the land located in the following zoning districts: Permitted in "B-l, Business Service Park District;" "1-1, Light Industrial District;" "1-2, Heavy Industrial District;" and "CS, Community Service District." EXCEPTION: Except as permitted in sections 8203.2.1.10 and 8203.4, LP-Gas containers are not allowed on land zoned for residential uses. Section 15-127. Adoption of appendices. The following appendices are adopted: Appendix I-C - STAIRWAY IDENTIFICATION Appendix II-B - PROTECTION OF FLAMMABLE AND COMBUSTIBLE LIQUID TANKS IN LOCATIONS SUBJECT TO FLOODING Appendix II-C-MARINAS Appendix II-E - HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOUS MATERIALS INVENTORY STATEMENTS Appendix II-F - PROTECTED ABOVEGROUND TANKS FOR MOTOR VEHICLE FUEL-DiSPENSING STATIONS OUTSIDE BUILDINGS Appendix II-H - SITE ASSESSMENTS FOR DETERMINING POTENTIAL FIRE AND EXPLOSION RISKS FROM UNDERGROUND FLAMMABLE OR COMBUSTIBLE LIQUID TANK LEAKS Appendix II-J - STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS IN TANKS LOCATED WITHIN BELOW-GRADE VAULTS Appendix Ill-A-FIRE-FLOW REQUIREMENTS FOR BUILDINGS Appendix III-C - INSPECTION, TESTING AND MAINTENANCE OF WATER-BASED FIRE-PROTECTION SYSTEMS Appendix IV-B - CHRISTMAS TREES with the following amendments: The amendment of Section One to read as follows: Page 17 of 20 Section 1 - SCOPE The use of natural or resin-bearing cut trees in all occupancies shall be in accordance with Appendix IV-B. EXCEPTION: Group R, Division 3 Occupancies and within individual dwelling units of Group R, Division 1 Occupancies. The deletion of Sections Two and Four. Appendix V-A - NATIONALLY RECOGNIZED STANDARDS OF GOOD PRACTICE AppendixVI-E-REFERENCETABLESFROMTHEUNIFORM BUILDINGCODE,withthe following amendments: The amendment of Table 5A, with the addition of footnote No. 8, to read as follows: Table 5A EXTERIOR WALL AND OPENING PROTECTION BASED ON LOCATION ON PROPERTY FOR ALI CONSTRUCTION TYPES When the exterior wall cfa non-high-rise building is more than 20 feet from the property line, the fire-resistive requirements for exterior bearing and exterior nonbearing walls may be reduced by one-hour when the building is provided with an approved automatic sprinkler system throughout as specified in Chapter 9. However, a wall that is required to be one-hour may not be reduced except as allowed under Section 508. Table 6-A, with the addition cfa footnote no 4 in building element No. 8, to read as follows: Table 6A TYPES OF CONSTRUCTION-FIRE RESISTIVE REQUIREMENTS. 8. ROOFS AND ROOF CEILINGS. The fire-resistive requirements for roofs of non-high-rise buildings may be reduced by one-hour when the building is provided with an approved automatic sprinkler system throughout as specified in Chapter 9. Table 8-B, page 1-346, change the rating for "Other Exit ways" for Group R, Division 1 Occupancies to Class "1". Table 8-B, page 1-346, footnote No. 2 is amended to read as follows: Page 18 of 20 Table 8-B Maximum Flame Spreadclass. 2 Finish classification is not applicable to interior walls and ceilings of exterior exit balconies except as required in Section 310.13 of the Building Code for Group R, Division 1 Occupancies. Uniform Fire Code Standard 80-3, a new paragraph is added to read as follows: Section 3-1.6 Limitations. Storage of flammable cryogens in stationary containers is prohibited upon land located in the following zoning districts, all residential districts, including "SF-1A, SF-1B, SF-30, SF-20A, and SF-20B, Single Family Residential Districts;" "RE, Single Family Residential Estate District;" "AG," Agricultural District; "MF-1, Two Family Residential District; .... MF-2, Multiple Family Residential District;" and "MH, Manufactured Housing District;" certain office and commercial districts, including "HC, Hotel District;" "O-1 and O-2, Office Districts;" "C-1, Neighborhood Commercial District;" "C-2, Local Retail Commercial District;" "C-3, General Commercial District;" "C-4, Arterial Mall District;" "B-2, Commercial Manufacturing District;" "CS, Community Service District;" and any "PUD, Planned Unit Development District," "S-P-l, Detailed Site Plan District," and "S-P-2, Generalized Site Plan District" which includes any use permitted in any of the above-referenced districts. Such storage is permitted in land located in the following zoning districts:"B-1, Business Service Park District;" '%1, Light Industrial District;" "1-2, Heavy Industrial District." or S-P-1 or S-P-2 Districts with the approval of the Fire Chief. Section 2. Penalty. Any person, firm, or corporation who violates, disobeys, omits, neglects or refuses to comply with or who resists the enforcement of any of the provisions of this ordinance shall be fined not more than Two Thousand Dollars ($2,000.00) for each offense. Each day that a violation is permitted to exist shall constitute a separate offense. Section 3. Cumulative Clause. This ordinance shall be cumulative of all provisions of ordinances of the City of Southlake, Texas, except where provisions of this ordinance are in direct conflict with the provisions of another ordinance, in which event the conflicting provisions of the other ordinance are hereby repealed. Section 4. Severability Clause. It is hereby declared to be the intention of the City Council that the phrases, clauses, sentences, paragraphs, and sections are severable, and if any phrase, clause, sentence, paragraph, or section of this ordinance shall be declared unconstitutional by the valid judgement or Page19of20 decree of any court of competent jurisdiction, such unconstitutionality shall not affect any of the remaining phrases, clauses, sentences, paragraphs, and sections of this ordinance, since they would have been enacted by the City Council without the incorporation in this ordinance of the unconstitutional phrase, clause, sentence, paragraph, or section. Section 5. Publication. The city secretary is directed to publish the preamble and penalty clause of this ordinance at least one time within 10 days after its final passage, in the official newspaper of the city in accordance with Section 3.13(b) of the Southlake Home Rule Charter. Section 6. APPROVED Effective Date. This ordinance shall be in full force and effect from and after its passage and publication as required by law, and it is so ordained. ON FIRST READING THms Ir-/ DAY OF (¢:~ , 200~ __ DAY or / M,~Y~R </Z>fZ,'/,,t CITY SECRETARY ~. % .e e APPROVED AS TO FORM AND LEGALIT'~':'"""" CITY ATTORNEY ,,4 ,2001. Page 20 of 20 INVOICE Star-Telegram Customer ID: CIT57 400 W.7th Street Invoice Number: 185553151 FORT WORTH,TX 76102 Invoice Date: 1/5/01 (817)390-7761 Federal Tax ID 22-3148254 Terms: Net due in 21 days Due Date: 1/31/01 Bill To: PO Number: CITY OF SOUTHLAKE Order Number: 18555315 667 N CARROLL AVE SOUTHLAKE, TX 76092-6412 Sales Rep: 073 Description: CITY OF SOUTHLA Publication Date: 1/5/01 CITY OF SOUTH- LAKE, TEXAS ArAliagit An* ORDINANCENO. 762 AN ORDINANCE OF CITY OF SOUTHLA E, TEx- ORDIN I358 1 82 82 LINE $6.09 $499.56 AS, AMENDING -THF CODE OF ORDINAN - C TYCES OF OF THE SOU ($433.14) Sales Dis LAKE, TEXAS B THY ADOPTING THE 1997 EDITION OF THE UNIFORM FIRE CODE VOLUMES 1 AND 2; REPEALING ORDINANCE NUM- Net Amount: $66.42 BER 572, REPEAL- ING ALL ORDINANC- ES IN CONFLICT HEREWITH; PRE- SCRIBING REGULA- TIONS GOVERNING CONDITIONS HAZ- ARDOUS TO LIFE AND PROPERTY FROM FIRE AND- EXPLOSION; PRO- VIDING FOR TIM- AMENDMENT OF THE 1997 UNIFORM FIRE CODE VOL UMES 1 AND 2 WITH CERTAIN DELE- TIONS, AMEND- MENTS, AND/OR ADDITIONS; PRO- VIDING A PENALTY CLAUSE; A CUMU- .t LATIVE CLAUSE; A S E V E R A B I L I T Y CLAUSE; PROVID- ING FOR PUBLICA- N ST TIOVID INGNANN D OE EFFECT Coun1 DATE. Section 2 . Penalty Any person, firm Of corporation who vbu Be fort bates,disobeys,omits, or said County and State,this day personally appeared Shalini Doss, Bid and Legal Coordinator, for the Star- Tele refuses comply with or who egram, Inc.atFort Worth,neglects or reIusa to I County,Texas; who, in Tarrant and after being duly sworn, did depose and say that the attach resists the enforce- it waspublished in the above named paper on the listed dates: moot of any f of the p p provisions of this o �/ dinance shall be fined not more than T wu Signed (j/2.4_J Thousand Dollars ($2,000.00) Tor earth SUBSI avttsafat 'roaion iperntted EFORE ME,THIS Monday, )anu ry 8 2001. to exist shall constitute a separate offense. / PASSED AN A F' PROVEED BY THE Notary Publ.c .(J CITY COUNCIL OF THE CITY OF SOUTHLAKE, TEX- AS,ON THIS THE 2nd DAY OF JANUARY, 2001 MAYOR ' CHRISTY L. HOLLAND RICK STACY LAO" Thank ALEGRANDANDRA Ly ent '` MY COMMISSION EXPIRES CITY,._. APPROVEDSECRETARY TO - -" � ,,,!ll���.,,, __ 1U1. 33;�5904— FORM: E. ALLEN TAYLOR J R., CITY ATTORNEY Remit To: Star-Telegram Customer ID: CIT57 P.O. Box 901051 Customer Name: CITY OF SOUTHLAKE FORT WORTH, TX 76101-2051 Invoice Number: 185553151 Invoice Amount: $66.42 PO Number: Amount Enclosed: $ INVOICE Star-Telegram Customer ID: CIT57 400 W.7th Street Invoice Number: 181721941 FORT WORTH,TX 76102 Invoice Date: 10/20/00 (817)390-7761 Federal Tax ID 22-3148254 Terms: Net due in 21 days Due Date: 10/31/00 Bill To: PO Number: CITY OF SOUTHLAKE 667 N CARROLL AVE Order Number: 18172194 SOUTHLAKE, TX 76092-6412 Sales Rep: 073 Description: CITY OF SOUTHLA Publication Date: 10/20/00 y`aaE a t I t ¢ tlg au R• � ....--. Ask„ L„€Y'. x,.:rc'Sm'f',..a:E....,.,b CITY OF SOUTH CITY OF SOUTHLAKErs 's'tI358 1 66 66 LINE $5.79 $382.14 NOTICE is hereby given to all interested persons that the City Council of the City of Southlake, Texas, will Sales Discount be holding a public hearing ($328.68) during the regular city council meeting to be held on November 7, 2000, at 7:00 m. The meeting will be held in the City Council Chambers of City Hall, 667 North Carroll Avenue, Southlake, Texas. Purpose Net Amount: $53.46 of the hearing of will be held regarding the follow- ing ORDINANCE NO. 762 AN ORDINANCE OF THE CITY OF SOUTHLAKE, TEX- AS, AMENDING THE CODE OF ORDINANCES OF THE TEX- AS OUTH ITY BY OFSADOPTING THE 1997 EDITION OF THE UNI- FORM FIRE CODE VOL- UMES 1 AND 2; REPEAL- ING ORDINANCE NUMBER 572; REPEALING ALL ORDI- NANCES IN CONFLICT HEREWITH- PRESCRIBING REGULATIONS GOVERNING CONDITIONS HAZARDOUS TO LIFE AND PROPERTY FROM FIRE AND EXPLO- SION; PROVIDING FOR THE AMENDMENT OF THE 1997 UNIFORM FIRE CODE VOLUMES 1 AND 2 WITH THE STATE OF CERTAIN DE LEY County of Tarran ADDIT ONS;T PROVID NDGIO/NS OA PENALTY CLAUSE; A CU- MULATIVE CLAUSE- A SEV- Before me,a Not VOANGI FORCPU BLECATIOi R •ounty and State,this day personally appearci TAMMIE BRYANT, Bid and Legal Coordinator, for the Star- Telegram, publish AND DATE.D PRROIDING AN EFFEC- nc.at Fort Worth, in Tarrant County,Texas;and who,after being duly sworn,did depose and say that the attached clipping section 2. Penalty. Any iblished in the above named pa'. - he listed dates: person, firm, or corpora- tion who violates, dis- obeys, omits, neglects or � �' `� refuses to comply with or — who resists the enforce- ment of any of the provi- SUBSCRIBED Al` lions of this ordinance 1E,THIS Monday,Oct 3,2000. shall be fined not more than Two Thousand Dollars ($2,000.00) for each of- fense. Each day that a vio- Notary Public lation is permitted to exist shall constitute a separate offense. Sandra L. LeGrand City Secretary - City of Southlake Tews _ CHRISTY L.HOLLAND f• MMY COMMISSION EXPIRES Thank You For Your Payment � 1 „rItY, JULY 31,2004 Remit To: Star-Telegram Customer ID: CIT57 P.O. Box 901051 Customer Name: CITY OF SOUTHLAKE FORT WORTH, TX 76101-2051 Invoice Number: 181721941 Invoice Amount: $53.46 PO Number: Amount Enclosed: $�..�..�,,,�,���_.���,.,���...._.......�....._�