0935~°ICIAL RLj :. . 2006 International Fuel Gas Code ORDINANCE N0.935 Febr Lary 11, 2008 AN ORDINANCE ADOPTING THE INTERNATIONAL FUEL GAS CODE, 2006 EDITION; PROVIDING FOR THE ADOPTION OF LOCAL AMENDMENTS THERETO; PROVIDING FOR RECORDING OF SUCH CODE AS A PUBLIC RECORD; PROVIDING THAT THIS ORDINANCE SHALL BE CUMULATIVE OF ALL ORDINANCES; PROVIDING A SEVERABILITY CLAUSE; PROVIDING A SAVINGS CLAUSE; PROVIDING FOR PUBLICATION IN PAMPHLET FORM; PROVIDING FOR PUBLICATION IN THE OFFICIAL NEWSPAPER; AND PROVIDING AN EFFECTIVE DATE. WHEREAS, The City of Southlake, Texas is a home rule city acting under its charter adopted by the electorate pursuant to Article XI, Section 5 of the Texas Constitution and Chapter 9 of the Local Government Code; and WHEREAS, City Council of the City of Southlake deems it necessary to adopt this ordinance governing requirements for the installation and maintenance fuel gas systems including requirements for materials, in order to protect the health, safety and welfare of the citizens of the City of Southlake. WHEREAS, beginning in the spring of 2007, NCTCOG's Regional Codes Coordinating Committee (RCCC) and its four advisory boards conducted 20 open review meetings over an 8- month period to review the 2006 editions of the International Codes and to develop regional amendments. Their review and recommendations were completed and endorsed by NCTCOG's Executive Board in October 2007. Now NCTCOG encourages jurisdictions in North Central Texas to adopt the 2006 International Fuel Gas Code along with its respective regional amendments with an effective date of April 1, 2008: NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF SOUTHLAKE, TEXAS: SECTION 1 That the International Fuel Gas Code, 2006 Edition, published by The International Code Council, Inc., is hereby adopted as the Fuel Gas Code of the City of Southlake, except for fuel gas systems otherwise regulated under the International Residential Code for One- and Two- Family Dwellings as adopted. A true and correct copy of this Code is attached to this ordinance as Exhibit "A." SECTION 2 That the 2000 International Fuel Gas Code, as adopted herein, is hereby amended as provided in Exhibit "B" incorporated herein and attached hereto for all purposes of this ordinance. The City of Southlake may from time to time determine that additional local modifications to the 2006 International Fuel Gas Code are necessary and appropriate to meet the unique construction needs of the City of Southlake. To effectuate these modifications, the City council shall enact individual ordinances amending this ordinance fully setting forth the Chang to be made in the code. The amendments shall be consolidated as Exhibit "B" to this ordinance, SECTION 3 The material contained in Exhibits "A" and "B" to this ordinance shall not be includea' in the formal municipal codification of ordinances, but shall be maintained as a public record in the office of the City Secretary and will be available for public inspection and copying during regular business hours. SECTION 4 This ordinance shall be cumulative of all provisions of ordinances of the City of Southlake, Texas, except where the provisions of this ordinance are in direct conflict with the provisions of such ordinances, in which event the conflicting provisions of such ordinances are hereby repealed. SECTION 5 It is hereby declared to be the intention of the City Council that the phrases, clauses, sentences, paragraphs and sections of this ordinance are severable, and if any phrase, clause, sentence, paragraph or section of this ordinance shall be declared unconstitutional by the valid judgment or decree of any court of competent jurisdiction, such unconstitutionality shall not affect any of the remaining phrases, clauses, sentences, paragraphs and sections of this ordinance, since the same would have been enacted by the City council without the incorporation in this ordinance of any such unconstitutional phrase, clause, sentence, paragraph or section. It is not the intention of this ordinance to conflict in any way with the Plumbing License Law of Texas. SECTION 6 Any person, firm or corporation who violates, disobeys, omits, neglects or refuses to comply with or who resists the enforcement of any of the provisions of this ordinance shall be fined not more than Two Thousand Dollars ($2,OOT1.00) for all violations involving zoning, fire safety or public health and sanitation, including dumping or refuse, and shall be fined not more than five hundred dollars ($500) for all other violations of this ordinance. Each day that a violation is permitted to exist shall constitute a separate offense. SECTION 7 All rights and remedies of the City of Southlake are expressly saved as to any and all violations of the provisions of any ordinances affecting the installation and maintenance of electrical systems which have accrued at the time of the effective date of this ordinance; and, as to such accrued violations and all pending litigation, both civil and criminal, whether pending in court or not, under such ordinances, same shall not be affected by this ordinance buy may be prosecuted until final disposition by the courts. SECTION 8 The City Secretary of the City of Southlake is hereby authorized to publish this ordinance 2 r in book or pamphlet form for general distribution among the public, and the operative provisions of this ordinance as so published shall be admissible in evidence in all courts without further proof than the production thereof. SECTION 9 The City Secretary of the City of Southlake is hereby directed to publish in the official newspaper of the City of Southlake,the caption,penalty clause, publication clause and effective date of this Ordinance one time within ten days after passage of this ordinance, as required by Section 3.13 of the 6harter of the City of Southlake. SECTION 10 This ordinance shall be in full force and effect from and after its passage and publication as requit;=ed by law, but not sooner than April 1, 2008, and it is so ordained. .............» Pass,ed And Approved On First Reading On This rith Day Of Q kn./(PP/ ,2008. c �J MAYOR ATTEST: Q • A'' P : CITY SECRETARY A. o " ww • � iems ''f,`S1;Tol¢pa,:s ` y Passed And Approved On Second Reading On This Ut �1 Day Of 1101 ,2008. A MAYOR , ATTEST: G 1 i. )Ai' / : CITY SECRETARY CI a i�6' �o,ti e`,a I+�,sd8�f*98 %°° AP'ROV' P ' FID AND LEGALITY: f,, City Attorney Date: %d c P EFFECTIVE: J1 `1,69067 3 EXHIBIT "B" Amendments to the 2006 International Fuel Gas Code The following sections, paragraphs, and sentences of the 2006 International Fuel Gas Cpde are hereby amended as follows: Standard type is text from the IFGC. Underlined type is inserted. .• "e - : _ _ • - - - - "e - • e " — _. A double asterisk at the beginning. of a section identifies an amendment carried over from the 2003 edition of the code and a t:ciple asterisk identifies a new or revised amendment with the 2006 code. **Section 102.2; insert a sentence to read as follows: §FG101.2 Scope. This code is not intended to contradict the Texas Plumbing License Law• This code shall apply to the installation of fuel gas piping systems, fuel gas utilization equipment, and related accessories as follows: (Remainder of section unchanged.) **Section 102.2; add an exception to read as follows: Exception: Existing dwelling units shall comply with Section 621.2. (Reason: Previous code provisions made unvented heater provisions retroactive except as provided for in local amendment. This amendment and amendment to IFGC 621.2 better clarify what the code already states: existing systems may stay unless considered unsafe.) **Section 102.8; change to read as follows: 102.8 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 8 and such codes, when specifically adopted, and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. (Reason: Legal wording to recognize locally adopted codes and amendments adopted with referenced codes.) **Section 304.10; change to read as follows: 304.10 Louvers and grilles. The required size of openings for combustion, ventilation and dilution air shall be based on the net free area of each opening. Where the free area through a design of louver, grille or screen is known, it shall be used in calculating the size opening required to provide the free area specified. Where the design and free area of louvers and 4 grilles are not known, it shall be assumed that wood louvers will have 25-percent free area and metal louvers and grilles will have 75-50-percent free area. (Remainder of section unchanged.) (Reason: This is the generally accepted practice in the region.) **Section 304.11; change Exception 8 to read as follows: 304.11 Combustion air ducts. (Bulk of section unchanged.) 8. Combustion air intake openings located on the exterior of a building shall have the lowest side of such openings located not less than 12 inches (305 mm) vertically from the adjoining grade level or the manufacturer's recommendation, whichever is more stringent. (Reason: To recognize the manufacturer's installation requirements.) **Section 305.5; delete. (Reason: This provision does not reflect standard practice in this area. Consistent with regional amendment to IMC 304.6.) **Section 305.7; change to read as follows: 305.7 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending a minimum of 3 inches (76 mm) above adjoining grade or shall be suspended a minimum of 6 inches (152 mm) above adjoining grade. (Reason: Consistent with current local practice. Consistent with regional amendment to IMC 304.9.) ***Section 306.3; change to read as follows: 306.3 Appliances in attics. Attics containing appliances requiring access shall be provided . . . (bulk of paragraph unchanged) . . . from the opening to the equipment. The passageway shall have continuous unobstructed solid flooring not less than 24- 30 inches (640 762 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the equipment. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), or larger where such dimensions are not large enough to allow removal of the largest appliance. As a minimum, access to the attic space shall be provided by one of the following: 1. A permanent stair. 2. A pull down stair. 3. An access door from an upper floor level. 4. Access Panel may be used in lieu of items 1, 2, and 3 with prior approval of the code official due to building conditions. Exceptions: (No changes to exceptions.) (Reason: To provide a safe means of accessibility. Consistent with regional amendment to IMC 306.3.) 5 **Section 306.5; change to read as follows: 306.5 Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a an aggregate height exceeding 16 feet (4877 mm), such access shall be provided by a permanent approved means of access_, - - - • - - _ - _ - _ - _ -• Permanent exterior ladders providinq roof access need not extend closer than 8 feet (2438 mm) to the finish grade or floor level below and shall extend to the equipment and appliance's level service space. Such access shall . . . (bulk of section to read the same). . . on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). A receptacle outlet shall be provided at or near the equipment and appliance location in accordance with the Electrical Code. (Reason: To assure safe access to roof appliances. Consistent with IMC amendments.) ***Section 306.5.1; change to read as follows: 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed - - e_ - _ - - _ _ - _ - -- - - - __ _ _ _ percent slope) or greater on roofs having slopes greater than 4 units vertical in 12 units horizontal and having an edge more than 30 inches (762 mm) above grade at such edge, a catwalk at least 16 inches in width with substantial cleats spaced not more than 16 inches apart shall be provided from the roof access to a level platform at the appliance. The level platform shall be provided on each side of the appliance to which access is required for service, repair or maintenance. The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm) above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the International Building Code. (Reason: To assure safe access to roof appliances. Consistent with IMC amendments.) ***Add Section 306.7 to read as follows: 306.7 Water heaters above ground or floor. When the attic, roof, mezzanine or platform in which a water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level, it shall be made accessible by a stairway or permanent ladder fastened to the building. Exception: A max 10 gallon water heater (or larger with approval) is capable of being accessed through a lay-in ceiling and a water heater is installed is not more than ten (10) feet (3048 mm) above the ground or floor level and may be reached with a portable ladder. 306.7.1. Whenever the mezzanine or platform is not adequately lighted or access to a receptacle outlet is not obtainable from the main level, lighting and a receptacle outlet shall be provided in accordance with Section 306.3.1. (Reason: To provide safe access to water heaters. Consistent with regional amendments to IPC 502.5 and IMC 306.6.) 6 **Section 306.5; change to read as follows: 306.5 Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a an aggregate height exceeding 16 feet (4877 mm), such access shall be provided by a permanent approved means of access, +"° °.,+°^+ of ~~,hinh c h•~ll h° frnm Permanent exterior ladders providing roof access need not extend closer than 8 feet (2438 mm) to the finish grade or floor level below and shall extend to the equipment and appliance's level service space. Such access shall ... {bulk of section to read the same}... on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). A receptacle outlet shall be provided at or near the equipment and appliance location in accordance with the Electrical Code. (Reason: To assure safe access to roof appliances. Consistent with IMC amendments.) ***Section 306.5.1; change to read as follows: 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed ^^ ° rnnf hwinn .~ ~L,n° of +hr°° „ni+~ .,°r+in~l in '17 ~ ~ni+~ hnri~nn+.~1 /7 C._ r,°rn°n+ elnn°~ r~r ryr°~+°r on roofs having slopes greater than 4 units vertical in 12 units horizontal and having an edge more than 30 inches (762 mm) above grade at such edge, a catwalk at least 16 inches in width with substantial cleats spaced not more than 16 inches apart shall be provided from the roof access to a level platform at the appliance. The level platform shall be provided on each side of the appliance to which access is required for service, repair or maintenance. The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm) above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the International Building Code. (Reason: To assure safe access to roof appliances. Consistent with IMC amendments.) **'`Add Section 306.7 to read as follows: 306.7 Water heaters above ground or floor. When the attic, roof, mezzanine or platform in which a water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level, it shall be made accessible by a stairway or permanent ladder fastened to the building. Exception: A max 10 gallon water heater (or larger with approval) is capable of being accessed through a lay-in ceiling and a water heater is installed is not more than ten (10) feet (3048 mm) above the ground or floor level and may be reached with a portable ladder. 306.7.1. Whenever the mezzanine or platform is not adequately lighted or access to a receptacle outlet is not obtainable from the main level, lighting and a receptacle outlet shall be provided in accordance with Section 306.3.1. (Reason: To provide safe access to water heaters. Consistent with regional amendments to IPC 502.5 and IMC 306.6.) 6 **Section 401.5; add a second paragraph to read as follows: Both ends of each section of medium pressure corruaated stainless steel tubin (CSST) shall identify its operating gas pressure with an approved tag. The tags are to be composed of aluminum or stainless steel and the following wording shall be stamped into the tag_ "WARNING 1/2 to 5 psi gas pressure Do Not Remove" (Reason: To protect homeowners and plumbers.) **Section 402.3; add an exception to read as follows: Exception: Corrugated stainless steel tubing (CSST) shall be a minimum of 1/2" (18 EHD). (Reason: Pipe less than 1/2" has a history in this region of causing whistling.) **Section 404.6; change to read as follows: 404.6 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels, the piping shall be installed in accordance with Section 404.11 a nnin+ ~~ih°r° +h° nin° °mern°e frnm +h° flnnr (Reason: Referencing Section 404.11 provides CSST piping with outside venting.) **Section 404.9; change to read as follows: 404.9 Minimum burial depth. Underground piping systems shall be installed so the top of i e is a minimum depth of 4~ 18 inches (~ 458 mm) below grade, °~^°^+ ~~ r,rn.,i'+°,~ fnr (Reason: To provide increased protection to piping systems.) ***Section 404.9.1; delete. (Reason: Individual lines should also be buried to 18 inches.) ~**Section 406.1; change to read as follows: 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication, and installation practices comply with the requirements of this code. The permit holder shall make the applicable tests prescribed in Sections 406.1.1 through 406.1.5 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the code official when the piping system is ready for testing The equipment, material, power and labor necessary for the inspections and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests (Reason: To utilize language used in the IPC regarding who is responsible for testing procedures.) ***Section 406.4; change to read as follows: 406.4 Test pressure measurement. Test pressure shall be measured with a monometer or with apressure-measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. ~"°^"°ni^,~ n.,,,^°~ „ °,+ +^ ^,°.. ,.r° fi~i° +irv~°c+ +h° +°~+ r+r°ee~ ~r° (Reason: To require the use of more accurate diaphragm gauges. Spring gauges do not provide accurate measurement below approximately 17 psig.) ***Section 406.4.1; change to read as follows: 406.4.1 Test pressure. The test pressure to be used shall be not less than #des-tT"e-~9sed~ma~iwer~~~;ess~, h„+ .,n+ ~°~~ +h ~ 3 psig (20 kPa gauge), or at the discretion of the Code Official, the piping and valves may be tested at a pressure of at least six (6) inches (152 mm) of mercury measured with a manometer or slope gauge. eoo~des+gn-pn?se~°~Refe- +°ct~fe&,rk~Fe-e~cseedsT~ ~G131131t]GLC1Lp1t°,~T~_~.n~sr~n+ of +h° ~n°nifi°rl minirr~~ ~m ~ii°Ir) c+r°nry+h of +h° r+ir~° For f''~f''~~ ~~ J~ ""~ r ~r v,an vary tests requiring a pressure of 3 psig, iaphragm gauges ~ ~°°^~ +n ,,,°,~, ,~° +°~+ pfess~es shall utilize a dial with a minimum diameter of three and one half inches (3'/") a set hand, 1/10 pound incrementation and pressure range not to exceed 6 psi for tests requiring a pressure of 3 psig. For tests requiring a pressure of 10 psig diaphragm gauges shall utilize a dial with a minimum diameter of three and one-half inches (3 '/2"), a set hand, a minimum of 2/10 pound incrementation and a pressure range not to exceed 20 psi. #~..o a-~a~ge~#~+ +nes#-er~d-e,~a~,~~°~° i~ .,n+ nr~t~ ~h•+~ +im°~ +h° +°~+ .,~°~~„~°. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa) (1/2 psi) and less than 200 inches of water column pressure (52.2 kPa~ (7.5 psi), the test pressure shall not be less than ten (10) pounds per square inch (69.6 kPa). For piping carrying gas at a pressure that exceeds 200 inches of water column (52.2 kPa) (7.5 psi), the test pressure shall be not less than one and one-half times the proposed maximum working pressure. (Reason: To provide for lesser pressures to coordinate with the use of more accurate diaphragm gauges.) **Section 406.4.2; change to read as follows: 406.4.2 Test duration. Test duration shall be held for a length of time satisfactory to the Code Official, but in no case for net less than fifteen (15) minutes. For welded piping, and for piping carNing gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa), the test duration shall be held for a length of time satisfactory to the Code Official, but in no case for less than thirty (30) minutes. (Delete remainder of section.) (Reason: To comply with accepted regional practices.) **Add Section 409.1.4 to read as follows: 409.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless steel (CSST) piping systems shall be supported with an approved termination fitting or equivalent support, suitable for the size of the valves, of adeauate strength and quality and located at intervals so as to prevent or damp out excessive vibration but in no case greater than 12-inches from the center of the valve. Supports shall be installed so as not to interfere with the free expansion and contraction of the system's piping fittings and valves between anchors. All valves and supports shall be designed and installed so they will not be disengaged by movement of the supporting piping. (Reason: To provide proper security to CSST valves. These standards were established in this region in 1999 when CSST was an emerging technology.) **Section 410.1; add a second paragraph and exception to read as follows: Access to regulators shall comply with the requirements for access to appliances as specified in Section 306. Exception: A passageway or level service space is not required when the regulator is capable of being serviced and removed through the required attic opening_ (Reason: To require adequate access to regulators.) **Section 614.6; add a sentence to read as follows: The size of duct shall not be reduced alona its developed length nor at the point of termination. (Reason: To clarify the size requirement. Consistent with regional amendment to IMC 504.6.) ***Section 614.6.1; change to read as follows: 614.6.1 Maximum length. The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet (7620 mm) from the dryer location to the outlet terminal. The maximum length of the duct shall be reduced 2% feet (762 mm) for each 45 degree (0.79 rad) bend and 5 feet (1524 mm) for each 90 degree (1.6 rad) bend. Exceptions: 1_Where the make and model of the clothes dryer to be installed is known and the manufacturer's installation instructions for such dryer are provided to the code official, the maximum length of the exhaust duct, including any transition duct, shall be permitted to be in accordance with the dryer manufacturer's installation instructions, and provided that a 4 inch by 6 inch sign red in color with white letters is permanently affixed to the structure stating the following_ Warning: Dryer must be approved for vent length not to exceed 40 feet total developed length (TDL.) Duct Size: (Insert Number) Total Developed Length: (Insert Number) 2. Where the first 9 feet of vent are 4"diameter pipe with not over two 90° bends and the pipe size is then increased to 5" diameter, it may extend horizontally as far as 28.5 feet to the termination outdoors. (Reason: Engineered dryer vent equivalent considering velocity and pressure drop. To make more consistent with regional practice. Dryer technology has improved to the point where they should be capable of handling this. Consistent with regional amendment to IMC 504.6.1.) **Section 621.2; change to read as follows: 621.2 Prohibited use. One or more unvented room heaters shall not be used as the sole source of comfort heating in a dwelling unit. Exception: Existing approved unvented heaters may continue to be used in dwelling units, in accordance with the code provisions in effect when installed, when approved by the Code Official unless an unsafe condition is determined to exist as described in Section 108.7. (Reason: Gives code official discretion.) **Section 624.1.1; change to read as follows: 624.1.1 Installation requirements. The requirements for water heaters relative to access, sizing, relief valves, drain pans and scald protection shall be in accordance with the International Plumbing Code. (Reason: To clarify installation requirements. Also corresponds with amendments regarding water heater access.) END OF AMENDMENTS to INVOICE Preview Star-Telegram Customer ID: CIT57 400 W.7TH STREET Invoice Number: 294286691 FORT WORTH,TX 76102 RECEIVED (817)390-7761 Invoice Date: 2/16/2008 Federal Tax ID 22-3148254 MAR — 3 2008 Terms: Net due in 21 days Due Date: 2/29/2008 Bill To: CITY OF SOUTHLAKE OFFICE OF CITY 7r"r PO Number: no po 1400 MAIN ST Order Number: 29428669 STE 440 Sales Rep: 073 SOUTHLAKE, TX 76092-7604 Description: CITY OF SOUTHLA Attn Attn: ACCOUNTS PAYABLE Publication Date: 2/16/2008 Description Location Col Depth Linage MU Rate Amount CITY PUBLICATION IN CITY OF SOUTH Nottiice is OUTHLAKE hereby given PAMPHLET FORM; I 87 87 LINE $0.8 1 $70.47 by the City Council PROVIDING FOR of the City of PUBLICATION IN Southlake, Texas, THE OFFICIAL Sales Discount that a public hearing NEWSPAPER; AND ($5.00) will be held on March PROVIDING AN EF- 4,2008,at 5:00 p.m. FECTIVE DATE. or immediately fol- SECTION 6 Misc Fee lowing the Work Any person, firm or Session, during the corporation who vi- $5.00 Regular City Council olates, disobeys, meeting to be held omits, neglects or in the City Council refuses to comply Chambers of Town with or who resists Hall, 1400 Main the enforcement of Street, Southlake, any of the provisions Texas. Purpose of of this ordinance ` the public hearing is shall be fined not ,([,1``/�vr` Net Amount: $70.47 to consider the sec- more than Two �� and reading of the Thousand Dollars CV - ,,._ following ordinance: ($2,000.00) for all ,( ORDINANCE violations involving NO. 935 zoning,fire safety or AN ORDINANCE'' publictionedlth and including FEB 2 6 1000 ADOPTING THE IN- dumping or refuse, - TERNATIONAL FUEL and shall be fined not --- EDI CODE,PROVID-2006 more than five hun- INGTIO FORTE dred dollars ($500) . ADOPTION OF LO- for all other viola- • HOLLAND CAL AMENDMENTS tions of this ordi- a M •ION EXPIRES THERETO; PROVID- Hance.Each day that i*; �� •'�: ING FOR RECORD- a violation is per- ,i` .•. "'r 'July 31,2008 ING OF SUCH CODE mitted to exist shall `,Ay '•,;f. 'ItV AS A PUBLIC REC- constitute a sepa- ORD; PROVIDING rate offense. _ THE STATE OF TE THAT THIS ORDI- City of Southlake NANCE SHALL BE Lori Payne County of Tarrant CUMULATIVE OF City Secretary ALL ORDINANCES; PROVIDING A SEV.- Before me,a NotarRIGSPOVDINAAV- d County and State,this day personally appeared Deborah Baylor, Bid and Legal Coordinator for the Star- Telegram,publishedNGS PR CLAUSE; FOR 71, Inc.at Fort Worth,in Tarrant County,Texas;and who,after being duly sworn,did depose and say that the attached clipping of an aaverusement was published in t bove named paper on the listed dates: BIDS&LEGAL DEPT. STAR TELEGRAM (817)390-7501 Signed ` \C\ ‘4b QN SUBSCRIBED AND SWORN TO BEFORE ME,THIS Tuesday, Febru. 19, ,i li. CC--; Notary Public Thank You For Your Payment Remit To: Star-Telegram Customer ID: CIT57 P.O. BOX 901051 Customer Name: CITY OF SOUTHLAKE FORT WORTH, TX 76101-2051 Invoice Number: 294286691 Invoice Amount: $70.47 PO Number: no po Amount Enclosed: $ I INVOICE Preview Star-Telegram Customer ID: CIT57 400 W. 7TH STREET Invoice Number: 294874911 FORT WORTH,TX 76102 (817)390-7761 Invoice Date: 3/7/2008 Federal Tax ID 22-3148254 Terms: Net due in 21 days Due Date: 3/31/2008 Bill To: PO Number: NO PO CITY OF SOUTHLAKE 1400 MAIN ST Order Number: 29487491 STE 440 Sales Rep: 073 SOUTHLAKE, TX 76092-7604 Description: CITY OF SOUTHLA Attn Attn: ACCOUNTS PAYABLE Publication Date: 3/7/2008 Description Location Col Depth Linage MU Rate Amount CITY CITY OF SOUTHLAK OR ODFINANEHNOK g35 ) 135 S0 1 72 72 LINE $0.81 $58.32 AN ORDINANCE ADOPTING THE IN- TERNATIONAL FUEL ���, Sales Discount GAS CODE, 2006 ['�.E 1:t V i_ • ($5.00) EDITION; PROVID- ING FOR THE ADOPTION OF LO- Misc Fee CAL AMENDMENTS $5.00 THERETO; PROVID- ING FOR MAR 2 0 2008 RECORD- ING OF SUCHCHCODEDE AS A PUBLIC REC- ORD; PROVIDING THAT THIS ORDI- NANCE SHALL BE CUMULATIVE OF /°'� ���aaa^ A rivet Amount: $58.32 PROVIDINGL ORDINANCES; it ; Ot VICY StCRET(],`Y ABLITYA SEV; QFF��_ ERABILITY CLAUSE; � PROVIDING A SAV- INGS CLAUSE; PROVIDING FOR PUBLICATION IN PAMPHLET FORM; PROVIDING FOR PUBLICATION IN THE OFFICIAL —NEWSPAPER; ANDPROVIDING AN EF- cit..* CHRIST'�L.HOLLANFECTIVE DATE. MYOpMMISSIONEXPIRES SECTION 6ry 91,2006 Any person, firm or corporation who vi- olates, disobeys, 1kx!P ,_...THE STATE OF TEXA, o fuses neglects or County of Tarrant with or who resists the enforcement of any of the provisions Before me,a Notary PL oshallthbe fined Tanotunty and State,this day personally appeared Deborah Baylor, Bid and Legal Coordinator for the Star- Telegram,published by Thousandhan Dollars C.at Fort Worth,in Tarrant County,Texas;and who,after being duly sworn,did depose and say that the attached clipping of an olations invorlving>lished in the ove named paper on the listed dates: BIDS&LEGAL DEPT. STAR TELEGRAM (817)390-7501 zoning,fire safety or public health and sanitation,upinincluding dumping or refuse, and shall be fined not Signed more than five hun- dred dollars ($500) SUBSCRIBED AND SV1 forons all of other this violaordi---_. ' THIS Tuesday, rch 1 2 Li nance.Each day that / j a violation is per- '� / mitted to exist shall NotaryPublic constitute a sepa- rate offense. PASSED AND AP- PROVED THIS THE 4th DAY OF MARCH, 2008, DURING THE REGULAR CITY COUNCIL MEETING. MAYOR: Andy Wambsganss Thank You For YI ATTESTty : LonSecretary Payne, Ci Remit To: Star-Telegram Customer ID: CIT57 P.O. BOX 901051 Customer Name: CITY OF SOUTHLAKE FORT WORTH,TX 76101-2051 Invoice Number: 294874911 Invoice Amount: $58.32 PO Number: NO PO Amount Enclosed: $