Loading...
0870 International Fire Code O"INANCE NO. 870 OFFICIAL RECORD' AN ORDINANCE OF THE CITY OF SOUTHLAKE, TEXAS, AMENDING CHAPTER 15, ARTICLE III, "FIRE CODE" OF THE CODE OF ORDINANCES OF THE CITY OF SOUTHLAKE, TEXAS BY ADOPTING THE 2003 EDITION OF THE INTERNATIONAL FIRE CODE; REPEALING ORDINANCE NUMBER 817 AND REPEALING ALL ORDINANCES IN CONFLICT HEREWITH; PRESCRIBING REGULATIONS GOVERNING CONDITIONS HAZARDOUS TO LIFE AND PROPERTY FROM FIRE AND EXPLOSION; PROVIDING FOR THE ADOPTION OF LOCAL AMENDMENTS THERETO; PROVIDING A PENALTY CLAUSE; PROVIDING A CUMULATIVE CLAUSE; PROVIDING A SEVERABILITY CLAUSE; PROVIDING A SAVINGS CLAUSE; PROVIDING FOR PUBLICATION; AND PROVIDING AN EFFECTIVE DATE. WHEREAS, the City of Southlake, Texas is a home rule city acting under its charter adopted by the electorate pursuant to Article XI, Section 5 of the Texas Constitution and Chapter 9 of the Local Government Code; and WHEREAS, the City wishes to adopt the 2003 Edition of the International Fire Code to provide for the safety of the citizens of Southlake; and WHEREAS, the Director of Public Safety has recommended certain amendments to the International Fire Code, and NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF SOUTHLAKE, TEXAS: Section 1. That Article III of Chapter 15 of the Code of Ordinances, City of Southlake, Texas, is hereby amended to read as follows: "ARTICLE III. FIRE CODE Sec. 15-126. Adoption of 2003 Edition of the International Fire Code, The City of Southlake hereby adopts the 2003 Edition of the International Fire Code, including Appendix Chapters A, B, C, D, E, F and G, published by the International Code Council, Inc, save and except such portions as are deleted or amended by this ordinance, and the same are hereby adopted and incorporated as fully as if set out at length herein. Sec. 15-127. Amendments. The following sections of the 2003 Edition of the International Fire Code as adopted in Sec. 15-126, are hereby amended as follows: Inserted text is underlined, 4ek4ea *°°t ^°a ~ Section 101.1; Change to read as follows: 101.1 Title. These regulations shall be known as the Fire Code of the City of Southlake, Texas hereinafter referred to as "this code." Section 102.4; Change to read as follows: 102.4 Application of other codes. The design and construction of new structures shall comply with this code and other codes as applicable and any alterations additions changes in use or changes in structures required by this code which are within the scope of this and other codes shall be made in accordance therewith. Section 102.6; Change to read as follows: Section 102.6 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 and such codes, when specifically adopted, and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between the provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. Section 103.1, 103.2 and 103.3 Change to read as follows: Section 103.1-General. The Fire Code shall be enforced by the Division of Fire Prevention. The Division of Fire Prevention is hereby established as a division of the Department of Public Safety of the City of Southlake and shall be operated under the supervision of the Chief of the Fire Department. Section 103.2 Appointment. The Code Official in charge of the Division of Fire Prevention shall be appointed by the Director of Public Safety on the basis of proper qualification as required by the City of Southlake. Section 103.3 Deputies. In accordance with the prescribed procedures of this jurisdiction and the concurrence of the Fire Chief, the code official shall have the authority to appoint a deputy code official, other related technical officers, inspectors and other employees. Section 105.6 Change as follows: Section 105.6.0 Required operational permits. The code official is authorized to issue operational permits for the operations set forth in Sections 105.6.1 through 105.6.34 Sections 105.6.1 through 105.6.47 is hereby rescinded and Sections 105.6.1 through 105.6.34 is adopted as follows: Section 105.6.1 Underground Storage Tanks (UST) Section 105.6.2 Aboveground Storage Tanks (AGST) Section 105.6.3 UST and AGST removal or Temporary out of service Section 105.6.4 Changing UST contents Section 105.6.5 Trench Burning - Clearing Land/Rubbish Section 105.6.6 Fireworks Display Section 105.6.7 Dry Cleaning Operations, non-flammable liquids Section 105.6.8 Dry Cleaning Operations, flammable/combustible liquids Section 105.6.9 Explosives or Blasting Agents, use of Section 105.6.10 Hazardous Materials (Storage, dispense, use of) Section 105.6.11 Highly Toxic Pesticides (storage, use of) Section 105.6.12 High-Piled Combustible Storage Section 105.6.13 Tire Storage Section 105.6.14 LPG, 25-119 WGC Section 105.6.15 LPG, 120 - 1,999 WGC Section 105.6.16 LPG, 2,000 < WGC Section 105.6.17 LPG fueled vehicles/equipment in assemblies Section 105.6.18 Spraying and Dipping Operations Section 105.6.19 Battery Systems Section 105.6.20 Private Agency License Inspection/Certification Section 105.6.21 Asbestos Removal Section 105.6.22 Malls, covered Section 105.6.23 Motor Vehicle Fuel Dispensing Stations Section 105.6.24 Pyrotechnic material Section 105.6.25 Cut Tree in Public Building Section 105.6.26 Controlled Access Gates Section 105.6.27 Circus, Carnivals, Fairs Section 105.6.28 Pipeline Operations Maintenance or Excavation Section 105.6.29 Candles- Open Flame, Use in Assembly Areas Section 105.6.30 Parade Floats Section 105.6.31 Refrigeration Equipment, use of special type Section 105.6.32 Speed Bumps/Humps in Fire Lane Section 105.6.33 Garages-Auto Equipment Maintenance/Repairs Section 105.6.34 Compressed Gases, Use of Sec. 109.3 is amended to read as follows: Sec. 109.3 Any person, firm, or corporation violating any of the provisions or terms of this Ordinance shall be guilty of a misdemeanor and, upon conviction in the Municipal Court, shall be subject to a fine not exceed TWO THOUSAND AND NO/ 100 ($2,000.00) DOLLARS for each offense, and each and every day any such violation shall continue shall be deemed to constitute a separate offense. Sec. 111.4 is amended to read as follows: Sec. 111.4 Any person who shall continue any work after having been served with a stop work order except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable to a fine not to exceed TWO THOUSAND AND NO/100 (,$2,000.00) DOLLARS for each offense, and each and every day any such violation shall continue shall be deemed to constitute a separate offense. Section 202 is amended by adding the following definitions: ADDRESSABLE FIRE DETECTION SYSTEM is any system capable of providing identification of each individual alarm initiating device. The identification shall be in plain English and as descriptive as possible to specifically identify location of the device in alarm. The system shall have alarm verification. ANALOG INTELLIGENT ADDRESSABLE FIRE DETECTION SYSTEM is any system capable of calculating a change in value by directly measurable quantities (voltage, resistance, etc.) at the sensing point. The physical analog may be conducted at the sensing point or at the main control panel. The system shall be capable of compensating for long-term changes in sensor response while maintaining a constant sensitivity. The compensation shall have a preset point at which a detector maintenance signal shall be transmitted to the control panel. The sensor shall remain capable of detecting and transmitting an alarm while in the maintenance mode. CITY shall mean the City of Southlake, Texas CODE OFFICIAL. The Fire Marshal is the designated authority charged by the Director of Public Safety with the duties of administration and enforcement of the code, or a duly authorized representative. FIRE CHIEF shall mean the City of Southlake Chief of Fire Services. FIRE LANE shall mean fire apparatus access road FIRE MARSHAL. See Code Official HIGH -RISE BUILDING A building having floors used for human occupancy located more than 55 feet or three stories above the lowest level of fire department vehicle access. MECHANICAL CODE is the International Mechanical CodeT' as adopted by this jurisdiction. SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self-service basis. STANDBY PERSONNEL. Qualified fire service personnel, approved by the Fire Chief. When utilized, the number required shall be as directed by the Fire Chief. Charges for utilization shall be as normally calculated by the jurisdiction. **Section 307.2; change to read as follows: 307.2 Permit required. A permit shall be obtained from the code official in accordance with Section 105.6 prior to kindling a fire for recognized silvicultural or range or wildlife management practices, prevention or control of disease or pests, or open burning. Application for such approval shall only be presented by and permits issued to the owner of the land upon which the fire is to be kindled. Examples of state or local law, or regulations referenced elsewhere in this section may include but not be limited to the following: 1. Texas Commission on Environmental Quality Regulations. 2. State, County or Local temporary or permanent bans on open burning. 3. Local written policies as established by the Code Official. **Section 307.3; change to read as follows: 307.3 Location. The location for open burning shall not be less than 300 feet (91440 mm) from any structure, and provisions shall be made to prevent the fire from spreading to within 300 feet (91440 mm) of any structure. (exceptions unchanged) **Add Section 307.3.3 to read as follows: 307.3.3 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with Section 307.2. **Section 307.4; change to read as follows: 307.4 Attendance. Open burning, trench burns, bonfires or recreational fires shall be constantly attended until the (remainder of section unchanged). **Section 308.3.1. and 308.3.1.1; change to read as follows: 308.3.1 Open-flame cooking devices. Charcoal burners and other open-flame cooking devices shall not be operated or located on combustible balconies or within 10 feet (3048 mm) of combustible construction. Exceptions: 1. One- and two-family dwellings. 2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system. 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. When permitted as listed in the exceptions of Section 307.5, LP-gas burners having a LP-gas container with a water capacity greater than 2.5 pounds (1.14 kg) [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. Exception: One- and two-family dwellings, and other residential occupancies when those residential occupancies are in compliance with Section 308.3.1, exception #2 may have containers with a water capacity not greater than 20 pounds (9.08 kg) [nominal 1 pound (0.454 kg) LP-gas capacity]. ***Section 405.1; change to read as follows: 405.1 General. Emergency evacuation drills complying with the provisions of this section shall be conducted in the occupancies listed in Table 405.2 or when required by the fire code official. Drills shall be designed in cooperation with the local authorities. ***Section 408.5.4; change to read as follows: 408.5.4 Drill frequency. Emergency evacuation drills shall be conducted at least twelve times per year, four times per year on each shift. "Section 503.2.1; change to read as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4 115 i 14 feet (4267 mm). Exception: Vertical clearance may be reduced, provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance when approved. "Section 503.2.2; change to read as follows: 503.2.2 Authority. The code official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations. Section 503.2.3is changed and 503.2.3.1 is added to read as follows: 503.2.3 Surface. All weather surface shall be asphalt or concrete. Fire lanes shall be designed to support a minimum 65,000 lb. GVW load. Subgrade shall be prepared to a density of not less than 95% as determined by Standard Proctor. Concrete fire lanes shall be a minimum five (5) inch thick 3000 psi concrete reinforced with #3 rebar on 18 inch centers. Asphalt fire lane shall be minimum six (6) inches thick. Drive approaches shall be minimum six (6) inches 3000 PSI concrete with # 3 rebar on 18 inch centers both ways on chairs. Section 503.2.3.1 Private Access Easements shall be built to city street standards as specified in the Subdivision Ordinance. Section 503.3 is changed to read as follows. 503.3 Marking Either approved striping or signs shall be provided and maintained for fire apparatus access roads to identify such roads and prohibit the obstruction thereof or both. (1) Striping - Fire apparatus access roads shall be marked by painted lines of red traffic paint six inches in width to show the boundaries of the lane. The words "FIRE LANE NO PARKING" or "NO PARKING FIRE LANE" shall appear in four inch white letters with a one inch stroke centered on the red stripe at 25 foot intervals on the red border markings along both sides of the fire lanes. (2) Signs - If signs are used, the signs shall read "FIRE LANE NO PARKING" or "NO PARKING FIRE LANE" and shall be 12 inches wide and 18 inches high. Signs shall be painted on a white background with letters and borders in red, using not less than two inch lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet six inches above finished grade. Signs shall be spaced not more than 50 feet apart. Signs may be installed on permanent buildings or walls or as approved by the Code Official. "Section 503.4; change to read as follows: 503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be maintained at all times. **Section 508; shall be amended by adding the following section: 508.5.7 Required Installations. This section provides the minimum hydrant requirements Whenever the fire flow requirements of Appendix C require additional hydrants they are also required The location number and type of fire hydrants connected to a water supply capable of delivering the required fire flow shall be provided on the public street or on the site of the premises, or both to be protected as required and approved by the Chief A fire hydrant shall be located within 100 feet of a fire department connection. Maximum spacing of Fire hydrants shall be in accordance with the following distances: Occupancy Unsprinklered Sprinklered R-3 and U Occupancies 400 feet 600 feet All Others 300 feet 600 feet Hydrants shall be provided at all intersecting streets and at intermediate locations between intersections as prescribed above, measured as the hose would be laid. Fire hydrants shall be accessible to the fire department apparatus by roads which meet the requirements of Section 503.2. Section 509; add subsection 509.2 as follows: 509.2 Emergency Radio Communications. In all buildings in which the type of construction or distance from an operational emergency services antenna or dispatch site does not provide adequate frequency or signal strength as determined by the code official. the building owner shall be responsible for providing the equipment, installation and maintenance of said equipment in a manner to strengthen the radio signal. The radio signal shall meet the minimum input / output strengths according to the emergency radio system's provider and system manager. **Section 704.1; change to read as follows; 704.1 Enclosure. Interior vertical shafts, including but not limited to stairways, elevator hoistways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected in accordance with the codes in effect at the time of construction but, regardless of when constructed, not less than as specified in Table 704.1. When openings are required to be (remainder of section unchanged). Sections 803.3.2 and 803.4.2; add an exception to read as follows: Exception: Corridors protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area. **Section 901.7, change to read as follows: 901.7 Systems out of service. Where a required fire protection system is out of service or in the event of an excessive number of accidental activations, the fire department and the code official shall be notified immediately and, where required by the code official, the building shall either be evacuated or an appFe ed fire teh standby personnel shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. **Section 902.1; add definition of "Fire Area" to read as follows: FIRE AREA. The aggregate floor area enclosed and bounded by fire walls, fire barriers, exterior walls, combustible overhangs or fire-resistance-rated horizontal assemblies of a building. **Section 902.1; under "Standpipe, Types of definition, amend "Manual dry" by adding a sentence to read as follows: The system must be supervised as specified in Section 905.2. ***Section 903.2; delete the exception ***Add Section 903.2.8.3 to read as follows: 903.2.8.3. Self-service storage facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities. Exception: One-story self-service storage facilities that have no interior corridors with a one-hour fire barrier separation wall installed between every storage compartment Section 903.2.10, Amend 903.2.10.3 and add 903.2.10.4, 903.2.10.5 and 903.2.10.6 as follows: 903.2.10.3 Buildings over 55 35 feet or three stories in height. An automatic sprinkler system shall be installed throughout buildings with a floor level, other than penthouses in compliance with Section 1509 having an ee -upant lead of 'Q that is located -5 35 feet or three stories or more above the lowest level of fire department vehicle access. Exceptions: !.Airport eeatr-al towers. 2. Open parking structures in compliance with IBC Section 406. 3. 00eupancies in gr-oup 903.2.10.4 High-Piled Combustible Storage For any building with a clear height exceeding 12 feet (4572 mm) see Chapter 23 of the International Fire Code to determine if those provisions apply. 903.2.10.5 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire-extinguishing system. 903.2.10.6 Buildings Over 6,000 sq. ft. An automatic sprinkler system shall be installed throughout all buildings over 6,000 sa ft. For the purpose of this provision, fire walls shall not define separate buildings For this section only area measurement shall be based on outside dimensions of exterior walls exclusive of vent shafts and courts without deduction for corridors stairways, closets, the thickness of interior walls, columns or other features The floor area of a building, or portion thereof, not provided with surrounding exterior walls shall be the usable area under the horizontal projection of the roof or floor above The gross floor area shall not include shafts with no openings or interior courts For upper level attic type rooms areas where the ceiling height is less than five feet (5' 0") shall not be considered. Unfinished space framed to permit future expansion of floor area shall be considered as part of the area. Joists designed to support floor loads shall be assumed to be for future area Exceptions: 1. Open parking garages in compliance with IBC Section 406.3. 2. Buildings regulated under the International Residential Code as amended "Section 903.3.1.1.1; change to read as follows: 903.3.1.1.1 Exempt locations. When approved by the code official, automatic his sprinklers shall not be required in the following rooms or areas where such {bulk of section unchanged) because it is damp, of fire-resistance-rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the code official. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours. "Section 903.3.5, add a second paragraph to read as follows: Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every fire protection system shall be designed with a 10 psi safety factor. Section 903.3.8; add the following: 903.3.8 Fire Department Connection Lock. All fire department connections shall be secured with a Knox Locking Fire Department Cap after the adopted date of this ordinance. Existing systems shall be brought into compliance with this section within 30 days of notice by the fire code official. **Section 903.4; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. **Add Section 903.6.2 to read as follows: 903.6.2 Spray booths and rooms. New and existing spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system in accordance with Section 1504 **Section 905.2; change to read as follows: 905.2 Installation standards. Standpipe system shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psi air pressure with a high/low alarm. **Section 905.3.2; delete exceptions #1 and 2. **Section 905.4, item #5; change to read as follows: 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with an approved hose connection located either (remainder of paragraph unchanged) **Section 905.9; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. * *Section 906.1 Delete exception. **Add Section 907.1.3 to read as follows: 907.1.3 Design Standards. All alarm systems new or replacement serving 50 or more alarm actuating devices shall be addressable fire detection systems. Alarm systems serving more than 75 smoke detectors or more than 100 total alarm actuating devices shall be analog intelligent addressable fire detection systems. Exception: Existing systems need not comply unless the total building remodel or expansion initiated after the effective date of this code, as adopted, exceeds 30% of the building. When cumulative building remodel or expansion exceeds 50% of the building must comply within 18 months of permit application. **Section 907.2.3; change to read as follows: 907.2.3 Group E. A manual fire alarm system shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems. **Section 907.2.3; change exception #1 and add exception #13 to read as follows: 1. Group E educational and day care occupancies with an occupant load of less than 50 when provided with an approved automatic sprinkler system. 1.1 Residential In-Home daycare with not more than 12 children may use interconnected single station detectors in all habitable rooms (For care of more than five children 2 1/2 or less years of age, see Section 907.2.6.) **Section 907.2.12; change to read as follows: 907.2.12 High-rise buildings. Buildings having floors used for human occupancy located more than 74 55 feet or three stories above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voice/alarm communications system in accordance with Section 907.2.12.2. **Section 907.2.12, exception #3; change to read as follows: 3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code, when used for open air seating-, however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants and similarly enclosed areas. "Section 907.4; add a second paragraph to read as follows: Manual alarm actuating devices shall be an approved double action type. **Add Section 907.6.1 to read as follows: 907 6 1 Installation All fire alarm systems shall be installed in such a manner that the failure of any single alarm-actuating or alarm indicating device will not interfere with the normal operation of any other such devices. All systems shall be Class "A" wired with a minimum of six feet separation between supply and return loops IDC - Class "A" style - D - SLC Class "A" Style 6 - notification Class "B" Style Y. **Section 907.9.2; change to read as follows: 907.9.2 High-rise buildings. In buildings that have floors located more than 75--55 feet or three stories above the (remainder of section unchanged). **Section 912.2; add a sentence to the end of the paragraph to read as follows: Section 912.2 Location. (Paragraph unchanged) The Fire Department Connection shall be located within100 feet of a fire hydrant and so that in the event of collapse a concrete wall panel precast, cast in place or tilt wall would not fall on the fitting or on fire department equipment. **Section 913.4; add a second paragraph to read as follows: The fire pump system shall also be supervised for "loss of power" "phase reversal" and "pump running" conditions by supervisory signal on distinct circuits. ***Section 1008.1.3.4; add criteria #7 as follows: 7 If a full building smoke detection system is not provided approved smoke detectors shall be provided on both the access and egress sides of doors and in a location approved by the authority having jurisdiction of NFPA 72 Actuation of a smoke detector shall automatically unlock the door. **Section 1016.1; add an exception #5 to read as follows: 5. In GroupB office buildings, corridor walls and ceilings need not be of fire-resistive construction within office spaces of a single tenant when the space is equipped with an approved automatic smoke-detection system within the corridor. The actuation of any detector shall activate alarms audible in all areas served by the corridor. The smoke-detection system shall be connected to the building's fire alarm system where such a system is provided. **Section 1019.1.8; change to read as follows 1019.1.8 Smoke proof enclosures. In buildings required to comply with Section 403 or 405, each of the exits of a building that serves stories where the aM floor surface is located more than 35 feet (22 860 mm) or three stories above the lowest level of fire... (remainder of section unchanged) **Section 1504.6; change to read as follows: 1504.6 Fire Protection. New and existing spray Spmy booths and spray rooms shall be protected by an approved automatic fire-extinguishing system [remainder of section unchanged) **Section 2302; add a second paragraph to the definition of "High-Piled Combustible Storage" to read as follows: Any building exceeding 6,000 sq.ft. that has a clear height in excess of 12 feet, making it possible to be used for storage in excess of 12 feet, shall be considered to be high-piled storage and shall comply with the provisions of this section. When a specific product cannot be identified, a fire protection system shall be installed as for Class IV commodities, to the maximum pile height. **Section 3301.1.3; change to read as follows: 3301.1.3 Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are prohibited. Exceptions: 4- Only when approved for fireworks displays, storage and handling of fireworks as provided permitted in Section 3304 and 3308 z. assembly The use of fireworks for aqpproved display as permitted in Section 3308. ***Section 3302; change the definition of "fireworks" to read as follows: FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for entertainment purposes by combustion, deflagration, aPA detonation, and/or activated by ignition with a match or other heat producing device that meets the definition of 1 AG fireworks or 1.3G fireworks as set forth herein. Section 3403.2.2; add new section to read as follows: 3403 2 2 Fire Protection. An approved deluge water foam extin uig 'shing system shall be installed and maintained on all loading facilities and on all unloading facilities. **Section 3403.6; add a sentence to read as follows: An approved method of secondary containment shall be provided for underground tank and piping systems. *Section 3404.2.9.5.1 changed to read as follows: 3404.2.9.5.1 Locations where above ground tanks are prohibited. The storage of Class I and II liquids in above ground tanks is prohibited on land located in the following zoning districts: all residential districts including "SF-1A SF-1B SF-30 SF-20A and SF-2013, Single Family Residential Districts;" "RE, Single Family Residential Estate District;" "AG," Agricultural District; "MF-1, Two Family Residential District," "MF-2, Multiple Family Residential District;" and "MH Manufactured Housing District;" "HC, Hotel District;" "0-1 and 0-2, Office Districts;" "C-1, Neighborhood Commercial District" "C-2 Local Retail Commercial District;" "C-3, General Commercial District;" "C-4, Arterial Mall District;" "13-2 Commercial Manufacturing District", and any "PUD, Planned Unit Development District". "SP-1, Detailed Site Plan District" and "SP-2 Generalized Site Plan District" which includes any use permitted in any of the above-referenced districts Such storage is permitted on land zoned within the following zoning districts: "B-1, Business Service Park District: " `74Light Industrial District; " "7--2, Heavv Industrial District; " and "CS, Community Service District. " or on land zoned for certain S-1-1 or S-P-2 Districts with the approval of the Fire Chief **Section 3404.2.11.5; add a sentence to read as follows: An approved method of secondary containment shall be provided for underground tank and piping systems. **Section 3404.2.11.5.2; change to read as follows: 3404.2.11.5.2 Leak detection. Underground storage tank systems [bulk of provision unchanged] and installed in accordance with NFPA 30 and as specified in Section 3404.2.11.5.3. **Add Section 3404.2.11.5.3 to read as follows: 3404.2.11.5.3 Dry sumps. Approved sampling tubes of a minimum 6 inches in diameter shall be installed in the backfill material of each underground flammable or combustible liquid storage tank. The tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling sump at the corners of the excavation with a minimum of 4 sumps. Sampling tubes shall be placed in the product line excavation within 10 feet of the tank excavation and one every 50 feet routed along product lines towards the dispensers, a minimum of two are required. **Add Sections 3406.5.4.5 and 3406.5.4.5.1 through 3406.5.4.5.3 to read as follows: 3406.5.4.5 Commercial, industrial, governmental or manufacturing. Dispensing of Class II and III motor vehicle fuel from tank vehicles into the fuel tanks of motor vehicles located at commercial, industrial, governmental or manufacturing establishments is allowed where permitted, provided such dispensing operations are conducted in accordance with Sections 3406.5.4.5.1 through 3406.5.4.5.3. 3406.5.4.5.1 Site requirements. 1. Dispensing may occur at sites that have been permitted to conduct mobile fueling. 2. A detailed site plan shall be submitted with each application for a permit. The site plan must indicate: a. all buildings, structures, and appurtenances on site and their use or function; b. all uses adjacent to the property lines of the site, c. the locations of all storm drain openings, adjacent waterways or wetlands; d. information regarding slope, natural drainage, curbing, impounding and how a spill will be retained upon the site prope ; and, e. the scale of the site plan. 3. The Code Official is authorized to impose limits upon: the times and/or days during which mobile fueling operations are allowed to take place, and specific locations on a site where fueling is permitted. 4. Mobile fueling operations shall be conducted in areas not generally accessible to the public. 5. Mobile fueling shall not take place within 15 feet (4.572 m) of buildings, property lines, or combustible storage. 3406.5.4.5.2 Refueling Operator Requirements. 1. The owner of a mobile fueling operations shall provide to the jurisdiction a written response plan which demonstrates readiness to respond to a fuel spill carry out appropriate mitigation measures, and to indicate its process to properly dispose of contaminated materials when circumstances require. 2. The tank vehicle shall comply with the requirements of NFPA 385 and Local, State and Federal requirements. The tank vehicle's specific functions shall include that of supplying fuel to motor vehicle fuel tanks. The vehicle and all its equipment shall be maintained in good repair. 3. Signs prohibiting smoking or open flames within 25 feet (7.62 m) of the tank vehicle or the point of fueling shall be prominently posted on 3 sides of the vehicle including the back and both sides. 4. A fire extinguisher with a minimum rating of 40:BC shall be provided on the vehicle with signage clearly indicating its location. 5. The dispensing nozzles and hoses shall be of an approved and listed type. 6. The dispensing hose shall not be extended from the reel more than 100 feet (30.48m) in length. 7. Absorbent materials, non-water absorbent pads, a 10 foot (3.048 m) long containment boom, an approved container with lid, and a non-metallic shovel shall be provided to mitigate a minimum 5- gallon fuel spill. 8. Tanker vehicles shall be equipped with a fuel limit switch such as a count-back switch, limiting the amount of a single fueling operation to a maximum of 500 gallons (1893 L) between resettings of the limit switch. Exception: Tankers utilizing remote emergency shut-off device capability where the operator constantly carries the shut-off device which, when activated, immediately causes flow of fuel from the tanker to cease. 9. Persons responsible for dispensing operations shall be trained in the appropriate mitigating actions in the event of a fire, leak, or spill. Training records shall be maintained by the dispensing company and shall be made available to the Code Official upon request. 10. Operators of tank vehicles used for mobile fueling operations shall have in their possession at all times an emergency communications device to notify the proper authorities in the event of an emergency, 3406.5.4.5.3 Operational Requirements. 1. The tank vehicle dispensing equipment shall be constantly attended and operated only by designated personnel who are trained to handle and dispense motor fuels. 2. Prior to beginning dispensing operations, precautions shall be taken to assure ignition sources are not present. 3. The engines of vehicles being fueled shall be shut off during dispensing operations. 4. Night time fueling operations shall only take place in adequately lighted areas. 5. The tank vehicle shall be positioned with respect to vehicles being fueled so as to preclude traffic from driving over the delivery hose and between the tank vehicle and the motor vehicle being fueled. 6. During fueling operations, tank vehicle brakes shall be set, chock blocks shall be in place and warning lights shall be in operation. 7. Motor vehicle fuel tanks shall not be topped off. 8. The dispensing hose shall be properly placed on an approved reel or in an approved compartment prior to moving the tank vehicle. 9. The Code Official and other appropriate authorities shall be notified when a reportable spill or unauthorized discharge occurs. **Add Section 3803.2.1.8 to read as follows: 3803.2.1.8 Jewelry Repair, Dental Labs and Similar Occupancies. Where natural gas service is not available, portable LP-Gas containers are allowed to be used to supply approved torch assemblies or similar appliances. Such containers shall not exceed 20- pound (9.0 kg) water capacity. AAggregate capacity shall not exceed 60-pound (27.2 kg) water capacity. Each device shall be separated from other containers by a distance of not less than 20 feet. **Section 3804.2; add an exception #2 to read as follows: Exceptions: 1. {existing exception unchanged) 2 Except as permitted in 307.5 and 3804.3.2, LP-gas containers are not permitted in residential areas. **Add Section 3804.3.2 to read as follows: 3804 3 2 Spas and Pool Heaters Where natural gas service is not available LP-Gas containers are allowed to be used to supply spa and pool heaters Such containers shall not exceed 250-gallon water capacity. See Table 3804.3 for location of containers. Section 2. Penalty. Any person, firm, or corporation who violates, disobeys, omits, neglects or refuses to comply with or who resists the enforcement of any of the provisions of this ordinance shall be fined not more than Two Thousand Dollars ($2,000.00) for all violations involving zoning, fire safety or public health and sanitation, including dumping or refuse, and shall be fined not more than five hundred dollars ($500) for all other violations of this ordinance. Each day that a violation is permitted to exist shall constitute a separate offense. Section 3. Cumulative Clause. This ordinance shall be cumulative of all provisions of ordinances of the City of Southlake, Texas, except where provisions of this ordinance are in direct conflict with the provisions of another ordinance, in which event the conflicting provisions of the other ordinance are hereby repealed. Section 4. Severability Clause. It is hereby declared to be the intention of the City Council that the phrases, clauses, sentences, paragraphs, and sections are severable, and if any phrase, clause, sentence, paragraph, or section of this ordinance shall be declared unconstitutional by the valid judgement or decree of any court of competent jurisdiction, such unconstitutionality shall not affect any of the remaining phrases, clauses, sentences, paragraphs, and sections of this ordinance, since they would have been enacted by the City Council without the incorporation in this ordinance of the unconstitutional phrase, clause, sentence, paragraph, or section. Section 5. Savings Clause. All rights and remedies of the City of Southlake are expressly saved as to any and all violations of the provisions of Article III, Chapter 15 "Fire Code" of the Code of Ordinances, City of Southlake, Texas, as amended, or any other ordinances affecting such code which have accrued at the time of the effective date of this ordinance; and, as to such accrued violations and all pending litigation, both civil and criminal, whether pending in court or not, under such ordinances, same shall not be affected by this ordinance but may be prosecuted until final disposition by the courts. Section 6. Publication. The City Secretary of the City of Southlake is hereby directed to publish in the official newspaper of the City of Southlake, the caption, penalty clause, publication clause and effective date of this ordinance one time within ten days after passage of this ordinance, as required by Section 3.13 of the Charter of the City of Southlake. Section 7. Effective Date. This ordinance shall be in full force and effect from and after its passage and publication as required by law but not before September 30, 2004, and it is so ordained. APPROVED ON FIRST READING THIS DAY OF 12004. 19 tSTfffgL'•. M 70R °r % ATTE T: =v° ' °Oe e• ~ CITY SECRETARY P VED ON SECOND READING THIS DAY OF r I i l 2004. MA OR ° °4rarss►rrara+ars ATTE T: ~'0% cl CITY SECRETARY o APPROVED AS TO FORM AN LEGALITY:* (ZK J " 14#,,fill silt, CITY ATTORNEY EFFECTIVE: 2 3 OLI INVOICE e Star-Telegram Customer ID: CIT57 400 W. 7th Street Invoice Number: 243462951 FORT WORTH,TX 76102 (817)390-7761 Invoice Date: 7/6/04 Federal Tax ID 22-3148254 Terms: Net due in 21 days Due Date: 7/31/04 Bill To: PO Number: CITY OF SOUTHLAKE 1400 MAIN ST Order Number: 24346295 STE 440 Sales Rep: 073 SOUTHLAKE, TX 76092-7604 Description: CITY OF SOUTHLA Publication Date: 7/6/04 -�x„ ..,..,•,. • �--� . . � .� _• a ;�°- , . F. CITY OF SOUTHLAKE Notice is he 13580 1 99 99 LINE $0.81 $80.19 SOUTHLAKE CII 1 PROPERTY FROM Votico Is herebygiven FIR AND EXPLO- SIO PROVIDING byethe City Council of FOR THE ADOPTION thTexan tofaSo��i k OF LOCAL AMEND- $80 19 hearing at bap x,F�NTS THERETO: Net Amount: PEN- on July 2 l sa20 at PROVIDING A 6:00 p.m. or immedi- PROALT CLAUSE; ately followingthe PROVIDING A CU- Work Session,during PROVImuLADINVEG CLAUSE; the Regular City PROVIDING A USE; Council meetingto be ERABILITYVDINCAASAV- PROVIDING A UAV- held in the City INGS CLAUSE Council Chambers of PROVIDING FOR Town Hall,1400 Main PUBLICATION; AND i Street, Southlake, PROVIDING AN EF- Texas.Purpose of the FECTIVE DATE. public hearing is to Section 2.Penalty.Any consider the second person, firm or cor- reading of the fol- oratio who violates, lowing ordinance: disobeys, omits, ne- International Fire 1 glects or,refuses to Code comply with or who ORDINANCE NO. resists the enforce- AN ORDINANCE OF ment of any of the or- THE CITY OF provisions of this dinance shall be fined SOUTHLAKE TEX- not more than Two AS, AMENDING Thousand Dollars CHRISTY L.HOLLAND CHAPTER 15, ARTI- CLE III "FIRE CODE" ($2,000.00) for all vi- olations involving .%� OF THE CODE OF zoning, fire safety or MY COMMISSION EXPIRES ORDINANCES OF , ,J THE CITY OF publica health and SOUTHLAKE TEX- dumpation, including ,,. JULY 31,2004 and is or refuse, THE STA. AS BY ADbPTING i and shall be fined not THE 2003 EDITION more than fWilt ve hun- County of OF THE INTERNA- dred dollars $500)for TIONAL FIRE CODE; S I REPEALING ORDI- thisi other van eons h NANCE NUMBER ordinance. Each Before me, 617 AND REP L- f day that a violation is I. this day personally appeared Lisa Wesselman, Bid and Legal Coordinator for the Sta' lNG ALL O DI- op�`r uteted aesepta a at Fort Worth, in Tarrant County,Texas;and who, after beingdulysworn, did depose and NANCES IN C y WfenseP say that the at Pic HEREWI vclty of Southlake bin the above name a er on the listed dates: BIDS ai LEGAL DEPT. STAR TLEGRAM (817) 39 g N�a���o�N i;lty Sec et ry P OU TO LI E- AND Signed , SUBSCRIBED AND SWORN TO BEFORE ME, THIS Saturday,July 10,200 • /1-'446) Notary Public Thank You For Your Payment Remit To: Star-Telegram Customer ID: CIT57 P.O. Box 901051 Customer Name: CITY OF SOUTHLAKE FORT WORTH, TX 76101-2051 Invoice Number: 243462951 Invoice Amount: $80.19 PO Number: Amount Enclosed: _$ INVOICE Star-Telegram Customer ID: CIT57 400 W. 7th Street Invoice Number: 244155751 FORT WORTH,TX 76102 (817)390-7761 Invoice Date: 7/23/04 Federal Tax ID 22-3148254 Terms: Net due in 21 days Due Date: 7/31/04 Bill To: PO Number: CITY OF SOUTHLAKE 1400 MAIN ST Order Number: 24415575 STE 440 Sales Rep: 073 SOUTHLAKE, TX 76092-7604 Description: CITY OF SOUTHLA Publication Date: 7/23/04 Fn V ,.„, .W as ,i.+u y r 4;i 9 T i I $ I 1 S 6,&' ,.r , ',,r xV4P 1 @ i Y . CITY OF SOUTHLAKE Internationa I3580 1 86 86 LINE $0.81 $69.66 OF I s8UTHLAAKE — International Fire • ORDINANCE NO. 870 Net Amount: $69.66 AN ORDINANCE OF THE CITY OF SOUTHLAKE TEX- AS, AMENDING CHAPTER 15, ARTI- CLE III,"FIRE CODE" OF THE CODE OF ORDINANCES OF THE CITY OF SOUTHLAKE TEX- AS BY ADOPTING (nI��^ r� M 7THE 2003 EDITION [11 V 1? 0 U OF THE INTERNA- TIONAL FIRE CODE; I REPEALING ORDI- NANCE NUMBER 817 AND REPEAL- ING ALL ORDI- AUG - 5 2004 NANCES IN CON- _ ..1 FLICT HEREWITH' I PRESCRIBING y� REGULATIONS r�+[+•' �N's CHRISM L HOLLAND I GOVERNING CON- I DITIONS HAZARD- : MY COMMISSION EXPIRES 1 OUS TO LIFE AND ; . f OFFICE OF CITY SECRETARY PROPERTY FROM , ;; July 31,2008 FIRE AND EXPLO- - ' """'� FOR tHE ADOPTION - .." THE STATE 0 MEN OCATHERETO; County of Tarr AROVIDIN CALAUSE; PROVIDING A CU- MULATIVE CLAUSE; Before me,a N ERAOVIDITY cLA-ASEV aid County and State, this day personally appeared Lisa Wesselman, Bid and Legal Coordinator for the Star-Tel PROVIDING sAV- Star-Telegram, Inc.at Fort Worth, in Tarrant County,Texas; and who,after being duly sworn, did depose and say PROVIDING L A A FOB [hat the attach€ PUBLICATION; AND ement was published in the above na ed paper on the listed dates: BIDS 8i LEGAL DEPT. STAR TLEGRAM (817) 390-73 PROVIDING AN EF- FECTIVE DATE. Section 2.Penalty.Any person, firm, or cor- poration who violates, Signed ,disobeys, omits, ne- glects or refuses to SUBSCRIBED 7 re sill hB nfo ce- )RE ME, THIS Thursday,July 2 ,2 , ment of any of the provisions of this or- dinance shall be fined not more than Two Notary Public Thousand Dollars ( 2,000.00) for all vi- olations involving zoning, fire safety or public. health and sanitation, including Thank You dumping or refuse, and shall be fined not rent more than five hun- -————-... dred dollars($500)for all other violations of this ordinance. Each day that a violation is permitted to exist shall constitute a separate offense. AP- Remit To: PASSED THIS TE Customer ID: CIT57 20th DAY OF JULY REGU DURING c TY Customer Name: CITY OF SOUTHLAKE COUNCIL MEETING. MAYOR:. Andy TX 76101-2051 Invoice Number: 244155751 ATTEST: Lori Farwell, City Secretary Invoice Amount: $69.66 PO Number: Amount Enclosed: $