0930OFFICIAL RECORD
February 11, Zoos 2006 International Building Code
ORDINANCE NO. 930
AN ORDINANCE ADOPTING THE 2006 EDITION OF THE INTERNATIONAL
BUILDING CODE, REGULATING THE ERECTION, CONSTRUCTION,
ENLARGEMENT, ALTERATION, REPAIR, MOVING, REMOVAL,
DEMOLITION, CONVERSION, OCCUPANCY, EQUIPMENT, USE, HEIGHT,
AREA AND MAINTENANCE OF ALL BUILDINGS OR STRUCTURES, EXCEPT
ONE- AND TWO-FAMILY DWELLINGS AND MULTIPLE SINGLE-FAMILY
DWELLINGS (TOWNHOUSES), IN THE CITY OF SOUTHLAKE; PROVIDING
FOR THE ADOPTION OF LOCAL AMENDMENTS THERETO; PROVIDING FOR
RECORDING OF SUCH CODE AS A PUBLIC RECORD; PROVIDING THAT THIS
ORDINANCE SHALL BE CUMULATIVE OF ALL ORDINANCES; PROVIDING A
SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY FOR VIOLATIONS
HEREOF; PROVIDING A SAVINGS CLAUSE; PROVIDING FOR PUBLICATION
IN PAMPHLET FORM; PROVIDING FOR PUBLICATION IN THE OFFICIAL
NEWSPAPER; AND PROVIDING AN EFFECTIVE DATE.
WHEREAS, the City of Southlake is a home rule city acting under its charter adopted by
the electorate pursuant to Article XI, Section 5 of the Texas Constitution and Chapter 9 of the
Local Government Code; and
.WHEREAS, the City Council of the City of Southlake deems it necessary to adopt this
ordinance providing minimum standards to safeguard the health, property, and welfare of the
citizens of Southlake by regulating and controlling the use, occupancy, maintenance, repair,
design, construction and quality of materials for buildings and structures within the City.
WHEREAS, beginning in the spring of 2007, NCTCOG's Regional Codes Coordinating
Committee (RCCC) and its four advisory boards conducted 20 open review meetings over an 8-
month period to review the 2006 editions of the International Codes and to develop regional
amendments. Their review and recommendations were completed and endorsed by NCTCOG's
Executive Board in October 2007. Now NCTCOG encourages jurisdictions in North Central
Texas to adopt the 2006 International Building Code along with its respective regional
amendments with an effective date of April 1, 2008:
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY
OF SOUTHLAKE, TEXAS:
SECTION 1
That the International Building Code, 2007 Edition, published by the International Code
Council, including the standards referenced therein, including Appendix Chapters A, C, F, G, H,
I and J are hereby adopted as the Building Code of the City of Southlake regulating the erection,
construction, enlargement, alteration, repair, moving, removal, demolition, conversion,
occupancy, equipment, use, height, area and maintenance of all buildings or structures, except
one- and two-family dwellings and multiple single family dwellings (townhouses), in the City of
Southlake. True and correct copies of these documents are attached as Exhibit "A."
SECTION 2
That the 2003 International Building Code, as adopted herein, is hereby amended as
provided in Exhibit "B" incorporated herein and attached hereto for all purposes of this
ordinance. The City of Southlake, Texas may from time to time determine that additional local
modifications to the Building Code are necessary and appropriate to meet the unique needs of the
City of Southlake, Texas. To effectuate these local modifications, the City Council shall enact
individual ordinances amending this Ordinance, fully setting forth the change to be made in the
Building Code. These amendments shall be consolidated as Exhibit "B" to this Ordinance.
SECTION 3
The material contained in Exhibits "A" and "B" to this ordinance shall not be included in
the formal municipal codification of ordinances, but shall be maintained as a public record in the
office of the City Secretary and will be available for public inspection and copying during regular
business hours.
SECTION 4
This ordinance shall be cumulative of all provisions of ordinances of the City of
Southlake, Texas, except where the provisions of this ordinance are in direct conflict with the
provisions of such ordinances, in which event the conflicting provisions of such ordinances are
hereby repealed.
This ordinance is intended to replace the following:
1. Ordinance 868, as amended, the 2003 International Building Code.
This ordinance is not intended to amend or replace the following:
1. Ordinance 480, as amended, the Zoning Ordinance.
2. Ordinance 483, as amended, the Subdivision Ordinance.
3. Ordinance 557, as amended, Exterior Masonry Construction Requirements
4. Ordinance 568, as amended, Contractor's Licensing Ordinance
6. Ordinance 506-A, as amended, the Sign Ordinance
SECTION 5
It is hereby declared to be the intention of the City Council that the phrases, clauses,
sentences, paragraphs, and sections of this ordinance are severable, and if any phrase, clause
sentence, paragraph or section of this ordinance shall be declared unconstitutional by the valid
judgment or decree of any court of competent jurisdiction, such unconstitutionality shall not
affect any of the remaining phrases, clauses, sentence, paragraphs and sections of this ordinance,
since the same would have been enacted by the City Council without the incorporation in this
ordinance of any such unconstitutional phrase, clause, sentence, paragraph or section.
2
SECTION 6
Any person, firm or corporation who violates, disobeys, omits. neglects or refuses to
comply with or who resists the enforcement of any of the provisions of this ordinance shall be
fined not more than Two Thousand Dollars ($ 2,000.00) for any violation involving zoning, fire
safety or public health and sanitation, including dumping or refuse, and shall be fined not more
than five hundred dollars ($500) for any other violation of this ordinance. Each day that a
violation is permitted to exist shall constitute a separate offense.
SECTION 7
All rights and remedies of the City of Southlake are expressly saved as to any and all
violations of the provisions of any ordinances affecting the regulation and control of the use,
occupancy, maintenance, repair, design, construction and quality of materials for buildings and
structures within the City which have accrued at the time of the effective date of this ordinance;
and, as to such accrued violations and all pending litigation, both civil and criminal, whether
pending in court or not, under such ordinances, same shall not be affected by this ordinance but
may be prosecuted until final disposition by the courts.
SECTION 8
The City Secretary of the City of Southlake is hereby authorized to publish this ordinance
in book or pamphlet form or on the Internet for general distribution among the public, and the
operative provisions of this ordinance as so published shall be admissible in evidence in all
courts without further proof than the production thereof.
SECTION 9
The City Secretary of the City of Southlake is hereby directed to publish in the official
newspaper of the City of Southlake or as authorized by law, the caption, penalty clause,
publication clause and effective date of this ordinance one time within ten days after passage of
this ordinance, as required by Section 3.13 of the Charter of the City of Southlake.
SECTION 9
This ordinance shall be in full force and effect from and after its passage and publication
as required by law but not before April 1, 2008, and it is so ordained.
PASSED AND APPROVED ON FIRST READING THIS ~ DAY OF
2008.
;;~ ~`'v
MAYOR ~ .,~ ~~~~ °_
~ `-.
.d ~, "
~,
~~
ATTEST• ., ~ a m ~
a
t
~~ ~ a ,'
~s SSgH AAi9 CaA~"9,~
CITY SECRETARY
PASSED AND APPROVED ON SECOND READING THIS ~ DAY OF
2008.
MAYOR
ATTEST:
- -,;•`
CITY SECRETARY ~~.~~'~
AP ROV D S O FORM AND LEGALITY: v ~ ':
~r
r £~~ ~~~~' ~'~~
~~ ~° ~r~,~ ~ 7Y ~~1~s
~s~J31a014~a~~
City Attorney
Date: ~ ~,.~..or-~
EFFECTIVE: Date: /}~}~,~(,h ~ ~~)~
EXHIBIT "B"
LOCAL AMENDMENTS TO THE 2006 INTERNATIONAL BUILDING CODE
The following sections, paragraphs, and sentences of the 2003 International Building
Code are hereby amended as follows:
(Standard type is text from the IBC. Underlined type is text inserted. ~ ~^°~ fhrn„^h +.,.,o ;~
Qei~te~text-#r^~~ After each code amendment a reason is given in parentheses. The
reason is not a part of the code, but is given to aid in understanding the code.
**Section 101.1; Insert city name as follows:
101.1 Title. These regulations shall be known as the Building Code of The City of
Southlake, Texas hereinafter referred to as "this code."
**Section 101.4; change to read as follows:
101.4 Referenced codes. The other codes listed in Sections 101.4.1 through 101.4.7
and referenced elsewhere in this code, when specifically adopted, shall be considered part
of the requirements of this code to the prescribed extent of each such reference.
Whenever amendments have been adopted to the referenced codes and standards, each
reference to said code and standard shall be considered to reference the amendments as
well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code
as adopted.
(Reason: Legal wording to recognize locally adopted codes and amendments adopted with
referenced codes.)
**Section 105.1; change to read as follows:
105.1 Required. Any owner or authorized agent who intends to construct, enlarge, alter,
repair, move, demolish, or change the occupancy of a building or structure, to excavate or
change the grade of any property, or to erect, install, enlarge, alter, repair, remove,
convert or replace any electrical, gas, mechanical or plumbing system, the installation of
which is regulated by this code, or to cause any such work to be done, shall first make
application to the building official and obtain the required permit. For excavation or grading
permits see appendix chapter J as adopted.
(Reason: Consistent with previous edition amendment, to provide means to regulate grading
affecting other properties.)
*** Section105.2: amend item 2 under Building and Electrical as follows:
Building:
1. (No change)
2. Fences not over 6 feet(1829 mm) high) except masonry fences or pool barriers.
3. - 9. (No change)
(Reason: Consistent with current policy.)
5
Electrical:
Repairs and maintenance: Minor repair work, including the replacement of lamps or the
connection of approved portable electrical equipment to approved permanently
installed receptacles. Repair or replacement of fixed motors, transformers or fixed
approved appliances of the same type and rating in the same location Repair or
replacement of current-carrying parts of any switch, contactor or control device
Reinstallation of attachment plug receptacles but not the outlets therefor Repair or
replacement of any overcurrent device of the required capacity in the same location
Taping joints.
Radio and television transmitting stations: The provisions of this code shall not apply
to electrical equipment used for radio and television transmissions, but do apply to
equipment and wiring for a power supply and the installations of towers and antennas.
Temporary testing systems: A permit shall not be required for the installation of any
temporary system required for the testing or servicing of electrical equipment
or apparatus.
Other exemptions: Temporary decorative lighting Removal of electrical wirinq~ Electrical
wiring, devices, appliances, apparatus or equipment operating at less than 25 volts and
not capable of supplying more than 50 watts of energy Low-energy power control and
signal circuits of Class II and Class III as defined in the Electrical Code.
(Reason: Added language from former UAC is more specific.)
***Section 105.3.1 and 105.3.2; change to read as follows:
105.3.1 Action on application. The building official shall examine or cause to be
examined applications for permits and amendments thereto within a reasonable time after
filing, but not less than required by state law. If the application or the construction
documents do not conform to the requirements of pertinent laws, the building official shall
reject such application in writing, stating the reasons therefor. If the building official is
satisfied that the proposed work conforms to the requirements of this code and laws and
ordinances applicable thereto, the building official shall issue a permit therefor as soon as
practicable.
105.3.2 Time limitation of application. An application for a permit for any proposed work
shall be deemed to have been abandoned ~9 45 days after the date of filing, unless such
application has been pursued in good faith or a permit has been issued; except that the
building official is authorized to grant one or more extensions of time for additional periods
not exceeding g8 45 days each. A good faith effort shall be deemed to be demonstrated
by response to city comments, requests for additional information or purchasing of permit
within 45 days of notice by the citLr. The extension shall be requested in writing and
justifiable cause demonstrated.
(Reason: to call attention to state limitations on the city and place similar limitations on applicants in
order to reduce buildup of backlog of plans and applications.)
**Section 106.2; change to read as follows:
106.2 Site plan. The construction documents submitted with the application for permit
shall be accompanied by a site plan showing to scale the size and location of new
construction and existing structures on the site, distances from lot lines, the established
street grades and the proposed finished grades and, as applicable, flood hazard areas,
6
floodways, and design flood elevations; and it shall be drawn in accordance with an
accurate boundary line survey. Plans shall also show proposed erosion control and tree
protection measures in accordance with recognized standards and any additional
information as required by other ordinances. In the case of demolition, the site plan shall
show construction to be demolished and the location and size of existing structures and
construction that are to remain on the site or plot. The building official is authorized to
waive or modify the requirement for a site plan when the application for permit is for
alteration or repair or when otherwise warranted.
(Reason: Erosion control and tree preservation are required by other ordinances; this reference
calls those requirements to the attention of the designer.)
**Section 108.7; add.
108.7 Re-inspection Fee. A fee as established by city council resolution may be charged
when:
.The inspection called for is not ready when the inspector arrives;
.The temporary electrical pole does not have a building permit clearly posted;
• No building address or permit card is clearly posted;
• City approved plans are not on the job site available to the inspector;
.The building is locked or work otherwise not available for inspection when called;
• The job site is red-tagged twice for the same item;
.The original red tag has been removed from the iob site.
.Violations exist on the property including failure to maintain erosion control, trash
control or tree protection.
Anv re-inspection fees assessed shall be paid before any more inspections are made on
that job site.
(Reason: This fee is not a fine or penalty but is designed to compensate for time and trips when
inspections are called for when not ready.)
***Section 108.7 and 108.8; add:
108.7 Investigation Fee. Work without a permit.
108.7.1 Investigation. Whenever work for which a permit is required by this code has
been commenced without first obtaining a permit, a special investigation shall be made
before a permit may be issued for such work.
108.7.2 Fee. An investigation fee, in addition to the permit fee, shall be collected whether
or not a permit is subsequently issued. The investigation fee shall be equal to the amount
of the permit fee required by this code or the city fee schedule as applicable. The payment
of such investigation fee shall not exempt the applicant from compliance with all other
provisions of either this code or the technical codes nor from penalty prescribed by law.
108.8 Unauthorized cover up fee.
108.8.1 Anv work concealed without first obtaining the required inspection in violation of
section 109 shall be assessed a fee as established by the city fee schedule.
(Reason: This fee is not a fine or penalty but is designed to compensate for time and to remove
incentive to attempt to evade permits and code compliance. Language taken from former Uniform
Administrative Code.)
**Section 109.3.5; delete.
(Reason: Lath or gypsum board inspections are not normally performed in this area and that has
not caused problems.)
**Section 110.1; change to read as follows:
110.1 Use and occupancy. No building or structure shall be used or occupied, and no
change in the existing occupancy classification or occupant, either owner or tenant of a
building or structure or portion thereof shall be made until the building official has issued a
certificate of occupancy therefor as provided herein. Issuance of a certificate of
occupancy shall not be construed as an approval of a violation of the provisions of this
code or of other ordinances of the jurisdiction.
(Reason: Reflects regional policy and assists code officials track changes that affect building
safety.)
**Section 112.1 and 112.2; Amend as follows:
SECTION 112 BOARD OF APPEALS
R112.1 General. In order to hear and decide appeals of orders, decisions or
determinations made by the building official relative to the application and interpretation of
this code, there shall be and is hereby created a board of appeals. The building official
shall be an ex officio member of said board but shall have no vote on any matter before
the board. The board of appeals shall be appointed by the governing body and shall hold
office at its pleasure. The board shall adopt rules of procedure for conducting its business,
and shall render all decisions and findings in writing to the appellant with a duplicate copy
to the building official._The Building Board of Appeals as established by ordinance 622 as
amended, shall constitute the Board of Appeals referenced in this code
112.2 Limitations on authority. An application for appeal shall be based on a claim that
the true intent of this code or the rules legally adopted thereunder have been incorrectly
interpreted, the provisions of this code do not fully apply or an eaually good or better form
of construction is proposed. The board shall have no authority to waive reauirements of
this code.
(Reason: recognize appeal board previously established by ordinance.)
**Section 202; add a new definition to read as follows:
HIGH-RISE BUILDING is a building having floors used for human occupancy located
more than 55 feet (16 764 mm) or three stories above the lowest level of fire department
vehicle access.
(Reason: To define high-rise, as it influences sprinkler requirement thresholds based on the fire
fighting capabilities of the jurisdiction.)
**Section 304.1; add the following to the list of occupancies:
Fire stations
Police stations with detention facilities for 5 or less
(Reason: Clarify classification of these uses.)
**Section 403.1; change to read as follows:
403.1 Applicability. The provisions of this section shall apply to buildings having and
occupied floors located more than ~5 55 feet (~A 16 764 mm) above the lowest level
of fire department vehicle access.
(Reason: Consistent with amended definition of High Rise.)
**Section 403.1, exception #3; change to read as follows:
3. Open air portions of buildings ~+Id-Eris with an occupancy in Group A-5 in
accordance with Section 303.1
(Reason: To clarify enclosed portions of skyboxes and restaurants shall still be considered as high-
rise construction.)
**Section 403.2, exception #2; delete.
(Reason: To provide adequate fire protection to enclosed areas.)
**Section 404.1.1; amend definition of Atrium as follows:
ATRIUM. An opening connecting twe three or more stories ... {Balance remains
unchanged}
(Reason: Code is not consistent. Section 1019 permits unenclosed two story stairways under
certain circumstances.)
***Section 406.2.7 Change reference section as follows:
406.2.7 Mixed Separation. Parking garages shall be separated from other occupancies in
accordance with Section 505 508.
(Reason: Section 508 provides a more complete range of options for separation. Parking garages
are sometimes an incidental use and sometimes a separate occupancy.)
**Section 406.6.1; add a second paragraph to read as follows:
This occupancy shall include garages involved in servicing of motor vehicles for items
such as lube changes inspections windshield repair or replacement, shocks, minor part
replacement and other such non-major repair. When the repair garage is only involved in
such minor repair, it need not comply with Section 406.6.2.
(Reason: Correction to distinguish that service work is a repair garage as well to correspond with
definition in the IFC.)
***Section 501.2; Amend to read as follows:
501.2 Address numbers. Buildings shall have approved address numbers, building
numbers or approved building identification placed in a position that is plainly legible and
visible from the street or road fronting the property. T"°c° .,~~w,h°re ~h..n nnn+r.±c+.~ri+-,
~~`'.~ "^"'`. See Ordinance # 441 for specific addressing requirements.
(Reason: Call attention to addressing ordinance. Also matches amendment to IFC 505.1.)
**Section 506.2.2; add a sentence to read as follows:
In order to be considered as accessible, if not in direct contact with a street or fire lane, a
minimum 10-foot wide pathway from the street or approved fire lane must be provided.
(See International Fire Code Section 503.1.1 for hose lay measurement pathway
requirements.)
(Reason: To define what is considered accessible. Consistent with regional amendment to IFC
503.1.1.)
***Section 508.3.1 Exception #2: Change to read as follows:
Assembly areas that are accessory to Group E Occupancies are not considered separate
occupancies except when applying the assembly occupancy requirements of Chapters 10
and 11.
(Reason: The committee determined that the exiting requirements for Group A occupancies should
apply to assembly occupancies in schools.)
**Section 705.11; change the exception to read as follows:
Exception: For other than hazardous exhaust ducts penetrations by ducts and air
transfer openings of ... {remainder of exception unchanged}.
(Reason: To distinguish that hazardous exhaust ducts are a special case to be treated differently.)
*** 706.3.9; change to read as follows:
706.3.9 Fire areas. The fire barrier or horizontal assembly, or both,
separating a--s+r~-le-essupa~}~ occupancies into different fire areas shall have afire-
resistance rating of not less than that indicated in Table 706.3.9 for a single occupancy and
the most restrictive value indicated in Table 706 3 9 shall apply to the entire building or portion
thereof for a mixed occupancy
(Reason: To address and to clearly define the minimum value of fire barriers separating mixed
occupancies fire areas. The term "Fire Area" with respect to IBC application serves to define the
boundaries for sprinkler system and fire protection requirements set in chapter 9 based on the square
footage and occupant load of the fire areas. Section 706.3.9 provides an option to reduce single
occupancy fire areas by providing fire barriers as indicated in Table 706.3.9. "Mixed occupancy fire
areas separation" as used in this code is unclear. The designers may have an option of using
separated occupancies Section 508.3.3 and Table 508.3.3 however this Table does not provide fire
barrier separation values for all occupancies. This clarification is needed specifically innon-sprinklered
existing buildings which undergo a change in use which may result in an increase of occupant load or
placing the use in a different occupancy group in orderto eliminate interpretations which may prohibitor
incorrectly establish the value of the fire barrier separating mixed occupancies fire areas.)
**Section 707.2; delete items 7.4 and 7.5 and renumber the remainder as follows:
7. In other than Groups I-2 and I-3, a shaft enclosure is not required for a floor opening or
an air transfer opening that complies with the following:
7.1. Does not connect more than two stories.
7.2. Is not part of the required means of egress system, except as permitted in
Section 1020.1.
7.3. Is not concealed within the building construction.
7.4 Is separated from floor openings and air transfer openings serving other
floors by construction conforming to required shaft enclosures.
7.5 Is limited to the same smoke compartment.
(Reason: To be consistent with regionally accepted practices.)
10
**Section 716.5.2; add exception #4 to read as follows:
716.5.2 Fire barriers.
Duct and air transfer openings of fire barriers shall be protected with approved fire dampers
installed in accordance with their listing.
Exception: Fire dampers are not required at penetrations of fire barriers where any of
the following apply:
1. Penetrations are tested in accordance with ASTM E119 as part of the fire-
resistance-rated assembly.
2. Ducts are used as part of an approved smoke control system in accordance with
Section 909.
3. Such walls are penetrated by ducted HVAC systems, have a required fire-
resistance rating of 1 hour or less, are in areas of other than Group H and are in
buildings equipped throughout with an automatic sprinkler system in accordance with
Section 903.3.1.1 or 903.3.1.2. For the purposes of this exception, a ducted HVAC
system shall be a duct system for conveying supply, return or exhaust air as part of
the structure's HVAC system. Such a duct system shall be constructed of sheet steel
not less than 26 gage thickness and shall be continuous from the air-handling
appliance or equipment to the air outlet and inlet terminals.
4. In the duct penetration of the separation between the private garage and its
residence when constructed in accordance with Section 406.1.4, exception #2.
(Reason: To exclude specific penetration from fire damper requirements.)
**Section 903.2.8.3; Add section to read as follows:
903 2.8.3. Self-service storage facility. An automatic sprinkler system shall be installed
throughout all self-service storage facilities.
Exception: One-story self-service storage facilities that have no interior corridors,
with aone-hour fire barrier wall installed between every storage compartment.
(Reason: Consistent with regional practice, reduces hazard of occupancies that often have
unknown contents.)
**Section 903.2.10; amend title and 903.2.10.3 and add 903.2.10.4 thru 903.2.10.6 as
follows:
903.2.10 All occupancies except groups R-3 and U. An
automatic sprinkler system shall be installed in the locations set forth in Sections
903.2.10.1 through 903.2.10.1.3.
(Reason: Current title of windowless stories in all occupancies does not currently cover all the
subsections listed and referenced.)
903.2.10.3 Buildings over as 35 feet in height. An automatic sprinkler system shall be
installed throughout buildings with a floor level, other than penthouses in compliance with
Section 1509, that is located a5 35 feet (4~4 10
668mm) or more above the lowest level of fire department vehicle access.
Exceptions:
2. Open parking structures in compliance with Section 406.3.
(Reason: Lower height threshold for sprinklers reduces demands on fire fighters.)
11
903.2.10.4 High-Piled Combustible Storage For ant/ building with a clear height
exceeding 12 feet (4572 mm) see Chapter 23 of the International Fire Code to determine
if those provisions apply.
(Reason: Reference to Fire Code for special conditions.)
903.2.10.5 Sprat/ Booths and Rooms. New and existing spray booths and spraying
rooms shall be protected by an approved automatic fire-extinauishing system
(Reason: Reflects local practices. Consistent with regional amendments to IFC 903.2.10 and
903.2.10.5)
903.2.10.6 Buildings Over 6 000 sg. ft An automatic sprinkler system shall be installed
throughout all buildings over 6 000 sg ft For the purpose of this provision fire walls shall
not define separate buildings. For this section only area measurement shall be based on
outside dimensions of exterior walls exclusive of vent shafts and courts without deduction
for corridors, stairways, closets the thickness of interior walls columns or other features
The floor area of a building or portion thereof not provided with surrounding exterior walls
shall be the usable area under the horizontal projection of the roof or floor above The
gross floor area shall not include shafts with no openings or interior courts For upper level
attic type rooms, areas where the ceilina height is less than five feet (5' 0") shall not be
considered. Unfinished space framed to permit future expansion of floor area shall be
considered as part of the area. Joists designed to support floor loads shall be assumed to
be for future area.
Exception: Open parking aarages in compliance with Section 406 3
(Reason: Lower area threshold for sprinklers reduces demand on fire fighters. Detail added to
explain more precisely how areas are to be figured.)
**Section 903.3.1.1.1; amend as follows:
903.3.1.1.1 Exempt locations. When approved by the fire code official automatic
A~tee~t+s sprinklers shall not be required in the following rooms or areas where such .. .
{bulk of section unchanged} ...because it is damp, of fire-resistance-rated construction or
contains electrical equipment.
1. Any room where the application of water, or flame and water, constitutes a serious life
or fire hazard.
2. Any room or space where sprinklers are considered undesirable because of the nature
of the contents, when approved by the building official.
3: Generator and transformer rooms under the direct control of a public utility separated
from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies
having afire-resistance rating of not less than 2 hours.
~~ nwrrc°cr~i-~c.°r.
(Reason: Individual approval of exceptions allows code official to consider individual
circumstances.)
**Section 903.3.5; add a second paragraph to read as follows:
Water supply as required for such systems shall be provided in conformance with the
supply requirements of the respective standards however every fire protection system
shall be designed with a 10 psi safety factor.
(Reason: To define a uniform safety factor and to allow for seasonal changes to water pressure.)
12
**Section 903.4; add a second paragraph after the exceptions to read as follows:
Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to
the sprinkler system and shall cause an alarm upon detection of water flow for more than
45 seconds. All control valves in the sprinkler and standpipe systems except for fire
department hose connection valves shall be electrically supervised to initiate a supervisory
signal at the central station upon tampering.
(Reason: To avoid significant water losses. Consistent with amendment to section 905.9)
**903.4.2 -Add second paragraph to read as follows:
The alarm device required on the exterior of the building shall be a weatherproof
horn/strobe notification appliance with a minimum 75 candela strobe rating, installed as
close as practicable to the fire department connection.
(Reason: Fire department connections are not always located at the riser, this allows the fire
department faster access.)
**Add Section 903.6 to read as follows:
903.6 Spray booths and rooms. New and existing spray booths and spray rooms shall be
protected by an approved automatic fire-extinguishing system in accordance with Section
1504.
(Reason: Consistent with amendment to IFC 1504.)
**Section 905.2; change to read as follows:
905.2 Installation standards. Standpipe systems shall be installed in accordance with
this section and NFPA 14. Manual dry standpipe systems shall be supervised with a
minimum of 10 psiq and a maximum of 40 psiq air pressure with ahigh/low alarm.
(Reason: To define manual dry standpipe supervision requirements.)
***Add Section 905.3.8: Building Area.
905.3.8: Building Area. In buildings exceeding 10,000 square feet in area per story,
Class I automatic wet or manual wet standpipes shall be provided where any portion of the
building's interior area is more than 200 feet (60960 mm) of travel, vertically and
horizontally from the nearest point of fire department vehicle access.
Exception: Automatic dry and semi-automatic dry standpipes are allowed as
provided for in NFPA 14.
(Reason: Allows for the rapid deployment of hoselines to the body of the fire.)
**Section 905.4, item #5; change to read as follows:
5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-
percent slope), each standpipe shall be provided with an approved hose connection
located either ... {remainder of paragraph unchanged} .. .
(Reason: Clarity. Consistent with regional amendment to IFC 905.4.)
13
**Section 905.9; add a second paragraph after the exceptions to read as follows:
Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to
the sprinkler system and shall cause an alarm upon detection of water flow for more than
45 seconds. All control valves in the sprinkler and standpipe systems except for fire
department hose connection valves shall be electrically supervised to initiate a supervisory
signal at the central station upon tampering_
(Reason: To avoid significant water losses. Consistent with regional amendment to IFC 905.9.)
***Add Section 907.1.3 to read as follows:
907.1.3 Design Standards. All alarm systems new or replacement serving 20 or more
alarm actuating devices shall be addressable fire detection systems Alarm systems
serving more than 40 smoke detectors or more than 100 total alarm activating devices
shall be analog intelligent addressable fire detection systems
Exception: Existing systems need not comply unless the total building remodel or
expansion initiated after the effective date of this code as adopted exceeds 30% of the
building. When cumulative building remodel or expansion exceeds 50% of the building
must comply within 18 months of permit application
(Reason: Consistent with local practice. Consistent with regional amendment to IFC 907.1.3.)
*Section 907.2.1 change to read as follows:
907.2.1 Group A. A manual fire alarm system shall be installed in Group A occupancies
having an occupant load of 300 or more persons or more than 100 persons above or
below the lowest level of exit discharge. Portions of Group E occupancies occupied for
assembly purposes shall be provided with a fire alarm system as required for the Group E
occupancy. (Exception to remain.)
(Reason: Increases the requirement is changed to be consistent with Group B requirement.)
**Section 907.2.3; change to read as follows:
907.2.3 Group E. A manual fire alarm system shall be installed in Group E educational
occupancies. When automatic sprinkler systems or smoke detectors are installed, such
systems or detectors shall be connected to the building fire alarm system. An approved
smoke detection system shall be installed in Group E day care occupancies Unless
separated by a minimum of 100' open space all buildings whether portable buildings or
the main building, will be considered one building for alarm occupant load consideration
and interconnection of alarm systems.
(Reason: To distinguish educational from day care occupancy minimum protection requirements.
Further, to define threshold at which portable buildings are considered a separate building for the
purposes of alarm systems. Consistent with regional amendment to IFC 907.2.3.)
**Section 907.2.3; change exception #1 and add exception #1.1 added to read as
follows:
1. Group E educational and day care occupancies with an occupant load of less
than 50 when provided with an approved automatic sprinkler system.
14
1 1 Residential In-Home day care with not more than 12 children may use
interconnected single station detectors in all habitable rooms. (For care of
more than five children 2 1/2 or less years of age, see Section 907.2.6.)
(Reason: Consistent with Texas State laws concerning day care facility requirements. Consistent
with regional amendment to IFC 907.2.3.)
**Section 907.2.12; change to read as follows:
907.2.12 High-rise buildings. Buildings having ~ floors used for human occupancy
located more than ~5 55 feet (2~-86916 764 mm) or three stories above the lowest level of
fire department vehicle access shall be provided with an automatic fire alarm system and an
emergency voice/alarm communications system in accordance with Section 907.2.12.2.
(Reason: To correct per definition of high-rise. Consistent with regional amendment to IFC
907.2.12.)
**Section 907.2.12, exception #3; change to read as follows:
3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1, when used
for open air seating' however this exception does not apply to accessory uses including but
not limited to sky boxes restaurants and similarly enclosed areas.
(Reason: To indicate that enclosed areas within open air seating type occupancies are not excepted
from automatic fire alarm system requirements. Consistent with regional amendment to IFC 907.2.12.)
**Section 907.4; add a second paragraph to read as follows:
907.4 Power supply. The primary and secondary power supplies for the fire alarm system
shall be provided in accordance with NFPA 72. Manual alarm actuating devices shall be an
approved double action type.
(Reason: Consistent with local requirements.)
**Add Section 907.5.1 to read as follows:
907 5 1 Installation.. All fire alarm systems shall be installed in such a manner that a
failure of any single initiating device or single open in an initiating circuit conductor will not
interfere with the normal operation of other such devices. All initiating circuit conductors
shall be Class "A" wired with a minimum of six feet separation between supply and return
circuit conductors. IDC -Class "A" Style D• SLC -Class "A" Style 6; NAC -Class "B" Style
Y The IDC from an addressable device used to monitor the status of a suppression
system may be wired Class B Style B provided the distance from the addressable device
is within 10-feet of the suppression system device.
(Reason: To provide uniformity in system specifications and guidance to design engineers.
Consistent with regional amendment to IFC 907.6.1.)
**Section 907.8.2; change to read as follows:
907.8.2 High-rise buildings. In buildings that have floors located more than ~5 55 feet (~
868 16 764 mm) or three stories above the ... {remainder of section unchanged}.
(Reason: Consistent with high rise definition as amended.)
15
***Section 910.1; Amend exception 2 to read as follows:
910.1 General. Where required by this code or otherwise installed, smoke and heat vents,
or mechanical smoke exhaust systems, and draft curtains shall conform to the
requirements of this section.
Exceptions:
1. Frozen food warehouses used solely for storage of Class I and II commodities
where protected by an approved automatic sprinkler system.
2: Where areas of buildings are equipped with early suppression fast-response
(ESFR) sprinklers,. only manual smoke and heat vents shall be required within
these areas.
(Reason: Allows the fire department to control the smoke and heat during and after a fire event.)
***Section 910.2.4; Add Section 910.2.4 Group H, to read as follows:
910.2.4 Group H. Buildings and portions thereof used as a Group H occupancy as
follows:
1. In occupancies classified as Group H-2 or H-3 any of which are more than 15 000
square feet (1394 m2) in single floor area
Exception: Buildings of noncombustible construction containing only noncombustible
materials.
2. In areas of buildin sin Grou H used for storin Class 2 3 and 4 li uid and solid
oxidizers, Class 1 and unclassified detonable organic peroxides Class 3 and 4 unstable
reactive) materials, or Class 2 or 3water-reactive materials as required for a high hazard
commodity classification.
Exception: Buildings of noncombustible construction containing only noncombustible
materials.
(Reason: Maintain the current level of protection as outlined in the 2003 Code.)
***Table 910.3; Change the title of the. first row of the table to read as follows:
[F] TABLE 910.3
REQUIREMENTS FOR DRAFT CuRTews eNn ciunK~ eun uoeT vo~iTe
OCCUPANCY
DESIGNATED - ----
MINIMUM - ----.....__...--
MAXIMUM -......._,-.......~.,
VENT- , .".,tea
MAXIMUM
MAXIMUM
GROUP AND STORAGE DRAFT AREA AREATO- SPACING OF DISTANCE TO
COMMODITY HEIGHT CURTAIN FORMED BY FLOOR-AREA VENT VENTS FROM
CLASSIFICATION (feet) DEPTH DRAFT RATIOS CENTERS WALL OR
(feet) CURTAINS (feet) DRAFT
(square feet) CURTAINSn
(feet)
Group F-1 H - 0.2 H d 50,000 1:100 120 60
and S-1 but >_ 4
(Balance of
table remains
unchanged)
froornores remain uncnangeat
(Reason: Consistency with the amendment 910.2.4 to include Group H)
***Section 910.3.2.2; Add second paragraph to read as follows:
The automatic operating mechanism of the smoke and heat vents shall operate at a
temperature rating at least 100 degrees (F) (approximately 38 degrees Celsius) greater
16
than the temperature rating of the sprinklers installed.
(Reason: Specifies a temperature range at which smoke and heat vents should activate in
sprinklered buildings to ensure that the sprinkler system has an opportunity to activate and control
the fire prior to vent operation. The intent is to allow the sprinkler system to operate prior to allowing
the smoke and heat vents to operate so as not to pose a detriment to the operation of the sprinkler
system. This follows recommendations indicated in NFPA 204, Section F.3 with regards to Design
Considerations of smoke and heat vents in sprinklered buildings. Full scale fire testing results have
shown that smoke and heat venting is potentially detrimental to the proper operation of the sprinkler
system when vents are open prior to sprinkler activation. This was a primary reason for removing
smoke and heat venting requirements with regards to ESFR sprinkler systems in Article 23 of the
IFC for high-piled storage.)
***Section 1004.1.1; Delete exception as follows:
1004.1.1 Areas without fixed seating. The number of occupants shall be computed at
the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas
without fixed seating, the occupant load shall not be less than that number determined by
dividing the floor area under consideration by the occupant per unit of area factor assigned
to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in
Table 1004.1.1, the building official shall establish a use based on a listed use that most
nearly resembles the intended use.
(Reason: Consistent with local practice.)
**Section 1020.1.7; change to read as follows:
1020.1.7 Smokeproof enclosures. In buildings required to comply with Section 403 or 405,
each of the exits of a building that serves ~ s st r where the floor surface is located
more than 75 55 feet (~9 16 764 mm) above the lowest level of fire ... {remainder of
section unchanged}.
(Reason: Consistent with high rise definition as amended and clarify only one floor need be above the
threshold.)
Section 1101.2; add an exception to read as follows:
Exception: Buildings regulated under State Law and built in accordance with State
certified plans including any variances or waivers granted by the State, shall be
deemed to be in compliance with the requirements of this Chapter.
(Reason: To accommodate buildings regulated under Texas State law.)
**Section 1109.2.1; change to read as follows:
1109.2.1 Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an
accessible unisex toilet room shall be provided where an aggregate of six or more male
and female water closets are r° provided. In buildings of mixed occupancy, only
those water closets required for the assembly or mercantile occupancy shall be used to
determine the unisex toilet room requirement. In recreational facilities where separate-sex
bathing rooms are provided, an accessible unisex bathing room shall be provided. Fixtures
17
located within unisex toilet and bathing rooms shall be included in determining the number
of fixtures provided in an occupancy.
Exception: Where each separate-sex bathing room has only one shower or
bathtub fixture, a unisex bathing room is not required.
(Reason: Amendment is necessary to coincide with amendments in IBC Chapter 29.)
**Section 1210.2, exception #2; change to read as follows:
2. Toilet rooms that are not accessible to the public and which have not more than
one water closets provided that walls around urinals comply with the minimum
surrounding material specified by Section 419 3 of the International Plumbing
Code.
(Reason: Recognize the minimum wall material requirements of the IPC. Consistent with regional
amendment to IPC 419.3.)
**Table 1505.1; replace footnotes b and c with the following:
b.
the'.°wd°^y e~^° ^f +"° ~^^f All individual replacement shingles or shakes shall be in
compliance with the rating required by this table
c.
~~ ~nr! AI^ 1 ~"~~ Non-classified roof coverings shall be permitted on buildings of
U occupancies having not more than 120 sg ft of projected roof area When exceedina
120 sg.ft of projected roof area buildinas of U occupancies may use non-rated non
combustible roof coverings.
(Reason: Conforms to local practice affording increased fire protection.)
**Section 1507.8.1 and 1507.8.1.1; change deck requirement as follows:
1507.8.1 Deck requirements. Wood shingles shall be installed on solid eFSpased
sheathing.
0 0
(Reason: Solid sheathing makes roof replacement easier. In event of a roof fire less air is
available to the fire.)
**Section 1507.9.1 and 1507.9.1.1; change deck requirement as follows:
1507.9.1 Deck requirements. Wood shakes shall only be used on solid eF-spaced
sheathing.
. .,
18
0 0
(Reason: Solid sheathing makes roof replacement easier. In event of a roof fire less air is
available to the fire.)
**Section 1612.3; Insert name as follows:
1612.3 Establishment of flood hazard areas. To establish flood hazard areas, the
governing body shall adopt a flood hazard map and supporting data. The flood hazard
map shall include, at a minimum, areas of special flood hazard as identified by the Federal
Emergency Management Agency in an engineering report entitled "The Flood Insurance
Study for The City of Southlake, Texas," as amended or revised with the accompanying
Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map (FBFM) and
related supporting data along with any revisions thereto. The adopted flood hazard map
and supporting data are hereby adopted by reference and declared to be part of this
section.
**Add Section 2308.2.3 to read as follows:
2308.2.3 Application to engineered design. When accepted by the Building Official,
any portion of this section is permitted to apply to buildings that are otherwise outside the
limitations of this section provided that:
1. The resulting design will comply with the requirements specified in Chapter 16;
2. The load limitations of various elements of this section are not exceeded; and
3. The portions of this section which will apply are identified by an engineer in the
construction documents.
(Reason: Allows engineer to reference Section 2308 for designs for wood structures; eliminates
excessive engineering.)
**Section 2901.1; add a sentence to read as follows:
The provisions of this Chapter are meant to work in coordination with the provisions of
Chapter 4 of the International Plumbing Code. Should any conflicts arise between the two
chapters the Building Official shall determine which provision applies.
(Reason: Gives building official discretion.)
** Section 2902.1; change to read as follows:
2902.1 Minimum number of fixtures. Plumbing fixtures shall be provided for the type of
occupancy and in the minimum number as follows:
1. Assembly Occupancies: At least one drinking fountain shall be provided at
each floor level in an approved location.
Exception: A drinking fountain need not be provided in a drinking or dining
establishment.
2. Groups A, B, F, H, I, M and S Occupancies: Buildings or portions thereof
where persons are employed shall be provided with at least one water closet for
each sex except as provided for in Section 2902.2.
3. Group E Occupancies: Shall be provided with fixtures as shown in Table
2902.1.
19
4. Group R Occupancies: Shall be provided with fixtures as shown in Table
2902.1.
It is recommended, but not required that the minimum number of fixtures provided also
comply with the number shown in Table 2902.1. Types of occupancies not shown in
Table 2902.1 shall be considered individually by the ~+1 code official. The number of
occupants shall be determined by this code. Occupancy classification shall be determined
in accordance with Chapter 3.
(Reason: To allow flexibility for designer to consider specific occupancy needs.)
"`Section 2902.6; add an exception to read as follows:
2902.1.2 Finish material. Finish materials shall comply with Section 1210
(Reason: Call attention to related requirement)
***Section 3109.1; add a section to read as follows:
3109.1 General. Swimming pools shall comply with the requirements of this section and
other applicable sections of this code. Provisions of this section shall not be deemed to
nullify any provisions of state law or state code
(Reason: to recognize "state requirements')
**Section 3403.1.2 and 3403.1.3; add the following subsections:
Section 3403.1.2. For additions where chapter 9 of this code or the Fire Code require
structures to have fire protection system(s) such systems installed throughout the
building, both existing and new portions.
Section 3403.1.3. Alterations shall not require fire protection systems be added due to area
limits specified in chapter 9 of this code or the Fire Code (For change of occupancy see
section 3406.)
(Reason: to clarify application of fire protection requirements for additions or remodeling conditions.)
**Section 3410.2; Fill in the blank as follows:
3410.2 Applicability. Structures existing prior to annexation into the city limits or constructed
within the city prior to June 20, 1978 , in which there is work involving additions, alterations or
changes of occupancy shall be made to conform to the requirements of this section or the
provisions of Sections 3403 through 3407. The provisions in Sections 3410.2.1 through
3410.2.5 shall apply to existing occupancies that will continue to be, or are proposed to be, in
Groups A, B, E, F, M, R, S and U. These provisions shall not apply to buildings with
occupancies in Group H or I.
(Reason: To properly address buildings constructed without any regulating codes or inspections.)
**Section H101.1: add the following paragraph:
The sign ordinance of the City of Southlake is not changed by this chapter This chapter is intended to
only provide the structural standards for signs. In any conflict the sign ordinance shall take
precedence.
20
**SectionJ103.2: amend the exemptions as follows:
J103.2 Exemptions.
A grading permit shall not be required for the following:
1. Grading in an isolated, self-contained area, provided there is no danger to the
public, and that such grading will not adversely affect adjoining properties when
approved by the Building Official.
2. Excavation for construction of a structure permitted under this code.
3. Cemetery graves.
/I C?ofllco rlicnne~I ci~oc nnn4rnllerl by n~her renlll•~~innc
~. Cvn•~~i•~+innc. fnr ~.~ell~ nr 4ronnhe~ fnr 114ili~icc~
,
y. AA~n~, ry1~J1 rv~~~l nr~??ypp~,~,4Lny~~-nnlr c~ni-1 nro~icl
1
1 1
r~rnnor4icc
Pr°P~T"~T
7 nlnr~~nni py n~~i~4inn~ norfnrmorl llnrlor +he rJir Sinn of ~ renic•~ i'loeinn
T. 'r7TVTUiVT~T GTI'VTTfTGQ-QTTQ~Tri G~C7V7T'GTCTTG~T~•TCGT~.r~F~~l'7
11 11 '
f
nl Irnn~o of nror~~rinn ~ ~nil~ ronnr~ ~
Exemption from the permit requirements of this appendix shall not be deemed to grant
authorization for any work to be done in any manner in violation of the provisions of this
code or any other laws or ordinances of this jurisdiction.
END OF AMENDMENTS.
21
INVOICE Preview
Star-Telegram Customer ID: CIT57
400 W. 7TH STREET Invoice Number: 294286591
FORT WORTH,TX 76102 RECEIVED
(817)390-7761 Invoice Date: 2/16/2008
Federal Tax ID 22-3148254 Terms: Net due in 21 days
MAR — 3 2008 Due Date: 2/29/2008
Bill To: PO Number: no po
CITY OF SOUTHLAKE OFFICE OF CITY SECRETARY Order Number: 29428659
1400 MAIN ST
STE 440 Sales Rep: 073
SOUTHLAKE, TX 76092-7604 Description: CITY OF SOUTHLA
Attn Attn: STEVE MOORS Publication Date: 2/16/2008
Description Location Col Depth Linage MU Rate Amount
CITY OF SOUTHLAKE Notice is he 13580 1 113 113 LINE $0.81 $91.53
Sales Discount ($5.00)
Misc Fee $5.00
Net Amount: $91.53
i'•r JMCOMSSONE
'IRES Fop .�
,' ,'= July31, 1": I• 2 6 2O08
',A_?;',.
r _J
THE STATE OF TEXAS
County of Tarrant
Before me,a Notary Public in and for said County and State,this day personally appeared Deborah Baylor, Bid and Legal Coordinator for the Star-
Telegram,published by the Star-Telegram, Inc.at Fort Worth,in Tarrant County,Texas;and who,after being duly sworn,did depose and say that the
attached clipping of an advertisement was published in th bove named paper on the listed dates: BIDS&LEGAL DEPT. STAR TELEGRAM
(817)390-7501
Signed . ..ii,\ c illi:_____ _ `- \
SUBSCRIBED AND SWORN TO BEFORE ME,THIS Tuesday, F.• ••,�008. /
�� /
Notary Public ../1_, 1_1 _ Al‘
_ ��:_���� L�
Thank You For Your Payment
Remit To: Star-Telegram Customer ID: CIT57
P.O. BOX 901051 Customer Name: CITY OF SOUTHLAKE
FORT WORTH, TX 76101-2051 Invoice Number: 294286591
Invoice Amount: $91.53
PO Number: no po
Amount Enclosed: $
00 1
CITY
OF SOUTHLAKE
Notice is hereby given
by the City Council
of the City of
Southlake, Texas,
that a public hearing
will be held on March
4, 2008,at 5:00 p.m.
or immediately fol-
lowing the Work'
Session, during the I
Regular City Council
in the
meeting
to bCounce il
Chambers of Town
Hall, 1400 Main
Street, Southlake,
Texas. Purpose of
the public hearing is
to consider the sec-
ond reading of the
foil ORDINANCE ordinance:
NO. 930
AN ORDINANCE
EDIT 2006
ON ADOPTING OFE THE
INTERNATIONAL
BUILDING CODE
REGULATING THE
ERECTION,
CON-
STRUCTION, EN-
LARGEMENT, AL-
REPAIR
MOVING,N� REMOV-
AL, DEMOLITION,
CONVERSION, OC-
CUPANCY, EQUIP-
MENT,
HEIGHT, AREA AND
MAINTENANCE OF
ALL BUILDINGS OR
STRUCTURES, EX-
CEPT ONE- AND
DWELLINGS MI AND
MULTIPLE SINGLE-
FAMILY DWELL-
THE(TOWNHOUSES),O ES), INF
SOUTHLAKE; PRO-
ADOPTHE
TIONG FOR OF LO-
CAL AMENDMENTS
THERETO;
PROVID-
ING FOR RECORD-
ING OF SUCH CODE
REC-
ORD; PUBLIC PROVIDING
THAT THIS ORDI-
NANCE SHALL BE
CUMULATIVE ORDINANCES;
PROVIDING A SEV-
ERABILITY CLAUSE;
PROVING FOR A
PENALDTIY FOR VIO-
PROVOID NGHEREOF;A SAV-
INGS CLAUSE;
PROVIDING FOR
PUBLICATION IN
PAMPHLET FORM;
PROVIDING FOR
PUBLICATION
THE OFFICIAL
NEWSPAPER; AND
PROVIDING AN EF-
FECTIVE DATE.
SECTION 6 }1
Any person, firm or ,l_\+`��\�
corporation whoo y��
vi-
olates, disobeys, �/v_.`
omits. neglects or
refuses to comply FEB (.r i
with or who resists 2 the enforcement of i��
any of the provisions G }r
of this ordinance X14 U
shall be fined not
7.
more than Two
Thousand Dollars ($
2,000.00) for any'
violation involving
zoning,fire safety or
public health and
sanitation, including
dumping or refuse,
and shall be fined not
more than five hun-
dred dollars ($500)
for any other viola-
tion of this ordi-
nance.Each day that
a is er-
mittedation to exist shall
constitute a sepa-
rate offense.
City of Southlake
Lori Payne
rir., c o,rornry
INVOICE Preview
Star-Telegram Customer ID: CIT57
400 W.7TH STREET e r v �D Invoice Number: 294874851
FORT WORTH,TX 76102
(817)390-7761 r,+ �•
00� Invoice Date: 3/9/2008
Federal Tax ID 22-3148254 R C Y V Terms: Net due in 21 days
Due Date: 3/31/2008
Bill To: 2008 PO Number: no po
CITY OF SOUTHLAKE MAR 2 0
1400 MAIN ST Order Number: 29487485
STE 440 Cn\I� -C `r. 0: r!TY S'r'RETARY Sales Rep: 073
SOUTHLAKE, TX 76092-76eK, I I I " Description: CITY OF SOUTHLA
Publication Dates: 3/7/2008 -3/9/2008
Description AmmLocation Col Depth Linage MU Rate Amount
CITY OF SOUTHIII MMONIMINIII
-
CITY OF SOUT1 ORDINANCE NO. 930 Legal Notices
LAKE
AN ORDINANCE l ��`� ��8 I.INL $0.42 $82.88
ADOPTING THE 2006 more than Two,
EDITION OF THE Thousand Dollars,
INTERNATIONAL ($2,000.00) for any
Sales Discount BUILDING CODE, violation involving ($5.00)
REGULATING THE zoning,fire safety or
ERECTION, CON- panic dumping
ion, ncthluding
and
STRUCTION, AL- and hall berfi refuse,d not $5.00
Misc Fee LARGEMENT,, AL-
TERATION, REPAIR, more than five hun-
MOVING, REMOV- dred dollars ($500)
AL, DEMOLITION, for any other viola-
CONVERSION, OC- tion of this ordi-
CUPANCY, EQUIP- Hance.Each day that
HEIGHT US AREA ANED a violation is per-
MAINTENANCE OF matted to exist shall Net Amount: $82.88
ALL BUILDINGS OR constitute a sepa-
STRUCTURES, EX- rate offens
AP-
CEPT ONE- AND PASSED AND TWO-FAMILY PROVEDY THIS THE
DWELLINGS AND 20 DAD DURINGF MARCH,
MULTIPLE SINGLE- REGULAR CITYTY
FAMILY DWELL- N
I N G S COUNCIL MEETING.
(TOWNHOUSES), IN MAYOR: Andy
THE CITY OF ATTEST:Wambsganss _ .
SOUTHLAKE; PRO- C City Secretary Payne,Lori Ys Y.
VIDING FOR THE ____r ?'• '�(.+, CHRISTY L.HOLLAND
ADOPTION OF LO- - -- *: MY COMMISSION EXPIRES
CAL AMENDMENTS 'THERETO; PROVID- • 1:, July31,2008
ING FOR RECORD- '''t.,r... .
ING OF SUCH CODE
AS A PUBLIC REC- .1,... a--
THE STATE OF ORD; PROVIDING
THAT THIS ORDI-
County of Tarra NANCE SHALL BE
CUMULATIVE OF
ALL ORDINANCES;
Before me,a Ni ERABILLITY CLAUSE;said County and State,this day personally appeared Deborah Baylor, Bid and Legal Coordinator for the Star-
Telegram,publi PENALDTIY FOFR°vlo tram, Inc.at Fort Worth,in Tarrant County,Texas;and who,after being duly sworn,did depose and say that the
attached clippin PROVIID NG HEREOF;was published in the::eve named paper on the listed dates:BIDS&LEGAL DEPT. STAR TELEGRAM
(817)390-7501 INGS CLAUSE;
PROVIDING FOR
PUBLICATION IN
PAMPHLET FORM; ' bAtk
r'
PROVIDING FOR Signed _ .I� —A__ _'.r
PUBLICATION IN
THE OFFICIAL
SUBSCRIBED NREWSPAPER;WIP NG ANA :ORE ME,THIS Wednesday, / / 008.
EF-
FECTIVE DATE. //
SECTION 6 /
Any person, firm or Notary Public / • I0
corporation who vi-
olates, disobeys,
omits. neglects or
refuses to comply
with or who resists
the enforcement of
any of the provisions
of this ordinance
shall be fined not
Thank You For Your Payment
Remit To: Star-Telegram Customer ID: CIT57
P.O. BOX 901051 Customer Name: CITY OF SOUTHLAKE
FORT WORTH, TX 76101-2051 Invoice Number: 294874851
Invoice Amount: $82.88
PO Number: no po
Amount Enclosed: $